Advantage LogoMegaTron
Controller
Supplemental
Manual
BACnet H22 / H26
Communications

BACnet Introduction

The MegaTron controller is capable of connecting to the WebAdvantage Server and most Building Management Systems. The WebAdvantage service requires a gateway to the internet with firewall and security rules in place. The Building Management System needs to be on the same subnet to properly receive traffic from the MegaTron. This may require some advanced routing of network traffic within the network wiring or programming of advanced switching equipment. The datatraffic for both is provided via the same Ethernet cable coming from the MegaTron.
The BACnet protocol allows interfacing with more customizable PC applications using HMI/SCADA and stand-alone HMI systems

BACnet Overview

BACnet is an American National Standard. The BACnet protocol allows the creation of an automation and controls system which may interoperate with other BACnet systems. In BACnet terms, interoperate means that two or more BACnet-speaking computer systems may share the same communications networks, and ask each other to perform various functions on a peer-to-peer basis.
BACnet’s flexibility has two important benefits: vendor-independence and forward-compatibility with future generations of systems. This is accomplished using an object-oriented approach for representing all information within each controller. Since BACnet is based on standards, it provides maximum benefits for both the vendor who designs BACnet systems, and the specifier or owner of those systems.

Protocal Implementation Conformance Summary (Annex-A)

Applications Software Version: JA.16.0 and higher
Firmware Revision: JA.16.0 and higher
BACnet Protocol Revision: 6
BACnet Standardized Device Profile (Annex L): BACnet Application Specific Controller (B-ASC)
BACnet Interoperability Building Blocks Supported (Annex K):

  • DS-RP-B
  • DM-DDB-B
  • DM-DCC-B
  • DM-RD-B

Standard Object Types Supported: See table 3-1 “Object/Property Support Matrix”.
Data Link Layer Options: BACnet IP, (Annex J)
Character Set Supported: ANSI X3.4

Connecting to BACnet enabled MegaTron

This guide is designed to help with connecting a BACnet enabled MegaTron to a local BMS.
Note: Screens may vary slightly between models.Advantage Controls H22 MegaTron Controller - MegaTronStep 1:
Press Setup/Run, CONFIGURE, NETWORK, SETTINGS.
(See figures 1, 2, 3 and 4. H26 dual cards add figure 3B. H26 only available for MegaTron MT.)
Step 2:
Press BAC. (See figure 4.) Note: If these options are not visible, the dual network card needs to be enabled. See enabling dual network card to continue setup.
Step 3:
Enter the DEVICE INSTANCE and PORT. Press Enter to accept on each. (See figure 6.)
Step 4:
Press RESET and then press Enter to accept. The communications card will reset after a short countdown. (See figures 7 and 8.)
Step 5:
After the communications card has been reset cycle power to the controller.

MegaTron XS Setup

Advantage Controls H22 MegaTron Controller - MegaTron XS Setup

The MegaTron XS will be a “device object” on the particular BACnet network. Each device object (your MegaTron XS) must have an object identifier that is unique network wide. The device object instance number is normally configured on site after the device is installed. The device object instance number range is between 0 and 4194303. Note that 4194303 is known as “unconfigured” and is not really a valid device instance number. All devices are required to respond with their own Device object instance number when 4194303 is requested.
To enter your device object identifier, go to the Configure menu in the MegaTron XS and select the Network settings. Then select BAC.

Object Definitions

Object / Property Support Matrix (Table 1-1)

PropertyObject Type
DeviceBinary InputBinary ValueAnalog InputAnalog ValueMulti-State Value
Object Identifier??????
Object Name??????
Object Type??????
Description??????
System Status?
Vendor Name?
Vendor Identifier?
Model Name?
Firmware Revision?
App. Software Revision?
Protocol Version?
Protocol Revision?
Services Supported?
Object Types Supported?
Object List?
Max APDU Length?
Segmentation Support?
APDU Timeout?
Number APDU Retries?
Database Revision?
Present Value?????
Status Flags?????
Event State?????
Out-of-Service?????
Units??
Polarity??
Number of States?
State Text?

Binary Input Object Instance Summary (Table 1-2)

Instance IDObject NamePurposePresent Value – Access
0BI-000System #1 – Flow SwitchRead Only
1BI-001System #2 – Flow SwitchRead Only
2BI-002System #3 – Flow SwitchRead Only
3BI-003System #4 – Flow SwitchRead Only

Binary Value Object Instance Summary (Table 1-3)

Instance IDObject NamePurposePresent Value – Access
12BV-012System #1 – Conductivity High AlarmRead Only
13BV-013System #1 – Conductivity Low AlarmRead Only
14BV-014System #1 – Conductivity Limit AlarmRead Only
15BV-015System #1 – pH High AlarmRead Only
16BV-016System #1 – pH Low AlarmRead Only
17BV-017System #1 – pH Limit AlarmRead Only
18BV-018System #1 – ORP High AlarmRead Only
19BV-019System #1 – ORP Low AlarmRead Only
20BV-020System #1 – ORP Limit AlarmRead Only
21BV-021System #1 – S. Temp High AlarmRead Only
22BV-022System #1 – S. Temp Low AlarmRead Only
23BV-023System #1 – M. Temp High AlarmRead Only
24BV-024System #1 – M. Temp Low AlarmRead Only
25BV-025System #1 – D. Temp High AlarmRead Only
26BV-026System #1 – D. Temp Low AlarmRead Only
27BV-027System #1 – No Flow AlarmRead Only
28BV-028System #1 – Digital Input 1 AlarmRead Only
29BV-029System #1 – Digital Input 2 AlarmRead Only
30BV-030System #1 – Digital Input 3 AlarmRead Only
31BV-031System #1 – Digital Input 4 AlarmRead Only
32BV-032System #1 – Digital Input 5 AlarmRead Only
34BV-034System #1 – M. Conductivity High AlarmRead Only
35BV-035System #1 – M. Conductivity Low AlarmRead Only
36BV-036System #1 – M. Conductivity Limit AlarmRead Only
37BV-037System #1 – Notepad 1 High AlarmRead Only
38BV-038System #1 – Notepad 2 High AlarmRead Only
39BV-039System #1 – Notepad 3 High AlarmRead Only
40BV-040System #1 – Notepad 4 High AlarmRead Only
41BV-041System #1 – Notepad 5 High AlarmRead Only
42BV-042System #1 – Notepad 6 High AlarmRead Only
43BV-043System #1 – Notepad 7 High AlarmRead Only
44BV-044System #1 – Notepad 8 High AlarmRead Only
45BV-045System #1 – Notepad 9 High AlarmRead Only
46BV-046System #1 – Notepad 10 High AlarmRead Only
47BV-047System #1 – Notepad 1 Low AlarmRead Only
48BV-048System #1 – Notepad 2 Low AlarmRead Only
49BV-049System #1 – Notepad 3 Low AlarmRead Only
50BV-050System #1 – Notepad 4 Low AlarmRead Only
51BV-051System #1 – Notepad 5 Low AlarmRead Only
52BV-052System #1 – Notepad 6 Low AlarmRead Only
53BV-053System #1 – Notepad 7 Low AlarmRead Only
54BV-054System #1 – Notepad 8 Low AlarmRead Only
55BV-055System #1 – Notepad 9 Low AlarmRead Only
56BV-056System #1 – Notepad 10 Low AlarmRead Only
57BV-057System #1 – Notepad 1 Time AlarmRead Only
58BV-058System #1 – Notepad 2 Time AlarmRead Only
59BV-059System #1 – Notepad 3 Time AlarmRead Only
60BV-060System #1 – Notepad 4 Time AlarmRead Only
61BV-061System #1 – Notepad 5 Time AlarmRead Only
62BV-062System #1 – Notepad 6 Time AlarmRead Only
63BV-063System #1 – Notepad 7 Time AlarmRead Only
64BV-064System #1 – Notepad 8 Time AlarmRead Only
65BV-065System #1 – Notepad 9 Time AlarmRead Only
66BV-066System #1 – Notepad 10 Time AlarmRead Only
81BV-081System #2 – Conductivity High AlarmRead Only
82BV-082System #2 – Conductivity Low AlarmRead Only
83BV-083System #2 – Conductivity Limit AlarmRead Only
84BV-084System #2 – pH High AlarmRead Only
85BV-085System #2 – pH Low AlarmRead Only
86BV-086System #2 – pH Limit AlarmRead Only
87BV-087System #2 – ORP High AlarmRead Only
88BV-088System #2 – ORP Low AlarmRead Only
89BV-089System #2 – ORP Limit AlarmRead Only
90BV-090System #2 – S. Temp High AlarmRead Only
91BV-091System #2 – S. Temp Low AlarmRead Only
92BV-092System #2 – M. Temp High AlarmRead Only
93BV-093System #2 – M. Temp Low AlarmRead Only
94BV-094System #2 – D. Temp High AlarmRead Only
95BV-095System #2 – D. Temp Low AlarmRead Only
96BV-096System #2 – No Flow AlarmRead Only
97BV-097System #2 – Digital Input 1 AlarmRead Only
98BV-098System #2 – Digital Input 2 AlarmRead Only
99BV-099System #2 – Digital Input 3 AlarmRead Only
100BV-100System #2 – Digital Input 4 AlarmRead Only
101BV-101System #2 – Digital Input 5 AlarmRead Only
103BV-103System #2 – M. Conductivity High AlarmRead Only
104BV-104System #2 – M. Conductivity Low AlarmRead Only
105BV-105System #2 – M. Conductivity Limit AlarmRead Only
106BV-106System #2 – Notepad 1 High AlarmRead Only
107BV-107System #2 – Notepad 2 High AlarmRead Only
108BV-108System #2 – Notepad 3 High AlarmRead Only
109BV-109System #2 – Notepad 4 High AlarmRead Only
110BV-110System #2 – Notepad 5 High AlarmRead Only
111BV-111System #2 – Notepad 6 High AlarmRead Only
112BV-112System #2 – Notepad 7 High AlarmRead Only
113BV-113System #2 – Notepad 8 High AlarmRead Only
114BV-114System #2 – Notepad 9 High AlarmRead Only
115BV-115System #2 – Notepad 10 High AlarmRead Only
116BV-116System #2 – Notepad 1 Low AlarmRead Only
117BV-117System #2 – Notepad 2 Low AlarmRead Only
118BV-118System #2 – Notepad 3 Low AlarmRead Only
119BV-119System #2 – Notepad 4 Low AlarmRead Only
120BV-120System #2 – Notepad 5 Low AlarmRead Only
121BV-121System #2 – Notepad 6 Low AlarmRead Only
122BV-122System #2 – Notepad 7 Low AlarmRead Only
123BV-123System #2 – Notepad 8 Low AlarmRead Only
124BV-124System #2 – Notepad 9 Low AlarmRead Only
125BV-125System #2 – Notepad 10 Low AlarmRead Only
126BV-126System #2 – Notepad 1 Time AlarmRead Only
127BV-127System #2 – Notepad 2 Time AlarmRead Only
128BV-128System #2 – Notepad 3 Time AlarmRead Only
129BV-129System #2 – Notepad 4 Time AlarmRead Only
130BV-130System #2 – Notepad 5 Time AlarmRead Only
131BV-131System #2 – Notepad 6 Time AlarmRead Only
132BV-132System #2 – Notepad 7 Time AlarmRead Only
133BV-133System #2 – Notepad 8 Time AlarmRead Only
134BV-134System #2 – Notepad 9 Time AlarmRead Only
135BV-135System #2 – Notepad 10 Time AlarmRead Only
150BV-150System #3 – Conductivity High AlarmRead Only
151BV-151System #3 – Conductivity Low AlarmRead Only
152BV-152System #3 – Conductivity Limit AlarmRead Only
153BV-153System #3 – pH High AlarmRead Only
154BV-154System #3 – pH Low AlarmRead Only
155BV-155System #3 – pH Limit AlarmRead Only
156BV-156System #3 – ORP High AlarmRead Only
157BV-157System #3 – ORP Low AlarmRead Only
158BV-158System #3 – ORP Limit AlarmRead Only
159BV-159System #3 – S. Temp High AlarmRead Only
160BV-160System #3 – S. Temp Low AlarmRead Only
161BV-161System #3 – M. Temp High AlarmRead Only
162BV-162System #3 – M. Temp Low AlarmRead Only
163BV-163System #3 – D. Temp High AlarmRead Only
164BV-164System #3 – D. Temp Low AlarmRead Only
165BV-165System #3 – No Flow AlarmRead Only
166BV-166System #3 – Digital Input 1 AlarmRead Only
167BV-167System #3 – Digital Input 2 AlarmRead Only
168BV-168System #3 – Digital Input 3 AlarmRead Only
169BV-169System #3 – Digital Input 4 AlarmRead Only
170BV-170System #3 – Digital Input 5 AlarmRead Only
172BV-172System #3 – M. Conductivity High AlarmRead Only
173BV-173System #3 – M. Conductivity Low AlarmRead Only
174BV-174System #3 – M. Conductivity Limit AlarmRead Only
175BV-175System #3 – Notepad 1 High AlarmRead Only
176BV-176System #3 – Notepad 2 High AlarmRead Only
177BV-177System #3 – Notepad 3 High AlarmRead Only
178BV-178System #3 – Notepad 4 High AlarmRead Only
179BV-179System #3 – Notepad 5 High AlarmRead Only
180BV-180System #3 – Notepad 6 High AlarmRead Only
181BV-181System #3 – Notepad 7 High AlarmRead Only
182BV-182System #3 – Notepad 8 High AlarmRead Only
183BV-183System #3 – Notepad 9 High AlarmRead Only
184BV-184System #3 – Notepad 10 High AlarmRead Only
185BV-185System #3 – Notepad 1 Low AlarmRead Only
186BV-186System #3 – Notepad 2 Low AlarmRead Only
187BV-187System #3 – Notepad 3 Low AlarmRead Only
188BV-188System #3 – Notepad 4 Low AlarmRead Only
189BV-189System #3 – Notepad 5 Low AlarmRead Only
190BV-190System #3 – Notepad 6 Low AlarmRead Only
191BV-191System #3 – Notepad 7 Low AlarmRead Only
192BV-192System #3 – Notepad 8 Low AlarmRead Only
193BV-193System #3 – Notepad 9 Low AlarmRead Only
194BV-194System #3 – Notepad 10 Low AlarmRead Only
195BV-195System #3 – Notepad 1 Time AlarmRead Only
196BV-196System #3 – Notepad 2 Time AlarmRead Only
197BV-197System #3 – Notepad 3 Time AlarmRead Only
198BV-198System #3 – Notepad 4 Time AlarmRead Only
199BV-199System #3 – Notepad 5 Time AlarmRead Only
200BV-200System #3 – Notepad 6 Time AlarmRead Only
201BV-201System #3 – Notepad 7 Time AlarmRead Only
202BV-202System #3 – Notepad 8 Time AlarmRead Only
203BV-203System #3 – Notepad 9 Time AlarmRead Only
204BV-204System #3 – Notepad 10 Time AlarmRead Only
219BV-219System #4 – Conductivity High AlarmRead Only
220BV-220System #4 – Conductivity Low AlarmRead Only
221BV-221System #4 – Conductivity Limit AlarmRead Only
222BV-222System #4 – pH High AlarmRead Only
223BV-223System #4 – pH Low AlarmRead Only
224BV-224System #4 – pH Limit AlarmRead Only
225BV-225System #4 – ORP High AlarmRead Only
226BV-226System #4 – ORP Low AlarmRead Only
227BV-227System #4 – ORP Limit AlarmRead Only
228BV-228System #4 – S. Temp High AlarmRead Only
229BV-229System #4 – S. Temp Low AlarmRead Only
230BV-230System #4 – M. Temp High AlarmRead Only
231BV-231System #4 – M. Temp Low AlarmRead Only
232BV-232System #4 – D. Temp High AlarmRead Only
233BV-233System #4 – D. Temp Low AlarmRead Only
234BV-234System #4 – No Flow AlarmRead Only
235BV-235System #4 – Digital Input 1 AlarmRead Only
236BV-236System #4 – Digital Input 2 AlarmRead Only
237BV-237System #4 – Digital Input 3 AlarmRead Only
238BV-238System #4 – Digital Input 4 AlarmRead Only
239BV-239System #4 – Digital Input 5 AlarmRead Only
241BV-241System #4 – M. Conductivity High AlarmRead Only
242BV-242System #4 – M. Conductivity Low AlarmRead Only
243BV-243System #4 – M. Conductivity Limit AlarmRead Only
244BV-244System #4 – Notepad 1 High AlarmRead Only
245BV-245System #4 – Notepad 2 High AlarmRead Only
246BV-246System #4 – Notepad 3 High AlarmRead Only
247BV-247System #4 – Notepad 4 High AlarmRead Only
248BV-248System #4 – Notepad 5 High AlarmRead Only
249BV-249System #4 – Notepad 6 High AlarmRead Only
250BV-250System #4 – Notepad 7 High AlarmRead Only
251BV-251System #4 – Notepad 8 High AlarmRead Only
252BV-252System #4 – Notepad 9 High AlarmRead Only
253BV-253System #4 – Notepad 10 High AlarmRead Only
254BV-254System #4 – Notepad 1 Low AlarmRead Only
255BV-255System #4 – Notepad 2 Low AlarmRead Only
256BV-256System #4 – Notepad 3 Low AlarmRead Only
257BV-257System #4 – Notepad 4 Low AlarmRead Only
258BV-258System #4 – Notepad 5 Low AlarmRead Only
259BV-259System #4 – Notepad 6 Low AlarmRead Only
260BV-260System #4 – Notepad 7 Low AlarmRead Only
261BV-261System #4 – Notepad 8 Low AlarmRead Only
262BV-262System #4 – Notepad 9 Low AlarmRead Only
263BV-263System #4 – Notepad 10 Low AlarmRead Only
264BV-264System #4 – Notepad 1 Time AlarmRead Only
265BV-265System #4 – Notepad 2 Time AlarmRead Only
266BV-266System #4 – Notepad 3 Time AlarmRead Only
267BV-267System #4 – Notepad 4 Time AlarmRead Only
268BV-268System #4 – Notepad 5 Time AlarmRead Only
269BV-269System #4 – Notepad 6 Time AlarmRead Only
270BV-270System #4 – Notepad 7 Time AlarmRead Only
271BV-271System #4 – Notepad 8 Time AlarmRead Only
272BV-272System #4 – Notepad 9 Time AlarmRead Only
273BV-273System #4 – Notepad 10 Time AlarmRead Only
277BV-277ma Input 1 High AlarmRead Only
278BV-278ma Input 1 Low AlarmRead Only
280BV-280ma Input 2 High AlarmRead Only
281BV-281ma Input 2 Low AlarmRead Only
283BV-283ma Input 3 High AlarmRead Only
284BV-284ma Input 3 Low AlarmRead Only
286BV-286ma Input 4 High AlarmRead Only
287BV-287ma Input 4 Low AlarmRead Only
289BV-289ma Input 5 High AlarmRead Only
290BV-290ma Input 5 Low AlarmRead Only
292BV-292ma Input 6 High AlarmRead Only
293BV-293ma Input 6 Low AlarmRead Only
295BV-295ma Input 7 High AlarmRead Only
296BV-296ma Input 7 Low AlarmRead Only
298BV-298ma Input 8 High AlarmRead Only
299BV-299ma Input 8 Low AlarmRead Only
302BV-302Flow Meter 1 Flow AlarmRead Only
303BV-303Flow Meter 1 Flow Verfiy AlarmRead Only
304BV-304Flow Meter 1 Volume AlarmRead Only
305BV-305Flow Meter 2 Flow AlarmRead Only
306BV-306Flow Meter 2 Flow Verfiy AlarmRead Only
307BV-307Flow Meter 2 Volume AlarmRead Only
308BV-308Flow Meter 3 Flow AlarmRead Only
309BV-309Flow Meter 3 Flow Verfiy AlarmRead Only
310BV-310Flow Meter 3 Volume AlarmRead Only
311BV-311Flow Meter 4 Flow AlarmRead Only
312BV-312Flow Meter 4 Flow Verfiy AlarmRead Only
313BV-313Flow Meter 4 Volume AlarmRead Only
314BV-314Flow Meter 5 Flow AlarmRead Only
315BV-315Flow Meter 5 Flow Verfiy AlarmRead Only
316BV-316Flow Meter 5 Volume AlarmRead Only
317BV-317Flow Meter 6 Flow AlarmRead Only
318BV-318Flow Meter 6 Flow Verfiy AlarmRead Only
319BV-319Flow Meter 6 Volume AlarmRead Only
320BV-320Flow Meter 7 Flow AlarmRead Only
321BV-321Flow Meter 7 Flow Verfiy AlarmRead Only
322BV-322Flow Meter 7 Volume AlarmRead Only
323BV-323Flow Meter 8 Flow AlarmRead Only
324BV-324Flow Meter 8 Flow Verfiy AlarmRead Only
325BV-325Flow Meter 8 Volume AlarmRead Only
326BV-326Flow Meter 9 Flow AlarmRead Only
327BV-327Flow Meter 9 Flow Verfiy AlarmRead Only
328BV-328Flow Meter 9 Volume AlarmRead Only
329BV-329Flow Meter 10 Flow AlarmRead Only
330BV-330Flow Meter 10 Flow VerifyRead Only
331BV-331Flow Meter 10 Volume AlarmRead Only
332BV-332Relay 1 Max HoursRead Only
333BV-333Relay 2 Max HoursRead Only
334BV-334Relay 3 Max HoursRead Only
335BV-335Relay 4 Max HoursRead Only
336BV-336Relay 5 Max HoursRead Only
337BV-337Relay 6 Max HoursRead Only
338BV-338Relay 7 Max HoursRead Only
339BV-339Relay 8 Max HoursRead Only
340BV-340Relay 9 Max HoursRead Only
341BV-341Relay 10 Max HoursRead Only
342BV-342Relay 11 Max HoursRead Only
343BV-343Relay 12 Max HoursRead Only
344BV-344Relay 13 Max HoursRead Only
345BV-345Relay 14 Max HoursRead Only
346BV-346Relay 15 Max HoursRead Only
347BV-347Relay 16 Max HoursRead Only
348BV-348Relay 17 Max HoursRead Only
349BV-349Relay 18 Max HoursRead Only
350BV-350Relay 19 Max HoursRead Only
351BV-351Relay 20 Max HoursRead Only
352BV-352mA Input 1 LimitRead Only
353BV-353mA Input 2 LimitRead Only
354BV-354mA Input 3 LimitRead Only
355BV-355mA Input 4 LimitRead Only
356BV-356mA Input 5 LimitRead Only
357BV-357mA Input 6 LimitRead Only
358BV-358mA Input 7 LimitRead Only
359BV-359mA Input 8 LimitRead Only
360BV-360mA Input 9 Limit AlarmRead Only
361BV-361mA Input 10 Limit AlarmRead Only
362BV-362mA Input 11 Limit AlarmRead Only
363BV-363mA Input 12 Limit AlarmRead Only
364BV-369mA Input 13 Limit AlarmRead Only
365BV-365mA Input 14 Limit AlarmRead Only
366BV-366mA Input 15 Limit AlarmRead Only
367BV-367mA Input 16 Limit AlarmRead Only
369BV-369ma Input 9 High AlarmRead Only
370BV-370ma Input 9 Low AlarmRead Only
372BV-372ma Input 10 High AlarmRead Only
373BV-373ma Input 10 Low AlarmRead Only
375BV-375ma Input 11 High AlarmRead Only
376BV-376ma Input 11 Low AlarmRead Only
378BV-378ma Input 12 High AlarmRead Only
379BV-379ma Input 12 Low AlarmRead Only
381BV-381ma Input 13 High AlarmRead Only
382BV-382ma Input 13 Low AlarmRead Only
384BV-384ma Input 14 High AlarmRead Only
385BV-385ma Input 14 Low AlarmRead Only
387BV-387ma Input 15 High AlarmRead Only
388BV-388ma Input 15 Low AlarmRead Only
390BV-390ma Input 16 High AlarmRead Only
391BV-391ma Input 16 Low AlarmRead Only

Analog Input Object Instance Summary (Table 1-4)

Instance IDObject NamePurposePresent Value – Access
0AI-000System #1 – ConductivityRead Only
1AI-001System #2 – ConductivityRead Only
2AI-002System #3 – ConductivityRead Only
3AI-003System #4 – ConductivityRead Only
4AI-004System #1 – M. ConductivityRead Only
5AI-005System #2 – M. ConductivityRead Only
6AI-006System #3 – M. ConductivityRead Only
7AI-007System #4 – M. ConductivityRead Only
8AI-008System #1 – pHRead Only
9AI-009System #2 – pHRead Only
10AI-010System #3 – pHRead Only
11AI-011System #4 – pHRead Only
12AI-012System #1 – ORPRead Only
13AI-013System #2 – ORPRead Only
14AI-014System #3 – ORPRead Only
15AI-015System #4 – ORPRead Only
16AI-016System #1 – S. TempRead Only
17AI-017System #2 – S. TempRead Only
18AI-018System #3 – S. TempRead Only
19AI-019System #4 – S. TempRead Only
20AI-020System #1 – M. TempRead Only
21AI-021System #2 – M. TempRead Only
22AI-022System #3 – M. TempRead Only
23AI-023System #4 – M. TempRead Only
24AI-024Sys #1 – Water Meter #1 – Total ValueRead Only
25AI-025Sys #2 – Water Meter #1 – Total ValueRead Only
26AI-026Sys #3 – Water Meter #1 – Total ValueRead Only
27AI-027Sys #4 – Water Meter #1 – Total ValueRead Only
28AI-028Sys #1 – Water Meter #2 – Total ValueRead Only
29AI-029Sys #2 – Water Meter #2 – Total ValueRead Only
30AI-030Sys #3 – Water Meter #2 – Total ValueRead Only
31AI-031Sys #4 – Water Meter #2 – Total ValueRead Only
32AI-032System #1 – M.CyclesRead Only
33AI-033System #2 – M.CyclesRead Only
34AI-034System #3 – M.CyclesRead Only
35AI-035System #4 – M.CyclesRead Only
36AI-0364-20 mA / 0-5V Input #1 – ValueRead Only
37AI-0374-20 mA / 0-5V Input #2 – ValueRead Only
38AI-0384-20 mA / 0-5V Input #3 – ValueRead Only
39AI-0394-20 mA / 0-5V Input #4 – ValueRead Only
40AI-0404-20 mA / 0-5V Input #5 – ValueRead Only
41AI-0414-20 mA / 0-5V Input #6 – ValueRead Only
42AI-0424-20 mA / 0-5V Input #7 – ValueRead Only
43AI-0434-20 mA / 0-5V Input #8 – ValueRead Only
44AI-044Flow Meter #1 – Contact ValueRead Only
45AI-045Flow Meter #2 – Contact ValueRead Only
46AI-046Flow Meter #3 – Contact ValueRead Only
47AI-047Flow Meter #4 – Contact ValueRead Only
48AI-048Flow Meter #5 – Contact ValueRead Only
49AI-049Flow Meter #6 – Contact ValueRead Only
50AI-050Flow Meter #7 – Contact ValueRead Only
51AI-051Flow Meter #8 – Contact ValueRead Only
52AI-052Flow Meter #9 – Contact ValueRead Only
53AI-053Flow Meter #10 – Contact ValueRead Only
54AI-054Flow Meter #1 – Flow Rate (per MIN)Read Only
55AI-055Flow Meter #2 – Flow Rate (per MIN)Read Only
56AI-056Flow Meter #3 – Flow Rate (per MIN)Read Only
57AI-057Flow Meter #4 – Flow Rate (per MIN)Read Only
58AI-058Flow Meter #5 – Flow Rate (per MIN)Read Only
59AI-059Flow Meter #6 – Flow Rate (per MIN)Read Only
60AI-060Flow Meter #7 – Flow Rate (per MIN)Read Only
61AI-061Flow Meter #8 – Flow Rate (per MIN)Read Only
62AI-062Flow Meter #9 – Flow Rate (per MIN)Read Only
63AI-063Flow Meter #10 – Flow Rate (per MIN)Read Only
64AI-0644-20 mA / 0-5V Input #9 – ValueRead Only
65AI-0654-20 mA / 0-5V Input #10 – ValueRead Only
66AI-0664-20 mA / 0-5V Input #11 – ValueRead Only
67AI-0674-20 mA / 0-5V Input #12 – ValueRead Only
68AI-0684-20 mA / 0-5V Input #13 – ValueRead Only
69AI-0694-20 mA / 0-5V Input #14 – ValueRead Only
70AI-0704-20 mA / 0-5V Input #15 – ValueRead Only
71AI-0714-20 mA / 0-5V Input #16 – ValueRead Only

Analog Value Object Instance Summary (Table 1-5)

Instance IDObject NamePurposePresent Value – Access
0AV-000System #1 – Conductivity Setpoint #1Read / Write
1AV-001System #2 – Conductivity Setpoint #1Read / Write
2AV-002System #3 – Conductivity Setpoint #1Read / Write
3AV-003System #4 – Conductivity Setpoint #1Read / Write
4AV-004System #1 – Conductivity Setpoint #2Read / Write
5AV-005System #2 – Conductivity Setpoint #2Read / Write
6AV-006System #3 – Conductivity Setpoint #2Read / Write
7AV-007System #4 – Conductivity Setpoint #2Read / Write
8AV-008System #1 – Conductivity High AlarmRead / Write
9AV-009System #2 – Conductivity High AlarmRead / Write
10AV-010System #3 – Conductivity High AlarmRead / Write
11AV-011System #4 – Conductivity High AlarmRead / Write
12AV-012System #1 – Conductivity Low AlarmRead / Write
13AV-013System #2 – Conductivity Low AlarmRead / Write
14AV-014System #3 – Conductivity Low AlarmRead / Write
15AV-015System #4 – Conductivity Low AlarmRead / Write
16AV-016System #1 – M. Conductivity SetpointRead / Write
17AV-017System #2 – M. Conductivity SetpointRead / Write
18AV-018System #3 – M. Conductivity SetpointRead / Write
19AV-019System #4 – M. Conductivity SetpointRead / Write
20AV-020System #1 – M. Conductivity High AlarmRead / Write
21AV-021System #2 – M. Conductivity High AlarmRead / Write
22AV-022System #3 – M. Conductivity High AlarmRead / Write
23AV-023System #4 – M. Conductivity High AlarmRead / Write
24AV-024System #1 – M. Conductivity Low AlarmRead / Write
25AV-025System #2 – M. Conductivity Low AlarmRead / Write
26AV-026System #3 – M. Conductivity Low AlarmRead / Write
27AV-027System #4 – M. Conductivity Low AlarmRead / Write
28AV-028System #1 – pH Setpoint #1Read / Write
29AV-029System #2 – pH Setpoint #1Read / Write
30AV-030System #3 – pH Setpoint #1Read / Write
31AV-031System #4 – pH Setpoint #1Read / Write
32AV-032System #1 – pH Setpoint #2Read / Write
33AV-033System #2 – pH Setpoint #2Read / Write
34AV-034System #3 – pH Setpoint #2Read / Write
35AV-035System #4 – pH Setpoint #2Read / Write
36AV-036System #1 – pH High AlarmRead / Write
37AV-037System #2 – pH High AlarmRead / Write
38AV-038System #3 – pH High AlarmRead / Write
39AV-039System #4 – pH High AlarmRead / Write
40AV-040System #1 – pH Low AlarmRead / Write
41AV-041System #2 – pH Low AlarmRead / Write
42AV-042System #3 – pH Low AlarmRead / Write
43AV-043System #4 – pH Low AlarmRead / Write
44AV-044System #1 – ORP Setpoint #1Read / Write
45AV-045System #2 – ORP Setpoint #1Read / Write
46AV-046System #3 – ORP Setpoint #1Read / Write
47AV-047System #4 – ORP Setpoint #1Read / Write
48AV-048System #1 – ORP Setpoint #2Read / Write
49AV-049System #2 – ORP Setpoint #2Read / Write
50AV-050System #3 – ORP Setpoint #2Read / Write
51AV-051System #4 – ORP Setpoint #2Read / Write
52AV-052System #1 – ORP High AlarmRead / Write
53AV-053System #2 – ORP High AlarmRead / Write
54AV-054System #3 – ORP High AlarmRead / Write
55AV-055System #4 – ORP High AlarmRead / Write
56AV-056System #1 – ORP Low AlarmRead / Write
57AV-057System #2 – ORP Low AlarmRead / Write
58AV-058System #3 – ORP Low AlarmRead / Write
59AV-059System #4 – ORP Low AlarmRead / Write
60AV-060System #1 – S. Temp SetpointRead / Write
61AV-061System #2 – S. Temp SetpointRead / Write
62AV-062System #3 – S. Temp SetpointRead / Write
63AV-063System #4 – S. Temp SetpointRead / Write
64AV-064System #1 – S. Temp High AlarmRead / Write
65AV-065System #2 – S. Temp High AlarmRead / Write
66AV-066System #3 – S. Temp High AlarmRead / Write
67AV-067System #4 – S. Temp High AlarmRead / Write
68AV-068System #1 – S. Temp Low AlarmRead / Write
69AV-069System #2 – S. Temp Low AlarmRead / Write
70AV-070System #3 – S. Temp Low AlarmRead / Write
71AV-071System #4 – S. Temp Low AlarmRead / Write
72AV-072System #1 – M. Temp SetpointRead / Write
73AV-073System #2 – M. Temp SetpointRead / Write
74AV-074System #3 – M. Temp SetpointRead / Write
75AV-075System #4 – M. Temp SetpointRead / Write
76AV-076System #1 – M. Temp High AlarmRead / Write
77AV-077System #2 – M. Temp High AlarmRead / Write
78AV-078System #3 – M. Temp High AlarmRead / Write
79AV-079System #4 – M. Temp High AlarmRead / Write
80AV-080System #1 – M. Temp Low AlarmRead / Write
81AV-081System #2 – M. Temp Low AlarmRead / Write
82AV-082System #3 – M. Temp Low AlarmRead / Write
83AV-083System #4 – M. Temp Low AlarmRead / Write
84AV-084System #1 – D. Temp SetpointRead / Write
85AV-085System #2 – D. Temp SetpointRead / Write
86AV-086System #3 – D. Temp SetpointRead / Write
87AV-087System #4 – D. Temp SetpointRead / Write
88AV-088System #1 – D. Temp High AlarmRead / Write
89AV-089System #2 – D. Temp High AlarmRead / Write
90AV-090System #3 – D. Temp High AlarmRead / Write
91AV-091System #4 – D. Temp High AlarmRead / Write
92AV-092System #1 – D. Temp Low AlarmRead / Write
93AV-093System #2 – D. Temp Low AlarmRead / Write
94AV-094System #3 – D. Temp Low AlarmRead / Write
95AV-095System #4 – D. Temp Low AlarmRead / Write
96AV-096System #1 – Flow Switch Conf.Read / Write
97AV-097System #2 – Flow Switch Conf.Read / Write
98AV-098System #3 – Flow Switch Conf.Read / Write
99AV-099System #4 – Flow Switch Conf.Read / Write
100AV-100mA 1 – Output ValueRead / Write
101AV-101mA 2 – Output ValueRead / Write
102AV-102mA 3 – Output ValueRead / Write
103AV-103mA 4 – Output ValueRead / Write
104AV-104mA 5 – Output ValueRead / Write
105AV-105mA 6 – Output ValueRead / Write
106AV-106System #1 – Timer #1 – Run TimeRead / Write
107AV-107System #1 – Timer #2 – Run TimeRead / Write
108AV-108System #1 – Timer #3 – Run TimeRead / Write
109AV-109System #1 – Timer #4 – Run TimeRead / Write
110AV-110System #1 – Timer #5 – Run TimeRead / Write
111AV-111System #2 – Timer #1 – Run TimeRead / Write
112AV-112System #2 – Timer #2 – Run TimeRead / Write
113AV-113System #2 – Timer #3 – Run TimeRead / Write
114AV-114System #2 – Timer #4 – Run TimeRead / Write
115AV-115System #2 – Timer #5 – Run TimeRead / Write
116AV-116System #3 – Timer #1 – Run TimeRead / Write
117AV-117System #3 – Timer #2 – Run TimeRead / Write
118AV-118System #3 – Timer #3 – Run TimeRead / Write
119AV-119System #3 – Timer #4 – Run TimeRead / Write
120AV-120System #3 – Timer #5 – Run TimeRead / Write
121AV-121System #4 – Timer #1 – Run TimeRead / Write
122AV-122System #4 – Timer #2 – Run TimeRead / Write
123AV-123System #4 – Timer #3 – Run TimeRead / Write
124AV-124System #4 – Timer #4 – Run TimeRead / Write
125AV-125System #4 – Timer #5 – Run TimeRead / Write
126AV-126Read-Only ModeRead Only

Multi-State Value Object Instance Summary (Table 1-6)
Note #1  1=H-OFF 2=H-ON  3=OFF  4=ON

Instance IDObject NamePurposePresent Value – Access
0MSV-000Relay 1 – StateRead / Write
1MSV-001Relay 2 – StateRead / Write
2MSV-002Relay 3 – StateRead / Write
3MSV-003Relay 4 – StateRead / Write
4MSV-004Relay 5 – StateRead / Write
5MSV-005Relay 6 – StateRead / Write
6MSV-006Relay 7 – StateRead / Write
7MSV-007Relay 8 – StateRead / Write
8MSV-008Relay 9 – StateRead / Write
9MSV-009Relay 10 – StateRead / Write
10MSV-010Relay 11 – StateRead / Write
11MSV-011Relay 12 – StateRead / Write
12MSV-012Relay 13 – StateRead / Write
13MSV-013Relay 14 – StateRead / Write
14MSV-014Relay 15 – StateRead / Write
15MSV-015Relay 16 – StateRead / Write
16MSV-016Relay 17 – StateRead / Write
17MSV-017Relay 18 – StateRead / Write
18MSV-018Relay 19 – StateRead / Write
19MSV-019Relay 20 – StateRead / Write

Get the Advantage in Water Treatment Equipment
Advantage Controls can give you the Advantage in products, knowledge and support on all of your water treatment equipment needs.Advantage Controls H22 MegaTron Controller - AdvantageAdvantage Controls H22 MegaTron Controller - Symbol Cooling Tower Controllers
Advantage Controls H22 MegaTron Controller - Symbol Boiler Blow Down Controllers
Advantage Controls H22 MegaTron Controller - Symbol Blow Down Valve Packages
Advantage Controls H22 MegaTron Controller - Symbol Solenoid Valves
Advantage Controls H22 MegaTron Controller - Symbol Water Meters
Advantage Controls H22 MegaTron Controller - Symbol Chemical Metering Pumps
Advantage Controls H22 MegaTron Controller - Symbol Corrosion Coupon Racks
Advantage Controls H22 MegaTron Controller - Symbol Chemical Solution Tanks
Advantage Controls H22 MegaTron Controller - Symbol Solid Feed Systems
Advantage Controls H22 MegaTron Controller - Symbol Feed Timers
Advantage Controls H22 MegaTron Controller - Symbol Filter Equipment
Advantage Controls H22 MegaTron Controller - Symbol Glycol Feed Systems
Advantage Controls H22 MegaTron Controller - Symbol Pre Fabricated Systems

Get the Advantage

Advantage LogoAdvantage Controls
4700 Harold-Abitz Dr.
Muskogee, OK 74403
Phone: 800-743-7431
Fax: 888-686-6212