Digital Output with Shutdown Input FB6208C
- 8-channel
- Outputs Ex ib
- Installation in suitable enclosures in Zone 1
- Module can be exchanged under voltage (hot swap)
- Galvanic group isolation
- Line fault detection (LFD)
- Positive or negative logic selectable
- Simulation mode for service operations (forcing)
- Permanently self-monitoring
- Output with watchdog
- Output with bus-independent safety shutdown
Function
The device features 8 independent channels.
The device can be used to drive low power solenoids, sounders, or LEDs.
Open and short-circuit line faults are detected.
The outputs are galvanically isolated from the bus and the power supply.
The outputs can be switched off via a contact. This can be used for bus-independent safety applications.
Connection
Technical Data
Slots | |||
Occupied slots | 2 | ||
Functional safety related parameters | |||
Safety Integrity Level (SIL) | SIL 2 | ||
Performance level (PL) | PL d | ||
Supply | |||
Connection | backplane bus | ||
Rated voltage | Ur | 12 V DC , only in connection with the power supplies FB92** | |
Power dissipation | 2.35 W | ||
Power consumption | 2.35 W | ||
Internal bus | |||
Connection | backplane bus | ||
Interface | manufacturer-specific bus to standard com unit | ||
Digital output | |||
Number of channels | 8 | ||
Suitable field devices | |||
Field device | Solenoid Valve | ||
Field device [2] | audible alarm | ||
Field device [3] | visual alarm | ||
Connection | channel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-; channel IV: 7+, 8-; channel V: 9+, 10-; channel VI: 11+, 12-; channel VII: 13+, 14-; channel VIII: 15+, 16- | ||
Current limit | Imax | 5.2 mA | |
Open loop voltage | Us | 21.6 V | |
Line fault detection | can be switched on/off for each channel via configuration tool | ||
Test current | 0.33 mA | ||
Short-circuit | < 300 Ω | ||
Open-circuit | > 50 kΩ | ||
Response time | 20 ms (depending on bus cycle time) | ||
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | ||
Indicators/settings | |||
LED indication | LED green: supply LED red: line fault , communication error red flashing | ||
Coding | optional mechanical coding via front socket | ||
Directive conformity | |||
Electromagnetic compatibility | |||
Directive 2014/30/EU | EN 61326-1:2013 | ||
Conformity | |||
Electromagnetic compatibility | NE 21 | ||
Degree of protection | IEC 60529 | ||
Environmental test | EN 60068-2-14 | ||
Shock resistance | EN 60068-2-27 | ||
Vibration resistance | EN 60068-2-6 | ||
Damaging gas | EN 60068-2-42 | ||
Relative humidity | EN 60068-2-78 | ||
Ambient conditions | |||
Ambient temperature | -20 … 60 °C (-4 … 140 °F) | ||
Storage temperature | -25 … 85 °C (-13 … 185 °F) | ||
Relative humidity | 95 % non-condensing | ||
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | ||
ibration reistance | frequency range 10 … 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 … 100 Hz; transition frequency: 13.2 Hz mplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance | ||
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | ||
Mechanical specifications | |||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | ||
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14… 1.5 mm2) or screw terminals (0.08…. 1.5 mm2) | ||
Mass | approx. 750 g | ||
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | ||
Data for application in connection with hazardous areas | |||
EU-type examination certificate | PTB 97 ATEX 1074 U | ||
Marking | 1 II 2 G Ex d [ib] IIC Gb 1 II (2) D [Ex ib Db] IIIC |
Output | ||
Voltage | Uo | 30 V |
Current | Io | 13.5 mA |
Power | Po | 404 mW (characteristic curve rectangular type) |
Galvanic isolation | ||
Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 EN 60079-1:2014 EN 60079-11:2012 | |
International approvals | ||
ATEX approval | PTB 97 ATEX 1075 ; PTB 97 ATEX 1074 U | |
General information | ||
System information | The module has to be mounted in appropriate backplanes and housings (FB92**) in Zone 1, 2, 21, 22 or outside hazardous areas (gas or dust). Here, observe the corresponding EC-type examination certificate. | |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Assembly
Accessories
FB9224* | Field Unit |
FB9225* | Redundancy Field Unit |
FB9248* | Field Unit |
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Release date: 2022-07-06
Date of issue: 2022-07-06
Filename: 542157_eng.pdf
Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
Documents / Resources
![]() | Pepperl Fuchs FB6208C Digital Output With Shutdown Input [pdf] Instructions FB6208C Digital Output With Shutdown Input, FB6208C, Digital Output With Shutdown Input, Output With Shutdown Input, With Shutdown Input, Shutdown Input |