Dabeşkirinên Herêmî yên Xeterdar û Talîmatên Taybet ji bo "Bikaranîna Ewle" û Sazkirinên li Cihên Xeterdar

Dibe ku hin tabelayên navan ji yekê zêdetir pejirandinê hilgirin, û her pejirandî dibe ku hewcedariyên sazkirinê/telefonê û/an şertên "bikaranîna ewledar" yekta hebe. Van rêwerzên taybetî yên ji bo "bikaranîna ewledar" ji bilî prosedurên sazkirinê yên standard in û dibe ku ji holê rakin. Rêbernameyên taybetî bi pejirandinê têne navnîş kirin.

Not: This information supplements the nameplate markings affixed to the product and the LCP200 instruction manual (D104296X012), available from your Emerson sales office or Fisher.com Always refer to the nameplate itself to identify the appropriate certification. LCP200 instruments with an IIC rating may have different hardware than IIB-rated instruments; be sure to order the appropriately rated instrument based on your application and wiring practices.

GAZÎ: Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion, or area re‐classification.

Pêdivî ye

Mercên Taybet ên Bikaranînê

  1. Install the unit in the area of low risk from mechanical hazards. To prevent the risk of electrostatic sparking, the non-metallic surface shall be cleaned with a damp kinc.

Notes

Ambient temperature rating: -40 ° C ≤ Ta ≤ + 65 ° C

  1. Install per drawing GG55194, shown in Figures 1, 2, 3, and 4, as indicated on the nameplate.
  2. Veguheztina hêmanan dibe ku ewlehiya hundurîn xirab bike.
  3. The enclosure contains non-metallic enclosure parts. To prevent the risk of electrostatic sparking, the non-metallic surface shall be cleaned with a damp kinc.
    1. Refer to table 1 for approval information.

Table 1. Approval Information, ATEX/IECEx

Şehade Şehadet Hatiye bidest xistin Entity Rating Germî Navê dizî
 

 

 

ATEX IECEx

ATEX: FM17ATEX0071X  II 1 GD IECEx: IECEx FMG 17.0028X

Intrinsically Safe Gas

Ex ia IIC Ga Dust

Ex ia IIIC Da

Install Per Drawing GG55194 (shown in figure 1, 2, 3, and 4)

 

 

 

Per Drawing GG55194 (shown in figure 1, 2, 3, and 4)

 

 

Gas: T6 Dust: T85 C

Figure 1. Intrinsically Safe, LOOP Power, ATEX/IECEx

  • Wiring Configuration A (LOOP-Powered only) From Barrier to Digital Valve Controller and LCP200 See Notes in figure 3 and Notes 1, 2, 3, 4, and 5 in Figure 4.

EMERSON-LCP200-Local-Control-Panel-fig-1

Figure 2. Intrinsically Safe, External Power 24V, ATEX/IECEx

  • Wiring Configuration B (External 24V Only) From Barrier to Digital Valve Controller and LCP200 See Notes in figure 3 and Notes 1, 2, 4, and 5 in Figure 4.

EMERSON-LCP200-Local-Control-Panel-fig-2

Figure 3. Notes

THE INTRINSIC SAFETY ENTITY CONCEPT ALLOWS THE INTERCONNECTION OF TWO APPROVED INTRINSICALLY SAFE DEVICES, WITH ENTITY PARAMETERS NOT SPECIFICALLY EXAMINED IN COMBINATION AS A SYSTEM WHEN: UoEMERSON-LCP200-Local-Control-Panel-fig-3 Ui, IoEMERSON-LCP200-Local-Control-Panel-fig-3 Ii, CoEMERSON-LCP200-Local-Control-Panel-fig-4 Ci + Cable, LoEMERSON-LCP200-Local-Control-Panel-fig-4 Li + Liable, PoEMERSON-LCP200-Local-Control-Panel-fig-3 Pi. DUST-TIGHT SEAL MUST BE USED WHEN INSTALLED IN DUST-PROTECTED ENVIRONMENTS. EACH CONNECTION BETWEEN THE LCP200 AND THE ASSOCIATED INTRINSICALLY SAFE APPARATUS SHALL BE SEPARATELY SHIELDED FROM THE OTHER CONNECTIONS. WHEN CALCULATING THE ENTITY COMBINATIONS THAT INCLUDE THE DVC6000/DVC6200, THE SUMMATION OF THE Ci + Cable AS WELL AS THE Li + Lcable FOR THE DVC6000/DVC6200 AND THE LCP200 SHALL BE USED. ASSOCIATED APPARATUS MANUFACTURERS’ INSTALLATION DRAWINGS MUST BE FOLLOWED WHEN INSTALLING THIS EQUIPMENT.

Figure 4. Notes

Refer to Notes 1, 2, 3, 4, and 5 for Figure 1. Intrinsically Safe, LOOP Power, ATEX/IECEx Wiring Configuration A (LOOP-Powered only) From Barrier to Digital Valve Controller and LCP200 Refer to Notes 1, 2, 4, and 5 for Figure 2. Intrinsically Safe, External Power 24V, ATEX/IECEx Wiring Configuration B (External 24V Only) From Barrier to Digital Valve Controller and LCP200.

AGAHÎ

  1. FOR Ex ia APPLICATIONS THE FOLLOWING INFORMATION SHALL BE OBSERVED:
    • THE OVERALL GAS GROUP RATING OF THE INTRINSICALLY SAFE CIRCUIT WILL BE THE LOWEST GAS GROUPING OF ALL APPARATUS FORMING) THE CIRCUIT. FOR EXAMPLE, A CIRCUIT WITH BOTH IIB AND IIC APPARATUS WILL HAVE AN OVERALL CIRCUIT GAS GROUP RATING OF IIB.
    • THE LEVEL OF PROTECTION OF THE INTRINSICALLY SAFE CIRCUIT WILL BE THE LOWEST LEVEL OF ALL APPARATUS FORMING THE CIRCUIT. FOR EXAMPLE, A CIRCUIT WITH BOTH “ia” AND “ib” WILL HAVE AN OVERALL PROTECTION LEVEL OF “ib”.
  2. THE LOWEST PERMISSIBLE INPUT VOLTAGE (Ui), INPUT CURRENT (Ii), AND INPUT POWER (Pi) OF EACH APPARATUS SHALL BE GREATER THAN OR EQUAL TO THE OUTPUT VOLTAGE (Uo), OUTPUT CURRENT (Io), AND OUTPUT POWER (Po) OF THE ASSOCIATED APPARATUS (BARRIER). THE SUM OF THE MAX UNPROTECTED CAPACITANCE (Ci) AND MAX UNPROTECTED INDUCTANCE (Li), INCLUDING THE INTERCONNECTED CABLING CAPACITANCE (Cable) AND CABLING INDUCTANCE (Liable), MUST BE LESS THAN THE ALLOWABLE CAPACITANCE (Ca) AND INDUCTANCE (La) DEFINED BY THE ASSOCIATED APPARATUS. IF THE ABOVE CRITERIA ARE MET THAN THE COMBINATION MAY BE CONNECTED.
  3. INSTALLATION OF THE LCP200 IS SUCH THAT ITS LOOP TERMINALS WILL BE CONNECTED IN PARALLEL WITH OTHER INTRINSICALLY SAFE APPARATUS LOOP TERMINALS. THE WIRING COMING FROM THE BARRIER INTO THE HAZARDOUS LOCATION MAY BE TERMINATED AT EITHER THE INTRINSICALLY SAFE APPARATUS, OR AT THE LCP200.
  4. MAXIMUM SAFE AREA VOLTAGE MUST NOT EXCEED 250 VRMS
  5. THE ENCLOSURE CONTAINS NON-METALLIC ENCLOSURE PARTS. TO PREVENT THE RISK OF ELECTROSTATIC SPARKING, THE NON-METALLIC SURFACE SHALL BE CLEANED WITH A DAMP ÇÎT.

Figure 5. LCP200 ATEX/IECEx Nameplate, Intrinsically Safe

EMERSON-LCP200-Local-Control-Panel-fig-5

Bûyera teqînê

Mercên Taybet ên Bikaranînê
  1. The enclosure contains non-metallic enclosure parts. To prevent the risk of electrostatic sparking, the non-metallic surface shall be cleaned with a damp kinc.
  2. The flameproof joints of the equipment are not intended to be repaired. Consult the manufacturer if repair of the joints is necessary.
  3. The electronics compartment rear cover is assembled and torqued at the factory and is not to be removed by the end user.
  4. Consult the manufacturer for genuine replacement terminal cover fasteners. The fasteners are 316 stainless steel, bolt class A4-70, sized M6 x 1 mm x 15 mm.
Notes

Ambient temperature rating: -40 ° C ≤ Ta ≤ + 65 ° C

  1. Install unit in the area of low risk from mechanical hazards.
  2. Install per drawing GG55194, shown in Figures 6, 7, and 8, as indicated on the nameplate.
  3. Veguheztina hêmanan dibe ku ewlehiya hundurîn xirab bike.
    1. Refer to table 2 for approval information.

Table 2. Approval Information, ATEX/IECEx

Şehade Şehadet Hatiye bidest xistin Loop Hemematîk Germî Navê dizî
 

 

 

ATEX IECEx

ATEX: FM21ATEX0024X IECEx: IECEx FMG 21.0016X

Ex eb ia mb IIC T6 Gb Ex ta IIIC T85°C Da

Ex db ia IIB T6 Gb Ex db ia IIC T6 Gb

Install Per Drawing GG55194 (shown in figure 6, 7, and 8)

 

 

 

Per Drawing GG55194 (shown in figure 6, 7, and 8)

 

 

Gas: T6 Dust: T85 C

Figure 6. Explosion-proof, LOOP Power, ATEX/IECEx

  • Wiring Configuration A (LOOP-Powered only) See Figure 8 Notes

EMERSON-LCP200-Local-Control-Panel-fig-6

Figure 7. Explosion-proof, External Power 24V, ATEX/IECEx

  • Wiring Configuration B (External 24V Only) See Figure 8 Notes

EMERSON-LCP200-Local-Control-Panel-fig-7

Figure 8. Notes

AGAHÎ: ASSOCIATED APPARATUS MANUFACTURER’S INSTALLATION DRAWING MUST BE FOLLOWED WHEN INSTALLING THIS EQUIPMENT.

  1. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE CANADIAN ELECTRIC CODE, PART 1 OR NEC NFPA AND ANSI/ISA RP12.06.01.
  2. THE ENCLOSURE CONTAINS NON-METALLIC ENCLOSURE PARTS TO PREVENT THE RISK OF ELECTROSTATIC SPARKING. THE NON-METALLIC SURFACE SHALL BE CLEANED WITH A DAMP ÇÎT.
  3. DUST-TIGHT CONDUIT SEAL MUST BE INSTALLED WITHIN 18” WHEN INSTALLED IN CLASS II AND CLASS III ENVIRONMENTS.
  4. THE NAMEPLATE IS PROVIDED WITH BOXES THAT THE END USER/INSTALLER MUST CHECK OR ETCH FOR THE PROTECTION METHOD USED ACCORDING TO THE INSTALLATION.
  5. BALDAYNÎ: USE FASTENERS WITH YIELD STRESSEMERSON-LCP200-Local-Control-Panel-fig-4 450 MPa.
  6. THE END USER SHALL CLOSE ANY UNUSED ENTRIES WITH SUITABLY CERTIFIED BLANKING ELEMENTS.
  7. FOR ZONES APPLICATIONS, CONNECTION OF THE INTERNAL GROUND IS REQUIRED AS CONNECTION OF THE EXTERNAL GROUP IS OPTIONAL.

Figure 9. LCP200 ATEX/IECEx Nameplate, Explosion-proof, Group IIC

EMERSON-LCP200-Local-Control-Panel-fig-8

Figure 10. LCP200 ATEX/IECEx Nameplate, Explosion-proof, Group IIB

EMERSON-LCP200-Local-Control-Panel-fig-9

Ne Emerson, Çareseriyên Otomasyona Emerson, ne jî yek ji saziyên girêdayî wan berpirsiyariya hilbijartin, bikar an parastin û hilbera hilberek nagire ser xwe. Berpirsiyariya ji bo hilbijartin, karanîn, û parastina guncan a her hilberê tenê bi kiriyar û bikarhênerê dawîn re dimîne.

Fisher is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.

Naverokên vê weşanê tenê ji bo mebestên agahdariyê têne pêşkêş kirin, û dema ku hemî hewil hate dayîn ku rastbûna wan bête piştrast kirin, ew ne wekî garantiyê an garantiyê têne vegotin, eşkere an jî bête gotin, di derheqê hilber an karûbarên li vir hatine vegotin an karanîna wan an sepandin. Hemî firotan ji hêla şert û mercên me ve têne rêve kirin, ku li ser daxwazê ​​hene. Em mafê xwe digirin ku sêwiran an taybetmendiyên hilberên wusa di her demê de bêyî agahdarî biguherînin an baştir bikin.

Çareseriyên Otomasyona Emerson

  • Address: Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 France Dubai, Emiratên Erebî yên Yekbûyî Singapore 128461 Singapore
  • www.Fisher.com

2018, 2021 Fisher Controls International LLC. Hemû maf parastî ne.

Belge / Çavkanî

EMERSON LCP200 Local Control Panel [pdf] Rêbernameya Rêbernameyê
LCP200 Local Control Panel, LCP200, Local Control Panel, Control Panel, Panel
EMERSON LCP200 Local Control Panel [pdf] Rêbernameya Rêbernameyê
LCP200 Local Control Panel, LCP200, Local Control Panel, Control Panel

Çavkanî

Leave a comment

E-maila te ne dê bê weşandin. qadên pêwîst in *