KMC CONTROLS BAC-12xxxx Sensors and Thermostats 

KMC Sensors and Thermostats

KMC Controls manufactures a variety of pneumatic, analog electronic, and digital sensors and thermostats. Some sense only one variable (e.g., temperature), while others sense multiple variables (e.g., humidity and CO2). “Sensors” are used in diverse HVAC and Building Automation System (BAS) applications and are closely related to several other types of devices:

  • Sensors measure a physical characteristic of an environment and provide a signal corresponding to those properties. Sensors may be stand-alone or integrated within a control device (e.g., a thermostat).
  • Transmitters are also sensors, but take a relatively small (and passive) sensor signal (e.g., the resistance of a thermistor in response to a temperature) and convert it into an active voltage (e.g., 0–5 VDC) or active current (e.g., 4–20 mA). Boosting the signal allows greater distance between the sensor and the controller.
  • Transducers convert one kind of energy into another. The physics may be different, but they can function as sensors. In building automation, transducers may convert pressure into voltage or current (or vice versa) or voltage signals into current signals (or vice versa).
  • In HVAC and BAS applications, many sensors, transmitters, and transducers perform essentially the same function, sensing a physical characteristic and providing a signal to an external control device. Thermostats, on the other hand, contain a sensor integrated with a control device. Thermostat technology ranges from simple bimetallic switches to sophisticated digital devices.

See also the Sensor and Thermostat Selection Fundamentals white paper. For details about the various models in this document, see the product data sheets and other documentation on the KMC Controls web site.

Thermostats (Integrated Room Temperature Sensor Plus Controller)

TYPICAL APPLICATIONSTYPEDISPLAYFEATURESMODELS
AHU, FCU, HPU, RTU, and Custom ApplicationsDigital B-AACLCDBACnet Advanced Application Controller; optional humidity, motion, and CO2 sen- sors; programmableBAC-12xxxx, BAC-13xxxx, and BAC-14xxxx FlexStat
FCU, HPU, RTUDigital B-ASCColor LCDBACnet Application Specific Controller; optional humidity and motion sensors, configurableBAC-4xxx- CW000x AppStat
FCU and Baseboard HeatingAnalog ElectronicLCDSix-wire modular jack, single setpointCTE-5201-16
VAV, FCU, Base board Heating, and Chilled BeamAnalog ElectronicLCD“Universal” analog electronic replacement, dual setpoint, two analog outputsCTE-5202
VAVAnalog ElectronicMechanical Indicator on ScaleDesigned for use with CEE/CEP/CSE/CSP- 4xxx controller-actuators, single and dual setpoints (replaced by CTE-5202)CTE-100x and CTE-110x
VAVAnalog ElectronicMechanical Indicator on ScaleDesigned for use with CSP-500x control- ler-actuators, single and dual setpoints (replaced by CTE-5202)CTE-510x
VAV and FCUPneumaticMechanical Indicator on Scale1- and 2-pipe, DA and RACTC-16xx

Temperature  Sensors (Room)

TYPEDISPLAYFEATURESMODELS
DigitalLCDFor BAC/KMD-58xx and BAC/KMD-7xxx controllers, optional humidity and motion sensorsKMD-1xxx NetSensor
DigitalLCDFor BAC-8xxx SimplyVAV controller-actuatorsSTE-8xxx NetSensor
DigitalLCDFor BAC-59xx and BAC-9xxx controllers; optional humidi- ty, motion, and CO2 sensorsSTE-9xxx NetSensor
Thermistor, 10K, Type II and TransmitterLCD or NoneThermistor only or active voltage option, override and setpoint adjustment options, screw terminals or modular jack connectionSTE-60xx
Thermistor, 10K, Type IIINoneFlat wall plate with hidden thermistorSTE-1430
Analog Electronic TransmitterNoneWall-mounted humidity transmitters with temperature sensors (thermistors)THE-1102 and THE-1105
Analog Electronic TransmitterNoneFor use with CTE-110x/510x thermostatsTTE-1001

Temperature Sensors (Other)

TYPEDISPLAYFEATURESMODELS
Analog Electronic (Thermistor)NoneDuct, immersion, outside air, strap-on optionsSTE-14xx
Analog Electronic (Thermistor)NoneDuct-mounted humidity transmitter with temperature sensorTHE-1002

Analog Electronic (Thermistor)NoneDuct flow sensor with temp. sensing (for REE-1005)SSE-20xx
Analog Electronic (Thermistor)NoneDuct temperature transmitter for use with CEE-11xx remote thermostat controllersTTE-2001

Humidity Sensors

TYPEDISPLAYFEATURESMODELS
DigitalLCDFor BAC/KMD-58xx and BAC/KMD-7xxx controllers, optional humidity and motion sensorsKMD-1xxx NetSensor
DigitalLCDFor BAC-8xxx SimplyVAV controller-actuatorsSTE-8xxx NetSensor
DigitalLCDFor BAC-59xx and BAC-9xxx controllers; optional humidi- ty, motion, and CO2 sensorsSTE-9xxx NetSensor
Analog Electronic (Thermistor)NoneDuct-mounted humidity transmitter with temperature sensorTHE-1002
Analog Electronic TransmitterNoneCompact wall-mounted humidity transmitter with temper- ature sensor (thermistor)THE-1102
Analog Electronic TransmitterNoneWall-mounted humidity transmitter with temperature sensor (thermistor)THE-1105

  CO, CO2, and Smoke Sensors

TYPEDISPLAYFEATURESMODELS
Smoke—Analog Electronic (Contacts)NoneDuct smoke detectorCAE-1103
CO—Analog Elec- tronicLCDCO sensors, room and ductSAE-11xx
CO2—Analog Elec- tronicLCDCO2 sensors, room and ductSAE-10xx
CO2—DigitalLCDDigital wall sensor for BAC-59xx and BAC-9xxx controllersSTE-9xxx NetSensor

Flow and Pressure Sensors and Pickup Tubes

TYPEDISPLAYFEATURESMODELS
Analog ElectronicNoneFor use with CEP-4xxx controllersSSE-1000/2000
Pneumatic (but used with electronic and digital controller)NonePickup tubes (also known as pitot tubes) for use with controllers that have flow and pressure sensors, or with a TPE-1475-2x pressure transducer wired to a controllerSSS-1xxx
Analog Electronic TransducerNoneGauge pressure transducers (P-E/I)TPE-1464-x
Analog Electronic TransducerNoneLow pressure transducersTPE-1475-2x and TPE-1477-2x
Analog Electronic TransducerNoneLiquid differential pressure transducers (P-E/I)TPE-1483-x

Miscellaneous

For convenience in installing a complete BAS, KMC Controls sells to our customers a large variety of Veris data servers, current transformers, monitors, meters, sensors, and accessories. For full Veris product descriptions and specifications, go to Veris.com and enter the part number in the Search field at the top of the page. See also the Veris catalog.

Digital/Electronic Handling Precautions

For digital and electronic sensors, thermostats, and controllers, take reasonable precautions to prevent electrostatic discharges to the devices when installing, servicing, or operating them. Discharge accumulated static electricity by touching one’s hand to a securely grounded object before working with each device.

Important Notices

The KMC logo and KMC Controls are registered trademarks of KMC Controls, Inc. Other products and name brands mentioned may be trademarks of their respective companies or organizations.
All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language in any form by any means without the written permission of KMC Controls, Inc. The material in this document is for information purposes only. The contents and the product it describes are subject to change without notice. KMC Controls, Inc. makes no representations or warranties with respect to this document. In no event shall KMC Controls, Inc. be liable for any damages, direct or incidental, arising out of or related to the use of this document.

Support

Additional resources for product specifications, installation, configuration, application, operation, programming, upgrading and much more are available on the KMC Controls web site (www.kmccontrols.com). To see all available files, log-in to the KMC Partners site.

6© 2023 KMC Controls, Inc.
Specifications and design subject to change without notice AG151026D AG151026E