ដើម្បីដំឡើង Eaton 9PXM Bypass Power Module in a rack, follow these steps as outlined in the user manual:
1. Install the 4-post rail kit included with the BPM.
2. Place the BPM on the rails and push it into the rack, ensuring that the breakers face the front of the rack and the BPM wiring terminals face the rear of the rack.
3. Push the BPM past the back of the rack to access the rear wire access-point covers and the wire access panel cover.
4. Remove the wire access-point covers.
5. Remove the access panel cover.
6. Wire the BPM according to the provided instructions.
7. After wiring is complete, replace the covers removed in steps 4 and 5.
8. Push the BPM past the front of the rack to allow access for mounting ears installation.
9. Install the mounting ears to the BPM using the provided screws.
10. Push the BPM into the rack and secure the mounting ears to the rack using the provided screws.
Following these steps will ensure that the Eaton 9PXM Bypass Power Module is properly installed in a rack, providing reliable power distribution and mounting options for your UPS system.