To connect multiple Solis inverters to one Solis S3-WIFI-ST data loggerអ្នកត្រូវអនុវត្តតាមជំហានទាំងនេះ៖
1. **Daisy Chain the Inverters:** Connect the inverters together using RS485 communication cable. The logger can support a maximum of ten inverters. If you have more than ten inverters, additional loggers must be installed.
2. **Plug the Data Logger:** Plug the data logger into the first inverter in the daisy chain.
3. **Adjust Inverter Addresses:** Set the address for each inverter in the chain. The first inverter should be set to address 01. Each subsequent inverter in the chain must be set to a number other than 01. You can adjust the address by accessing the Settings menu of each inverter and navigating to the Address submenu.
4. **Commission the Logger:** Commission the logger as you would normally. Each inverter in the daisy chain will populate into SolisCloud once the logger transmits the first data packet.
By following these steps, you can successfully connect multiple Solis inverters to one Solis S3-WIFI-ST data logger for remote monitoring of your system.