ចម្លើយ

ថ្ងៃទី 04 ខែកញ្ញា ឆ្នាំ 2025 - ម៉ោង 04:28 ព្រឹក
The permissible ambient temperature ranges for the EATON GHG 624 Explosion-Protected Residual Current Operated ឧបករណ៍បំបែកសៀគ្វី are crucial for ensuring the proper functioning and safety of the device. According to the instruction manual, the ambient temperature range for the GHG 624 series varies depending on the size and category of the application. For exampលេ៖
- For IIC size 1 to size 4, the ambient temperature range is -20°C to +55°C for Serie A and Serie E.
- For IIB size 1 to size 2, the ambient temperature range is -45°C to +55°C for Serie A and Serie E.
- For IIB size 3 to size 4, the ambient temperature range is -20°C to +55°C for Serie A and Serie E.
It's important to note that the operating temperature range refers to the adherence to the explosion protection parameters and defines the maximum permissible temperatures of the materials of the flameproof enclosure. Any deviations from these specified temperature ranges should be agreed upon with the manufacturer, Cooper Crouse Hinds.
Ensuring that the ambient temperature remains within the specified ranges is essential to maintain the safety and performance of the circuit breaker in hazardous environments. Failure to adhere to these temperature limits may compromise the device's functionality and safety features.
បន្ថែមមតិយោបល់ថ្មី។