ចម្លើយ

ខែសីហា 26, 2025 - 10:59 PM
To properly wire the GE current ED28 Type B ភ្លើង LED គ្រោះថ្នាក់ Lamp to your existing luminaire, follow these steps based on the installation guide:
1. **Loosen the xxxx that holds the ballast housing and cover together.**
2. **Hinge open the ballast cover and separate the quick disconnect function located between the cover and housing.**
3. **Cut the black and white wires from the quick disconnect to the ballast circuitry, leaving as much wire attached to the quick disconnect as possible. Ensure the green ground wire remains connected.**
4. **Cut the white (neutral) and color (hot) wires from the lamp អ្នកកាន់នៅចំកណ្តាលផ្ទះ ballast ដោយបន្សល់ទុកនូវខ្សែជាច្រើនដែលភ្ជាប់ទៅនឹង lamp holder as possible.**
5. **Strip 3/8 inch from the snipped quick disconnect wires and the snipped lamp holder wires. Use the included wire connectors to connect white to white and black to color (may be black).**
6. **Reconnect the mains quick disconnect device and ensure no wires are pinched when tightening the cover xxxx .**
By following these steps, you can safely and correctly wire the GE current ED28 Type B LED Hazardous Rated Lamp to your existing luminaire. Remember to always consult a qualified electrician if you are unsure about any part of the installation process.