If the Power LED on your WATTS 294EXP Smart Boiler Expansion control is not lit, follow these troubleshooting steps as outlined in the user manual:
1. **Check Supply Voltage**: Use an electrical meter to check that the supply voltage is between 103.5 and 126.5 V (ac). If the supply voltage is within this range and the Power LED remains off, the control may be faulty.
2. **Verify Wiring Connections**: Ensure that the boiler expansion wiring terminals 1, 2, and 3 are connected using 3-conductor 18 AWG LVT wire if the connections are less than 100 feet (30 m). If the connections exceed 100 feet (30 m) or are installed in high radio-frequency environments, use 3-conductor 22 AWG shielded-twisted pair wire. The wiring is polarity sensitive, so double-check that the wire color codes are correctly connected to the terminal locations.