To configure the BACnet MS/TP settings for the ModMAG M2000 electromagnetic flow meterសូមអនុវត្តតាមជំហានទាំងនេះ ដូចដែលបានរៀបរាប់នៅក្នុងសៀវភៅណែនាំអ្នកប្រើប្រាស់៖
1. Power on the M2000 meter.
2. Navigate in the menu to Main Menu > Communications > Daughterbrd Config.
3. Configure the settings according to the table below:
- BACnet MS/TP Baud: Set the baud rate of the BACnet MS/TP network (common settings are 9600, 19200, 38400, and 76800).
- BACnet MS/TP MAC ID: Set the BACnet MS/TP Device ID of the module/meter (max value = 127).
- BACnet Max Master: Set the max master variable for the device (max value = 127).
- BACnet Instance: Set the BACnet Instance number (unsigned decimal number ranging from 0 to 4,194,302).
4. After configuring all parameters, exit the menu system back to the M2000 Home screen.
5. Cycle power to the M2000 meter for any daughterboard configuration changes to take place.
It is important to ensure that the BACnet MS/TP settings are correctly configured to establish proper communication between the ModMAG M2000 flow meter and the building automation system. Refer to the សៀវភៅណែនាំអ្នកប្រើប្រាស់ for additional details and troubleshooting tips if needed.