ដើម្បីភ្ជាប់ ATS unit to the building power supply network, you can follow the wiring diagrams provided in the manual. There are three recommended wiring options:
1. Single-Phase Connection: In this case, the maximum current from the external network is 50A. You will need to connect the generator via a 32A 230V CEE socket. The generator must be grounded using either the xxxx connection or the PE pin in the generator CEE socket. The N pin (neutral) in the generator sockets is NOT connected to the generator housing and must be connected to the main earthing busbar as a separate cable at the point of connection of the neutral from the generator on the AVR for the TN power supply system.
2. Three-Phase Connection: In this case, the maximum current from the external network is 25A per phase. The generator must be connected via a 32A 230V CEE socket. The generator must also be grounded using either the xxxx connection or the PE pin in the generator CEE socket. The N pin (neutral) in the generator sockets is NOT connected to the generator housing and must be connected to the main earthing busbar as a separate cable at the point of connection of the neutral from the generator on the AVR for the TN power supply system.
Please note that connecting the ATS unit to the mains should only be done by a qualified technician. It is important to follow all local laws and regulations regarding electrical connections.