To connect and wire the ប្រព័ន្ធសំណាញ់ HYTRONIK QCB01/BLESIDអនុវត្តតាមជំហានទាំងនេះ៖
1. Make sure to disconnect the power supply before starting the installation.
2. Identify the input and output terminals on the QCB01/BLESID device. In the middle of the device, there is a pre-installed Bluetooth 5.0 SIG mesh controller module.
3. Choose the appropriate controller module (HBTD8200S/F or HBTD8200S/F/CA) based on your requirements. Each controller module has 8 luminaire outlets as one channel (1 x 8).
4. The default rating for the controller module is 400VA capacitive and 800W resistive. If you need a higher loading capability, a special version with a maximum 10A capability can be requested.
5. The QCB01/BLESID device has a Wieland 4-pole terminal base (L', N, E, Em) for luminaire outlet connections.
6. The terminal capacity for wiring is 0.75 - 4.0mm2, with a maximum of 2 x 2.5mm2.
7. Ensure that the installation meets the minimum height requirement of 140mm, including connectors and cables.
8. Refer to the provided wiring diagram for the specific model (QCB01/BLE-S or QCB01/BLE-SCA) to understand the wiring connections.
9. If you need to perform an emergency test using a local lighting switch and local emergency test switch, follow the instructions provided in the manual. Make sure not to wire across phases.
10. If you have a central emergency test switch, you can perform an emergency test using it. Again, do not wire across phases.
11. If you need to take power from a conduit box, you can use the ceiling rose QCCR01. It provides a spacious termination space for easy wiring.
សូមចំណាំថា ស ការដំឡើង of this device should be carried out by a specialist in accordance with electrical technical regulations.