Operations Manual

NP2 + PLUS

How to use the NP2 + PLUS

Plug the detector into an 11-pin relay base socket or wiring harness. The detector will light up the segment display screen with a factory setting of 5. Pull the desired vehicle onto the loop, and you will see an array of red, yellow, and green LEDs next to the display, indicating the sensitivity strength of the detector. In most applications, the setting of 5 should suffice, but loop and vehicle size play a part in the optimal settings.

A compact, blue-cased electronic module labeled 'NP2+' with a digital display showing '8'. The front panel features several buttons, including 'SENS/PROG', 'FREQ/PROG', 'DETECT', 'RELAY 2', and 'RESET', along with indicator LEDs.

Adjusting the Sensitivity

  1. Remove the desired vehicle from the loop.
  2. Press and hold down the up-arrow button (⬆️) until you see a flashing blue dot on the LED segment screen and a single red LED appear. This puts the detector in EZ-TUNE mode, allowing sensitivity settings to be adjusted. While in this mode, no signal will be sent to the gate operator.

Warning: DO NOT PLACE A VEHICLE, EQUIPMENT OR PERSON IN THE PATH OF THE GATE!!

  1. Pull the vehicle directly onto the loop.
  2. Use the UP (⬆️) and Down (⬇️) arrows to adjust the sensitivity to the desired level.
  3. Ideally, you will want the full array of LEDs to light up (2 red ?, 2 yellow ?, 2 green ?) for optimal detection.

Press the reset button [reset button] and a single green LED will appear for 5 seconds to lock in the settings.

Test the settings by running the vehicle over the loop to see if you get a full array of LEDs to appear.

Adjusting the Frequencies

  1. Press and hold down the down-arrow button (⬇️) until you see a flashing blue dot on the segment screen and a single green LED appear. This puts the detector in EZ-TUNE mode, allowing frequency settings to be adjusted.
  2. Use the up (⬆️) and down (⬇️) buttons to select the desired frequency. The frequency numbers will flash on the segment display.
  3. Alternate the frequency of each detector in the rack to prevent crosstalk.
  4. To lock in the setting, press the reset button [reset button], and a single green LED will appear for 5 seconds to lock in the settings.

Additional Options

There is a 6-position DIP switch on the back of the detector for site-specific needs. Press the reset button [reset button] to implement the desired setting. If there is a fault, 2 yellow LEDs ?? will appear, and the letters 'OC' represent an open circuit, while 'SC' represents a shorted loop.

Relay 2

Pulse Length

Switch 4 provides for either a 250mS pulse length or a 500mS pulse length. Switch 4 in the OFF position provides 250mS (standard) pulse length. Switch 4 in the ON position provides a 500mS pulse length.

Operating Mode

Switches 5 and 6 determine the operating mode for Relay 2. The 4 modes are as follows:

  • Switch 5 and Switch 6 OFF provides pulse-on-entry.
  • Switch 5 ON & Switch 6 OFF provides pulse-on-leaving.
  • Switch 5 OFF & Switch 6 ON provides for presence.
  • Switch 5 and Switch 6 ON provides a fault output.

Specifications

Front Panel Controls

The NP2+ has three Front Panel pushbutton switches:

  • UP / sensitivity programming mode: Press and hold for 3 seconds to enter sensitivity mode. UP and DOWN buttons may be used to step through sensitivity levels.
  • DOWN / frequency programming mode: Press and hold for 3 seconds to enter frequency mode. UP and DOWN buttons may be used to step through the frequency selections.
  • Reset: Front panel reset performs a hard reset of the detector and resumes operation using the last programmed settings.

Indications

  • Single digit 7 Segment Multifunction Display:
    • In normal operation, this display shows the current sensitivity level.
    • In sensitivity programming mode, the sensitivity is displayed and may be changed by manipulating the UP/DOWN pushbuttons.
    • In frequency programming mode, the frequency of the loop oscillator in kHz is displayed. This frequency may be changed by manipulating the UP/DOWN pushbuttons. The display alternates digits to show the 'tens' digit, then the 'ones' digit, and then a pause.
    • When the detector is in fault, the display shows 'OC' for open circuit loop or 'SC' for short-circuited loop.
    • When delaying a signal, the display will show 'dL', and when extending a signal, 'En' will be displayed.
  • 6 segment bargraph:
    • 2 red ?, 2 yellow ?, and 2 green ? segments.
    • Shows depth of detection as a vehicle passes over the detection zone.
    • Shows the level of interference from adjacent loops.
  • Detect & Relay 2 LEDs: LEDs show the status of both Relay outputs.

Additional Indications

  • When the detector is in fault, two yellow LEDs ?? will be illuminated.
  • When the detector is tuning to the loop, a green LED ? will be illuminated.

Outputs

The NP2+ has two relay outputs: a primary Relay 1 for normal detection operation and a secondary Relay 2 for additional functionality. Relay 1 is Fail Safe (provides a constant closure on power fail). Relay 2 is Fail Secure (no closure on power fail). Optional Fail Secure Relay 1 operation is available.

Output Rating: Relay Contact Closure, 125VAC, 60VDC 1A.

Rear Panel DIP Switch

A six-position DIP switch on the back of the unit allows the selection of additional operational modes.

Switch No.OFFON
1No Extend5 Second Extend
2No Delay2 Second Delay
360 Minute PresencePermanent Presence
420ms Pulse500 Pulse
Switch 5Switch 6Relay 2 Function
OFFOFFPulse on Entry
ONOFFPulse on Leaving
OFFONPresence
ONONFault

Other Specifications

  • Supply Voltage: 12 to 24 volts AC or DC, 1VA max, 60mA max. Note: Incorrect voltage supplied to the unit will not result in damage; the unit will simply not operate until correct voltage is supplied. No fuses need to be reset.
  • Inductance Range: 20uH to 1500uH.
  • Temperature Range: -30 F to +180 F.
  • Lead-In Length: Up to 2500 ft. with proper lead-in and loop.
  • Mechanical: 3.25" H x 3.75" D x 1.375" W. incl. connector
  • Connector: 11P Amphenol Style
Pin #Function
1Power (+)
2Power (-)
3Relay 2 N.O.
4Earth
5Relay 1 Common
6Relay 1 N.O.
7Loop
8Loop
9Relay 2 Common
10Relay 1 N.C.
11Relay 2 N.C.

Models: NP2-PLUS Loop Detector, NP2-PLUS, Loop Detector, Detector