VARIMETER IMD RN 5897/300 Insulation Monitor

Translation of the original instructions

Your Advantages

Product Description

The insulation monitor RN 5897/300 of the VARIMETER IMD family provides best and up to date insulation monitoring of modern IT systems in an optimum and state of the art way fulfilling the relevant standards. The device can be used in the most flexible way for AC, DC and AC/DC systems. The adjustment of the setting values is simple and user friendly done on 3 rotary switches on the front of the device. Via multicolor LED the device status is indicated easy to read. With a sealable transparent cover the device is protected against manipulation.

Features

Circuit Diagram

The circuit diagram shows connections for L(+), L(-), UH, A1(+), A2, PE1, PE2, and terminal blocks X1, X2, 11, 12, 14, 21, 22, 24. L(+) and L(-) are inputs for the measuring circuit. A1(+) and A2 are for auxiliary voltage. PE1 and PE2 are for the protective conductor. X1 and X2 are for the external control input. Terminals 11, 12, 14 are for Alarm relay K1, and 21, 22, 24 are for Prewarning signal relay K2.

Approvals and Markings

[CE Mark] [cULus Listed Mark] Canada / USA [AC/DC Mark]

Applications

Insulation monitoring of:

Connection Terminals

Terminal designation Signal description
A1(+), A2 Auxiliary voltage AC or DC
L(+), L(-) Connection for measuring circuit
PE1, PE2 Connection for protective conductor
X1, X2 Control input (combined external Test- and Reset-input)
11, 12, 14 Alarm signal relay K1 (1 changeover contact)
21, 22, 24 Prewarning signal relay K2 (1 changeover contact)

Function

Measuring circuit (Insulation measurement between terminals L(+)/L(-) and PE1/PE2)

The device is supplied with DC auxiliary voltage via terminals A1(+) / A2. Switching on the auxiliary voltage (Power-On) is followed by an internal self-test for 12 sec. The test process is visible in the status LED. After this, measurement of the insulation resistance in the measuring circuits begins and the status LED changes to green. The terminals L(+) and L(-) are connected directly to the voltage system to be monitored. A broken wire detection creates a fault signal if there is no low-ohmic connection between both terminals. The type of network (AC, DC, 3NAC) must be selected. Terminals PE1 and PE2 must be connected with 2 separate wires to the protective earth. An interruption of a wire also causes a fault signal. The monitoring of the PE connection cannot be de-activated. To measure the insulation resistance, an active measuring voltage with changing polarity is connected between L(+)/L(-) and PE1/PE2. At the end of a measuring cycle, the actual insulation resistance is produced and indicated. The relays for alarm K1 and pre-alarm K2 switch when dropping under the adjusted response values. The LED changes to orange color on pre-alarm or to red color on alarm.

Manual reset of fault message

The rotary switch "UN" has 2 sections for selecting manual or auto reset. If manual reset is activated, insulation fault signals are stored even if the resistance returns to a healthy state. Pressing the "Reset" button for 2 s resets the alarm signal if the insulation resistance is healthy.

Indicator relay for insulation fault signal

For indicator relays K1 (contacts 11-12-14 for alarm) and K2 (contacts 21-22-24 for pre-alarm), the function (energized on trip or de-energized on trip) can be set via the pre-alarm rotational switch "RA" when the insulation resistance drops below the adjusted response value.

Broken wire detection

The measuring circuits L(+)/L(-) and protective conductors PE1/PE2 are constantly monitored for wire breaks. Broken wire detection between L(+) and L(-) uses a coupled alternating voltage. If this voltage is short-circuited by a low-ohmic connection, the device detects a proper connection. Large capacitances between L(+) and L(-) can cause false readings and should be avoided. Broken wire detection on L(+)/L(-) can be de-activated using rotary switch "RA". Monitoring of PE1/PE2 cannot be de-activated.

Device test functions

Two test functions are implemented: "Self-test" and "Expanded test".

Test Signal Timing:

Diagram Description: The diagram shows the measuring voltage (positive and negative phases) over time during self-test (approx. 12s duration) and continuous extended test (approx. 10s duration). It also indicates the relay state (Alarm/No Alarm) and the test signals.

Function

Behaviour with internal device faults

If internal device faults are detected during the test function, the LED flashes continuously red. Indicator relays K1 and K2 switch to the alarm state.

Behavior on faulty connection

Broken wire on L(+)/L(-): Measurement is disabled. Relays K1 and K2 go into alarm state, LED shows red flash code 1. Fault resets automatically after interruption is removed (max. 2 min reaction time). Stored alarm values remain.

Broken wire on PE1/PE2: Causes the same reaction as interrupting the measuring circuit, but the LED indicates red flash code 2.

External control input

Terminals X1/X2 can be connected to an external combined Test-/Reset button. Bridging X1/X2 for approx. 1 s starts the test mode. Bridging for > 3 s resets a stored alarm.

Programming/setting of parameters/set-up of the insulation monitor

All settings are done with 3 rotary switches behind a sealable transparent cover.

New settings are accepted without device restart.

Function Diagram

The diagram illustrates the hysteresis function for the alarm (K1) and pre-alarm (K2) relays, showing states like "Open circuit operation" and "De-energized on trip" for different configurations (e.g., energized on trip, de-energized on trip, manual reset).

Flashing Codes Status LED

LED-colour: Red

LED-colour: Orange

Indicators

The operational status of the device is indicated on a 3-colour LED:

Error Indication

Flash code red Status-LED Failure cause Failure recovery
1 Broken wire detection on L(+)/L(-). Check measuring circuit L(+) and L (-).
2 Broken wire detection on PE1/PE2. Check protective earth connections PE1 and PE2.
continuously flashing Internal failure detected in test mode. Press test button again or restart the unit by interrupting the auxiliary supply temporarily. If the fault remains permanent, send device back to manufacturer for examination.
continuously flashing Faulty calibration values detected in device memory. Send device back to manufacturer for recalibration and examination.

Notes

WARNING Risk of electrocution! Danger to life or risk of serious injuries.

! Attention!

Info Attention!

Technical Data

Measuring circuit L(+) / L(-) to PE1 / PE2

Auxiliary voltage input A1(+)/A2

Nom. Voltage Voltage range Frequency range
AC/DC 24 ... 60 V AC 19 ... 68 V
DC 16 ... 96 V
45 ... 400 Hz; DC 48% W*)
AC/DC 85 ... 230 V AC 68 ... 276 V
DC 67 ... 300 V
45 ... 400 Hz; DC 48% W*)
DC 12 ... 24 V DC 9.6 ... 30 V W*) ≤ 5%

*) W = Permitted residual ripple of auxiliary supply

Nominal consumption:

Control input X1/X2 for external kombinierte Test-/Reset-Taste

Outputs

General Data

Clearance and creepage distances

Measuring circuit L(+)/L(-) to auxiliary voltage A1(+)/A2 and indicator relay contacts K1, K2 Auxiliary voltage A1(+)/A2 to indicator relay contacts K1, K2 Indicator relay contact K1 to indicator relay contacts K2
Rated impulse voltage / pollution degree 4 kV / 2 4 kV / 2 4 kV / 2

EMC

Degree of protection

Vibration resistance

Thermoplastic with VO behaviour according to UL subject 94. Amplitude 0.35 mm, Frequency 10 ... 55 Hz (IEC/EN 60068-2-6). Frequency 2 ... 13.2 Hz, 13.2 ... 100 Hz, acceleration ± 0.7 gn (IEC/EN 60068-2-6)

Shock resistance

10 gn / 11 ms, 3 pulses (IEC/EN 60068-2-27)

Climate resistance

40/070/04 (IEC/EN 60068-1)

Terminal designation

Dimensions

Width x height x depth: 52.2 x 90 x 71 mm

Classification to DIN EN 50155

UL-Data

Info Technical data that is not stated in the UL-Data, can be found in the technical data section.

CCC-Data

Info Technical data that is not stated in the CCC-Data, can be found in the technical data section.

Standard Types

RN 5897.12/300/61

RN 5897.12/300/61

RN 5897.12/300/61

Outputs:

Accessories

Flush mounting kit

Order reference: KU 4087-150/0056598

For universal use with:

Connection Examples

Single phase mains, isolated from earth

Diagram shows connection for a single-phase mains (AC 0...300V, 40...1000Hz) to the RN5897/300. L1 and L2 are connected to L(+) and L(-). Auxiliary voltage UH is supplied to A1(+)/A2. PE is connected to PE1/PE2. An external combined Test/Reset button is connected to X1/X2. The setting of the type of network is AC.

Ungrounded mains (3N AC)

Diagram shows connection for a 3N AC ungrounded mains (400V/230V, 40...1000Hz) to the RN5897/300. L1, L2, L3, and N are shown. L(+) and L(-) are connected to L1 and L2 respectively. Auxiliary voltage UH is supplied to A1(+)/A2. PE is connected to PE1/PE2. An external combined Test/Reset button is connected to X1/X2. The setting of the type of network is 3N AC.

Ungrounded DC network

Diagram shows connection for an ungrounded DC network (DC 0...300V) to the RN5897/300. L+ and L- are connected to L(+) and L(-). Auxiliary voltage UH is supplied to A1(+)/A2. PE is connected to PE1/PE2. An external combined Test/Reset button is connected to X1/X2. The setting of the type of network is DC.

Notes on Connection Examples:

Characteristics

The graph titled "Max. measuring time in response to line capacitance RN5897/300" plots the maximum measuring time (TMes in seconds) on the Y-axis against the line capacitance (CE in µF) on the X-axis. It shows different curves for response values RE = 1000 kΩ, RE = 100 kΩ, and RE = 1 kΩ. The maximum line capacitance indicated is 30 µF.

Models: RN5897 Insulation Monitor, RN5897, Insulation Monitor, Monitor

File Info : application/pdf, 8 Pages, 655.83KB

0067252 2557514425850

References

Adobe PDF Library 10.0.1

Related Documents

Preview DOLD VARIMETER IMD Insulation Monitor IL 5880 Series - Technical Data and Features
Comprehensive technical specifications, features, and applications for the DOLD VARIMETER IMD Insulation Monitor series (IL 5880, IP 5880, SL 5880, SP 5880), designed for monitoring insulation resistance in AC voltage systems.
Preview VARIMETER IMD Insulation Monitor IL 5881, SL 5881 - DOLD Technical Datasheet
Comprehensive technical datasheet for the DOLD VARIMETER IMD Insulation Monitor models IL 5881 and SL 5881. Details features, applications, function, technical specifications, connection diagrams, and variants for monitoring ungrounded DC voltage systems according to IEC/EN 61557-8.
Preview DOLD RL 9877 RN 9877 Phase Monitor Relays | Technical Specifications & Overview
Comprehensive overview and technical specifications for DOLD RL 9877 and RN 9877 Phase Monitor Relays. Learn about features, applications, product selection, and technical details for these industrial monitoring relays.
Preview DOLD RL 9836 & RL 9854 Voltage Monitor Relays: Technical Overview
Explore the DOLD RL 9836 and RL 9854 Varimeter Series voltage monitor relays. These single-phase AC/DC relays provide reliable overvoltage and undervoltage protection with adjustable settings and no external auxiliary power required. Ideal for industrial applications.
Preview DOLD VARIMETER Level Sensing Relay IL 9151, SL 9151, MK 9151N Technical Data
Detailed technical specifications and application information for the DOLD VARIMETER Level Sensing Relay series, including models IL 9151, SL 9151, and MK 9151N. Features include 1-point and 2-point level control for conductive liquids and powders, adjustable response and release times, and various enclosure versions.
Preview Dold RN5883-001-24-80V Residual Current Monitor - Technical Specifications
Detailed technical specifications for the Dold RN5883-001-24-80V residual current monitor. Features include 10 mA to 3 A selectable trip point, 24-80 VAC/VDC operating voltage, and (2) SPDT outputs. Includes agency approvals and dimensional drawing link.
Preview DOLD VARIMETER IK 8715 Load Shedding Relay - Technical Specifications
Detailed technical specifications, features, application, and wiring diagrams for the DOLD VARIMETER IK 8715 load shedding relay. Learn about its advantages, technical data, and installation. Ideal for energy savings and optimizing electrical connections.
Preview Dold RN5883-011-24-80V Residual Current Monitor Technical Specifications
Technical specifications for the Dold RN5883-011-24-80V residual current monitor. Features include selectable trip points from 10 mA to 3 A, 24-80 VAC/VDC operating voltage, and (2) SPDT outputs. Includes agency approvals and dimensional drawing information.