Core Mitsubishi Heavy VRF & FD Systems Gateway CR-CG-MHI-KNX-01 Quick Start Guide

Core Mitsubishi Heavy VRF & FD Systems Gateway

Quick Start Guide

Model: CR-CG-MHI-KNX-01

Technical Specifications

ConceptDescription
Type of DeviceCore Mitsubishi Heavy VRF & FD KNX Gateway
Power Consumption10mA Max.
Complementary ModeS-Mode, System-B
Dimensions68.50mm X 49.00mm X 19.70mm
Response on AC Unit Faults / DisconnectLED2 Red Flashes (500ms On, 500ms Off)
Number of Inputs2 Digital Inputs
Input Switching TypeDry Voltage Contacts between Input and Common
Input Cable Cross-Section0.5-1mm²(IEC) / 26-16AWG(UL)
Connection Cable Length1m approx
Connection Cable Specification4x0.34mm(29AWG) with Screen for reduced interference
Connection @ AC Unit Equipment SideX, Y
CertificationKNX Certified
ConfigurationConfiguration with ETS

Package Contents

  • CR-CG-MHI-KNX-01
  • Core Mitsubishi Heavy VRF & FD KNX Gateway
  • Connection cable

Components

The device features a compact design with indicator LEDs, buttons, and connection terminals. Dimensions: 68.50 mm (width) x 49.00 mm (height) x 19.70 mm (depth).

Views and Numbered Parts

Front View: Displays indicator LEDs and a programming button.

  1. Status LED
  2. Prog. LED
  3. Prog KEY (Button)

Rear View: Features connection terminals for the AC unit and common ground.

  1. KNX-TP (Terminal)
  2. Input 1 (Terminal)
  3. Input 2 (Terminal)
  4. COM (Terminal)
  5. A/C UNIT (Terminal)

Top View: Indicates the overall depth of the device.

Device Connection

⚠️ Important: Always check the compatibility list before installation.

Connection to the Indoor Unit

The device connects directly to the Air Conditioner Indoor Unit using the provided cable. Do not use any other cable.

  1. Disconnect the main power from the AC unit.
  2. Open the internal controller board of the AC unit.
  3. Locate the X and Y terminals on the AC unit.
  4. Connect the Yellow and Green cables from the supplied installation cable to the X and Y terminals on the AC unit. Polarity does not matter for these connections.
  5. Connect the black connector from the supplied cable to the A/C Unit connector on the device.

Diagram shows the AC indoor unit with X, Y terminals and the device's A/C Unit connector, connected by a 1000 mm cable.

⚠️ Caution: Cutting, shortening, or modifying the cable can cause the device to malfunction.

Connection to the KNX Bus

Connect the device to the KNX TP-1 (EIB) Bus Line.

  1. Disconnect power from the KNX bus.
  2. Connect the device's standard KNX connector (red/black) to the KNX bus, respecting polarity.
  3. Reconnect power to the KNX bus.

Diagram illustrates the connection of the device's KNX connector to the KNX TP-1 (EIB) bus.

Commissioning

Configuration and commissioning require the use of ETS4 or later software. These tasks must be performed by a qualified planner according to the building automation system design.

To configure the device parameters, load the corresponding application program or the Core product database into your ETS program. For detailed information, refer to the application manual available on www.core.com.tr.

Required Commissioning Steps:

  1. Make the electrical connections as described above.
  2. Turn on the bus power supply.
  3. Switch the device operation to programming mode.
  4. Download the physical address and configuration using the ETS program.

Once the download is complete, the device will return to normal operation mode and is ready for use.

Safety Remarks

Warnings

Installation, electrical connection, configuration, and commissioning of this device must only be carried out by qualified personnel, adhering to applicable technical standards and national laws.

  • Electrical connections should only be performed by qualified personnel. Incorrect installation may lead to electric shock or fire. Ensure power is turned off before making connections.
  • Do not connect the main voltage (230V AC) to the digital input or KNX connector of the device.
  • Opening the device housing will immediately void the warranty.

Tampering with the device may compromise its compliance with essential requirements of applicable directives for which it has been certified.

⚠️ Important: Check compatibility list before installation.

Core Bina Otomasyon Sistemleri Ltd. Şti.

Fatih Mahallesi Ege Caddesi No:42/5, Gaziemir - İzmir - Türkiye

Website: www.core.com.tr

Certifications: KNX, CE, RoHS Compliant

Models: CR-CG-MHI-KNX-01 Mitsubishi Heavy Industries Vrf and Fd Systems Gateway, CR-CG-MHI-KNX-01, Mitsubishi Heavy Industries Vrf and Fd Systems Gateway, Industries Vrf and Fd Systems Gateway, and Fd Systems Gateway, Systems Gateway