SmartGen HMC4000RM Remote Monitoring Controller

USER MANUAL

Brand: SmartGen

Company: SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD.

Address: No. 28 Xuemei Street, Zhengzhou, Henan, China

Contact: Tel: +86-371-67988888/67981888/67992951, +86-371-67981000(overseas), Fax: +86-371-67992952

Web: www.smartgen.com.cn/, www.smartgen.cn/

Email: sales@smartgen.cn

All rights reserved. No part of this publication may be reproduced in any material form without written permission. SmartGen reserves the right to change contents without prior notice.

Software Version History:

Date Version Content
2017-08-29 1.0 Original release
2018-05-19 1.1 Change installation dimensions drawing.
2021-04-01 1.2 Change "A-phase power factor" described in 4th Screen of Screen Display to "C-phase power factor".
2023-12-05 1.3 Change lamp test description; Add contents and ranges of parameter setting.

1 OVERVIEW

The HMC4000RM remote monitoring controller integrates digitization, intelligentization, and network technology for remote monitoring systems of single units to achieve remote start/stop functions. It features an LCD display and optional Chinese/English language interfaces, making it reliable and easy to use.

2 PERFORMANCE AND CHARACTERISTICS

Main features include:

3 SPECIFICATION

Table 2 Technical Parameters

Item Content
Working Voltage DC8.0V to DC35.0V, uninterrupted power supply.
Power Consumption <2W
RS485 Communication Baud Rate 2400bps/4800bps/9600bps/19200bps/38400bps can be set
Case Dimension 135mm x 110mm x 44mm
Panel Cutout 116mm x 90mm
Working Temperature (-25~+70)°C
Working Humidity (20~93)%RH
Storage Temperature (-25~+70)°C
Protection Level Front panel IP65
Insulation Intensity Apply AC2.2kV voltage between high voltage terminal and low voltage terminal; The leakage current is not more than 3mA within 1min.
Weight 0.22kg

4 OPERATION

Table 3 Pushbuttons Description

Icon Function Description
? [Stop] Stop Stop running generator in remote control mode; When generator set is at rest, pressing and holding the button for 3 seconds will test indicator lights (lamp test).
? [Start] Start In remote control mode, press this button to start generator-set.
☀️➕ [Brightness Up] Dimmer + Press this button to increase LCD brightness.
☀️➖ [Brightness Down] Dimmer - Press this button to decrease LCD brightness.
? [Lamp Test] Lamp Test After pressing this button, LCD is highlighted with black and all LEDs on the front panel are illuminated. Hold and press this button to eliminate the alarm information of the local controller.
⚙️ [Set/Confirm] Set/Confirm Function is standby.
⬆️ [Up/Increase] Up/Increase Press this button to scroll the screen up.
⬇️ [Down/Decrease] Down/Decrease Press this button to scroll the screen down.

5 SCREENS DISPLAY

Table 4 Screen Display

Screen Display Example Description
1st Screen Generator is running: 1500 RPM, 400 V, 500 kPa, 100 kW. Engine Standby.
Generator is at rest: 1500 RPM, 98 °C, 500 kPa, 24.5 V. Engine Standby.
Engine speed, generator-set UA/UAB voltage; Oil pressure, Load power; Engine status.
2nd Screen Temp 35°C, Power 24.5V; Oil Temp 20°C, D+ 24.5V. Engine water temperature, controller power supply; Engine oil temperature, charger voltage.
3rd Screen UL-L 400 400 400 V; UL-N 230 230 230 V; I 500 500 500 A; P 345 kW Q 0 kvar; Pf 1.00 50.0 Hz. Wire voltage: Uab, Ubc, Uca; Phase voltage: Ua, Ub, Uc; Load current: IA, IB, IC; Load active power, load reactive power; Power factor, frequency.
4th Screen P(kW) Q(kvar) S(kvA)
A: 115 0 115
B: 115 0 115
C: 115 0 115
PF 1.00 1.00 1.00
Active power, reactive power, apparent power display; A-phase kW, A-phase kvar, A-phase kvA; B-phase kW, B-phase kvar, B-phase kvA; C-phase kW, C-phase kvar, C-phase kvA; A-phase power factor, C-phase power factor, C-phase power factor.
5th Screen Total kWh: 0kWh
Total kvarh: 0kvarh
Accumulated active electric energy; Accumulated reactive electric energy.
6th Screen Input ports: 1 2 3 4 5 Input port name.
7th Screen O:C 1 2 3 4 5; 2017-07-15 10:10:10 Input port status; Output port name; Output port status; System present time.
Alarm Screen Warning Alarm; Generator Under Volt. Alarm type; Alarm name.

Remark: If there is no electric parameters displayed, the 3rd, 4th, and 5th screens will be shielded automatically.

6 CONTROLLER PANEL AND OPERATION

6.1 CONTROLLER PANEL

Fig.1 HMC4000RM Front Panel Description:

The front panel features an LCD display and several pushbuttons:

Indicator Light Explanation:

6.2 REMOTE START/STOP OPERATION

6.2.1 ILLUSTRATION

By pressing a button on the host controller HMC4000, users can enter remote control mode to remotely control the HMC4000RM start/stop operation.

6.2.2 REMOTE START SEQUENCE

6.2.3 REMOTE STOP SEQUENCE

7 WIRING CONNECTION

HMC4000RM controller back panel layout:

Fig.2 Controller Back Panel Description: The back panel features terminal connections for power, CAN bus, and RS485 communication, along with a USB port.

Table 5 Description of Terminal Connection

No. Function Cable Size Remark
1 B- 2.5mm² Connected with negative of power supply.
2 B+ 2.5mm² Connected with positive of power supply.
3 NC - Not used
4 CAN H 0.5mm² This port is for expand monitoring interface and reserved temporarily.
5 CAN L 0.5mm² Shielding line is recommended if used.
6 CAN Common Ground 0.5mm² -
7 RS485 Common Ground / Impedance-1200 shielding wire is recommended, its single-end earthed.
8 RS485+ 0.5mm² This interface is used to connect with host controller HMC4000.
9 RS485- 0.5mm² -

NOTE: USB port in the back is system upgrade port.

8 RANGES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS

Table 6 Contents and Ranges of Parameter Setting

No. Item Range Default Description
1 Module Setting RS485 Baud Rate (0-4) 2 0: 9600bps, 1: 2400bps, 2: 4800bps, 3:19200bps, 4: 38400bps
2 Stop Bit (0-1) 0 0: 2 Bits, 1: 1 Bit

9 TYPICAL APPLICATION

Fig.3 HMC4000RM Typical Application Diagram Description: The diagram illustrates a typical application where the HMC4000RM controller is connected to a power supply (represented by a battery symbol with B+ and B- terminals) and a host controller (HMC4000MPU) via RS485 communication.

10 INSTALLATION

10.1 FIXING CLIPS

The controller features a panel built-in design and is fixed by clips during installation:

NOTE: Care should be taken not to over-tighten the screws of the fixing clips.

10.2 OVERALL DIMENSIONS AND CUTOUT

Fig.4 Case Dimensions and Panel Cutout Description: The diagram shows the controller's external dimensions: 135mm width, 110mm height, and 44mm depth. The required panel cutout dimensions are 116mm width and 90mm height.

11 TROUBLESHOOTING

Table 7 Troubleshooting

Problem Possible Solution
Controller no response with power. Check starting batteries;
Check controller connection wirings;
Check DC fuse.
Communication failure Check whether RS485 connections are correct;
Check whether communication baud rate and stop bit are consistent.