RED LION PM-50 Analog Output Module Installation Guide
File info: application/pdf · 4 pages · 915.54KB
Red Lion PMM000I0AN000000 Analog Output Module
PM-50 Analog Output Module - Products for Automation
2 Drawing No. LP1146 Revised 08 2024 SPECIFICATIONS Note: The PM-50 4.3 inch host accepts a maximum of 5 modules while the 3.5 inch host accepts a maximum of 3. Only one module from each function type (i.e. communicatio…
Extracted Text
PM-50 Analog Output Module Installation Guide z Retransmitted analog output z 0 (4) to 20 mA or 0 to 10 VDC, �10 VDC z Removable terminal block Install PM50AO-B Drawing No. LP1146 Revised 08/2024 UL C R US FOR USE IN HAZARDOUS LOCATIONS: LISTED Class I, Division 2, Groups A, B, C, and D T4A IND.CONT. EQ. E317425 MODULE PACKAGE CHECKLIST This product package should contain the items listed below. If any items are missing or damaged, contact Red Lion immediately. - Panel Mount Analog Output Module - Accessory Pack - Installation Guide DIMENSIONS In inches [mm] 1.76 [44.80] 1.76 [44.80] Bottom 1.34 [34.10] SAFETY SUMMARY All safety related regulations, local codes as well as instructions that appear in this document or on equipment must be observed to ensure personal safety and to prevent damage to either the device or equipment connected to it. Do not use these products to replace proper safety interlocking. No software-based device (or any other solid-state device) should ever be designed to be responsible for the maintenance of personnel safety or consequential equipment not equipped with safeguards. Red Lion disclaims any responsibility for damages, either direct or consequential, that result from the use of this equipment in a manner not consistent with these specifications. CAUTION: Risk of Danger Read complete instructions prior to installation and operation of the unit. ATTENTION : Risque de danger Lire les instructions compl�tes avant l'installation et l'utilisation de l'appareil. WARNING - Explosion Hazard - When in hazardous locations, disconnect power before replacing or wiring modules. AVERTISSEMENT - Risque d'explosion - Dans les endroits dangereux, d�branchez l'alimentation �lectrique avant de remplacer ou de c�bler les modules. This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D, or non-hazardous locations only. Cet �quipement est adapt� � une utilisation dans des endroits de classe I, Division 2, Groupes A, B, C, D, ou dans des endroits non dangereux seulement. ORDERING INFORMATION PART NUMBER DESCRIPTION PMM000I0AN000000 Analog Output Module A listing of the entire PM-50 family of products and accessories can be found at www.redlion.net. 1 Drawing No. LP1146 SPECIFICATIONS Note: The PM-50 4.3 inch host accepts a maximum of 5 modules while the 3.5 inch host accepts a maximum of 3. Only one module from each function type (i.e. communication, relay, analog output) can be installed. 1. POWER: Power is supplied by the PM-50 host device. Must use a Class 2 circuit according to National Electrical Code (NEC), NFPA-70 or Canadian Electrical Code (CEC), Part I, C22.1 or a Limited Power Supply (LPS) according to IEC/EN 60950-1 or Limited-energy circuit according to IEC/ EN 61010-1. Max Power: 1.3 W 2. ANALOG OUTPUT: Field installable module Types: 0 to 10 V, �10 V, 0 to 20 mA, or 4 to 20 mA Isolation To Sensor & User Input Commons: 500 Vrms Accuracy: 0 to 10 V or �10 V range: 0.1% of full scale (-10 to 55 �C) 0 to 20 mA or 4 to 20 mA: 0.1% of full scale (18 to 28 �C), 0.25% of full scale (-10 to 55 �C) Compliance for current output: 500 ohm max. (10 V max.) Minimum load for voltage output: 500 ohm min. (20 mA max.) Effective Resolution: Full 16-bit (Signed) Compliance: 20 mA: 500 load max. (self-powered) 3. ENVIRONMENTAL CONDITIONS: Operating Temperature Range: -10 to 55 �C Storage Temperature Range: -40 to 85 �C Vibration to IEC 68-2-6: Operational 5-500 Hz, 2 g Shock to IEC 68-2-27: Operational 20 g Operating and Storage Humidity: 0 to 85% max. RH noncondensing Altitude: Up to 2000 meters Installation Category II, Pollution Degree 2 as defined in IEC/ EN 60664-1. 4. CERTIFICATIONS AND COMPLIANCES: CE Approved EN 61326-1 Immunity to Industrial Locations Emission CISPR 11 Class A IEC/EN 61010-1 RoHS Compliant UL Hazardous: File # E317425 Rugged IP25 enclosure 5. CONSTRUCTION: Plastic enclosure with IP25 rating. For use only in an approved enclosure. 6. CONNECTIONS: High compression cage-clamp terminal blocks Wire Strip Length: 0.32-0.35" (8-9 mm) Wire Gauge Capacity: Four 28 AWG (0.32 mm) solid, two 20 AWG (0.61 mm) or one 16 AWG (2.55 mm) 7. WEIGHT: 1.8 oz (51.1 g) Revised 08 2024 HARDWARE INSTALLATION Installing a Module WARNING - Disconnect all power to the unit before installing or removing modules. AVERTISSEMENT - D�branchez l'alimentation �lectrique de l'appareil avant d'installer ou de retirer des modules. Installation of the product must comply with National Electrical Code (NEC), NFPA-70 or Canadian Electrical Code (CED) or any local regulation Authority. To a 4.3 inch Host It is recommended that a relay module be installed in Module Position 1 only (shown below). Short Side Rear Cover Tall Side Position 1 1. To install a module on the tall side of a 4.3 inch host, align the latches of the module with the host case such that the backplane connector shroud on the module cover aligns with the backplane connector opening in the host case. 2. To install a module on the short side of a 4.3 inch host, rotate the module 180 degrees and align the latches on the host with the module case so that the I/O connector is facing downward. 3. Insert the host latches into the openings in the module case by slightly deflecting the latches inward. 4. Press the module into the host case evenly until the latches engage. 5. Install Module Locks between each module as shown by fully inserting the legs of the Module Locks into the slots in the case until the button on the Module Lock aligns with the hole provided in the case. Press fit the button into the hole. Repeat this installation between each module in your system to provide the most secure installation. 6. When you have finished adding modules, the rear cover should be installed in the same manner as the modules. 2 Revised 08 2024 To a 3.5 inch Host It is recommended that a relay module be installed directly onto the back of the host (shown below), not on the back of any other module. Rear Cover Position 1 1. Align the latches of the module with the host case such that the backplane connector shroud on the module cover aligns with the backplane connector opening in the host case. 2. Insert the module latches into the openings in the host case by slightly deflecting the latches inward. 3. Press the module into the host case evenly until the latches engage. 4. Install Module Locks between each module as shown by fully inserting the legs of the Module Locks into the slots in the case until the button on the Module Lock aligns with the hole provided in the case. Press fit the button into the hole. Repeat this installation between each module in your system to provide the most secure installation. 5. When you have finished adding modules, the rear cover should be installed in the same manner as the modules. Removing a Module WARNING - Disconnect all power to the unit before installing or removing modules. AVERTISSEMENT - D�branchez l'alimentation �lectrique de l'appareil avant d'installer ou de retirer des modules. To remove a module from the assembly, first remove the module locks using a small screwdriver as shown. Then disengage the latch by deflecting the latch inward or by using a small screw driver, inserting it into the slot in the side of the case, and prying the latch inward to disengage the lat. Once the latches are disengaged, pull on the module and remove it from the assembly. Drawing No. LP1146 WIRING Wiring Connections All power, input and output (I/O) wiring must be in accordance with Class I, Division 2 wiring methods and in accordance with the authority having jurisdiction. When connecting relay contacts, you must use a Class 2 circuit according to National Electrical Code (NEC), NFPA-70 or Canadian Electrical Code (CEC), Part I, C22.1 or a Limited Power Supply (LPS) according to IEC/EN 60950-1 or Limited-energy circuit according to IEC/EN 61010-1. Electrical connections are made via cage-clamp terminal blocks located on the back of the meter. Strip and connect the wire according to the terminal block specifications on Page 2. Please take care to observe the following points: � The power supply must be mounted close to the unit, with usually not more than 6 feet (1.8 m) of cable between the supply and the PM-50. Ideally, the shortest length possible should be used. � The wire used to connect the PM-50's power supply should be at least 22-gage wire suitably rated for the temperatures of the environment to which it is being installed. If a longer cable run is used, a heavier gage wire should be used. The routing of the cable should be kept away from large contactors, inverters, and other devices which may generate significant electrical noise. � A power supply with an NEC Class 2 or Limited Power Source (LPS) and SELV rating is to be used. This type of power supply provides isolation to accessible circuits from hazardous voltage levels generated by a mains power supply due to single faults. SELV is an acronym for "safety extra-low voltage." Safety extralow voltage circuits shall exhibit voltages safe to touch both under normal operating conditions and after a single fault, such as a breakdown of a layer of basic insulation or after the failure of a single component has occurred. A suitable disconnect device shall be provided by the end user. CAUTION - The user should avoid a wiring configuration that connects the isolated common of the AO module to the input common of the PM-50, which defeats the isolation barrier. 1+ 2- 0-10 V ANALOG OUTPUT STS Status LED 3+ 4- 0-20 mA ANALOG OUTPUT LEDs LED/STATE Fast blink Solid MEANING Module is initializing. Module is running normally. Latch 3 Drawing No. LP1146 RED LION CONTROLS TECHNICAL SUPPORT If for any reason you have trouble operating, connecting, or simply have questions concerning your new product, contact Red Lion's technical support. Support: support.redlion.net Website: www.redlion.net Inside US: +1 (877) 432-9908 Outside US: +1 (717) 767-6511 Corporate Headquarters Red Lion Controls, Inc. 1750 5th Avenue York, PA 17403 Revised 08 2024 COPYRIGHT � 2024 Red Lion Controls, Inc. All Rights Reserved. The terms Red Lion and the Red Lion logo are registered trademarks of Red Lion Controls. All other marks are the property of their respective owners. LIMITED WARRANTY (a) Red Lion Controls Inc. (the "Company") warrants that all Products shall be free from defects in material and workmanship under normal use for the period of time provided in "Statement of Warranty Periods" (available at www.redlion.net) current at the time of shipment of the Products (the "Warranty Period"). EXCEPT FOR THE ABOVE-STATED WARRANTY, COMPANY MAKES NO WARRANTY WHATSOEVER WITH RESPECT TO THE PRODUCTS, INCLUDING ANY (A) WARRANTY OF MERCHANTABILITY; (B) WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE; OR (C) WARRANTY AGAINST INFRINGEMENT OF INTELLECTUAL PROPERTY RIGHTS OF A THIRD PARTY; WHETHER EXPRESS OR IMPLIED BY LAW, COURSE OF DEALING, COURSE OF PERFORMANCE, USAGE OF TRADE OR OTHERWISE. Customer shall be responsible for determining that a Product is suitable for Customer's use and that such use complies with any applicable local, state or federal law. (b) The Company shall not be liable for a breach of the warranty set forth in paragraph (a) if (i) the defect is a result of Customer's failure to store, install, commission or maintain the Product according to specifications; (ii) Customer alters or repairs such Product without the prior written consent of Company. (c) Subject to paragraph (b), with respect to any such Product during the Warranty Period, Company shall, in its sole discretion, either (i) repair or replace the Product; or (ii) credit or refund the price of Product provided that, if Company so requests, Customer shall, at Company's expense, return such Product to Company. (d) THE REMEDIES SET FORTH IN PARAGRAPH (c) SHALL BE THE CUSTOMER'S SOLE AND EXCLUSIVE REMEDY AND COMPANY'S ENTIRE LIABILITY FOR ANY BREACH OF THE LIMITED WARRANTY SET FORTH IN PARAGRAPH (a). BY INSTALLING THIS PRODUCT, YOU AGREE TO THE TERMS OF THIS WARRANTY, AS WELL AS ALL OTHER DISCLAIMERS AND WARRANTIES IN THIS DOCUMENT. 4