Instructions for THORN models including: Basicdim Ild Programmer, Basicdim Ild, Programmer

resources.z.lighting

PDF preview unavailable. Download the PDF instead.

96404588
basicDIM ILD ThebasicDIM ILDprovidesthebasisforaneasy-to-useandcost-effectivelightingsystem withmotion detection.
Whenthesensordetectsmovementittriggersaindividualadjustablemotiondetectionprofileinthecontrol unit.Astheamountofnaturalambientlightchangestheilluminancefrom theartificiallightingsystem is adjusted.
Theconnectedluminariescanbeswitchedonandoffviaremotecontrol.
Switch-on delay Thisisthetimeafterwhichthelightingisswitchedoffaftertheswitchdelay.Itcanbesetviathe"timedelay" parameter
Secondlightvalue OnthebasicDIM ILDyoucansetwhetherthelightistobeswitchedoffaftertheswitchdelayordimmedto thesecondlightvalue.Thelightvalueandthedwelltime(howlongthevaluecanbeheld)canbesetviathe "whenvacant"and"sec.level"parameters.
Bright-out Ifthenominalluminance(eg500lux)isexceededfor10minutesbymorethan150% (e.g.750lux)thelighting isswitchedoffevenifthemotionisdetected.Thelightingisswitchedonagainwhenthemeasuredlightvalue fallsbelowthesetpoint.Thebright-outfunctionisdisplayedbyagreenstatusindicationLEDatthesensor.
Bright-offdelay Ifthesystem isswitchedoffmanuallyviatheremotecontrolthemotionsensorisdeactivatedattheendofa 10minutesdelayifmotionhasnotbeendetectedthemotionsensorisactivatedagain.Ifthesensordetects motionduringthe"ManualOff"delay,thetimewillberesettothestart.