User Manual for TOSHIBA models including: TCB-SFMCA1V-E Multi Function Sensor, TCB-SFMCA1V-E, Multi Function Sensor, Function Sensor, Sensor
NEW Air-to-Air Heat Exchangers - Toshiba Air Conditioning UK
Air-to-Air Heat Exchangers - Toshiba Air Conditioning UK
File Info : application/pdf, 2 Pages, 136.64KB
DocumentDocumentEnglish SETTING MANUAL Multi function sensor (CO2 / PM) Model name: TCB-SFMCA1V-E Thank you for purchasing the "Multi function sensor" for TOSHIBA Air Conditioner. Before starting the installation work, please read this manual carefully and install the product properly. * This product is used in combination with a heat recovery ventilation unit. Do not use the multi function sensor on its own or in combination with other companies' products. CO2 / PM2.5 sensor DN code setting list Refer to How to set each setting for the details of each item. Refer to the installation manual of the heat recovery ventilation unit for other DN codes. DN code Description SET DATA and description 560 CO2 concentration control 0000: Uncontrolled 0001: Controlled 561 CO2 concentration remote controller display 0000: Hide 0001: Display 562 CO2 concentration remote controller display correction 0000: No correction -0010 - 0010: Remote controller display value (no correction) + setting data × 50 ppm 0000: No correction (altitude 0 m) 563 CO2 sensor altitude correction 0000 - 0040: Setting data ×100 m altitude correction 564 CO2 sensor calibration function 0000: Autocalibration enabled, Force calibration disabled 0001: Autocalibration disabled, Force calibration disabled 0002: Autocalibration disabled, Force calibration enabled 565 CO2 sensor force calibration 566 PM2.5 concentration control PM2.5 concentration remote 567 controller display 568 PM2.5 concentration remote controller display correction Multi function sensor 5F6 (CO2 / PM) connection 790 CO2 target concentration 793 PM2.5 target concentration 0000: No calibrate 0001 - 0100: Calibrate with setting data × 20 ppm concentration 0000: Uncontrolled 0001: Controlled 0000: Hide 0001: Display 0000: No correction -0020 - 0020: Remote controller display value (no correction) + setting data × 10 g/m3 0000: Without connection 0001: With connection 0000: 1000 ppm 0001: 1400 ppm 0002: 800 ppm 0000: 70 g/m3 0001: 100 g/m3 0002: 40 g/m3 796 Ventilation fan speed [AUTO] fixed operation 0000: Invalid (according to fan speed in remote controller settings) 0001: Valid (fixed at Fan speed [AUTO]) 79A Fixed ventilation fan speed setting Concentration-controlled 79B minimum ventilation fan speed 0000: High 0001: Medium 0002: Low 0000: Low 0001: Medium 1 Factory default 0001: Controlled 0001: Display 0000: No correction 0000: No correction (altitude 0 m) 0000: Autocalibration enabled, Force calibration disabled 0000: No calibrate 0001: Controlled 0001: Display 0000: No correction 0000: Without connection 0000: 1000 ppm 0000: 70 g/m3 0000: Invalid (according to fan speed in remote controller settings) 0000: High 0000: Low How to set each setting Configure the settings when the heat recovery ventilation unit is stopped (Be sure to stop the heat recovery ventilation unit). Refer to the installation manual of the heat recovery ventilation unit ("7 Installation method for each system configuration") or the installation manual of the remote controller ("9. DN setting" in the "7 Field setting menu") for details on how to set the DN code. 1 Sensor connection settings (be sure to implement) To perform automatic fan speed control using the CO2 / PM2.5 sensor, change the following setting (0001: With connection). DN code SET DATA 0000 0001 Multi function sensor (CO2 / PM) Without connection 5F6 With connection connection (factory default) 2 CO2 / PM2.5 target concentration setting Target concentration is the concentration at which the fan speed is the highest. The fan speed is changed automatically in 7 stages according to the CO2 concentration and PM2.5 concentration. The CO2 target concentration and PM2.5 target concentration can be changed in the settings below. DN code SET DATA 0000 0001 790 CO2 target concentration 1000 ppm (factory default) 1400 ppm 0002 800 ppm 793 PM2.5 target concentration 70 g/m3 (factory default) 100 g/m3 40 g/m3 * Although the fan speed is switched automatically using the set CO2 concentration or PM2.5 concentration as a target, the detection concentration differs depending on the operating environment and product installation conditions etc., so the concentration may go above the target concentration depending on the operating environment. * As a general guideline, the CO2 concentration should be 1000 ppm or less. (REHVA (Federation of European Heating Ventilation and Air Conditioning Associations)) * As a general guideline, the PM2.5 concentration (daily average) should be 70 g/m3 or less. (Ministry of Environment of China) * The concentration at which the fan speed is the lowest will not change even if the settings above are configured, with the CO2 concentration being 400 ppm, and the PM2.5 concentration being 5 g/m3. 3 Remote controller display settings The display of the CO2 concentration and PM2.5 concentration on the remote controller can be hidden with the following settings. DN code SET DATA 0000 0001 561 CO2 concentration remote controller display Hide Display (factory default) 567 PM2.5 concentration remote controller display Hide Display (factory default) * Even if the concentration is hidden in the remote controller display, when DN code "560" and "566" control is enabled, automatic fan speed control is performed. Refer to section 5 for DN code "560" and "566". * If the concentration is hidden, in the event of a sensor failure, the CO2 concentration "- - ppm", PM2.5 concentration "- - g/m3" will also not be displayed. * The display range of the concentration is as follows: CO2: 300 - 5000 ppm, PM2.5: 0 - 999 g/m3. * Refer to section 6 for details on the remote controller display in a group connection system. 4 Remote controller concentration display correction Detection of the CO2 concentration and PM2.5 concentration is performed at the RA air path of the heat recovery ventilation unit main body. As unevenness will also occur in the indoor concentration, a difference between the concentration displayed in the remote controller and the environmental measurement etc. may result. In such a situation, the concentration value displayed by the remote controller can be corrected. DN code SET DATA -0010 - 0010 562 CO2 concentration remote controller display Remote controller display value (no correction) + setting data × 50 ppm correction (factory default: 0000 (no correction)) DN code 568 SET DATA -0020 - 0020 PM2.5 concentration remote controller display Remote controller display value (no correction) + setting data × 10 g/m3 correction (factory default: 0000 (no correction)) * The CO2 concentration will appear as "- - ppm" if the corrected value is too low. * If the corrected PM2.5 concentration is negative, it will appear as "0 g/m3". * Correct only the concentration display value displayed by the remote controller. * Refer to section 6 for details on the remote controller display in a group connection system. 2 5 Concentration control setting Automatic fan speed control according to the CO2 concentration or PM2.5 concentration can be selected individually. When both controls are enabled, the unit will run at a fan speed close to the target concentration (higher of the concentrations). DN code SET DATA 0000 0001 560 CO2 concentration control Uncontrolled Controlled (factory default) 566 PM2.5 concentration control Uncontrolled Controlled (factory default) * Both CO2 concentration control and PM2.5 concentration control are enabled in the factory default settings, so be extra careful when either control is disabled as the following faults may occur. 1) If CO2 concentration control is disabled and the PM2.5 concentration is maintained at a low level, the fan speed will drop, so the indoor CO2 concentration may rise. 2) If PM2.5 concentration control is disabled and the CO2 concentration is maintained at a low level, the fan speed will drop, so the indoor PM2.5 concentration may rise. * Refer to section 6 for details on the concentration control in a group connection system. 6 Remote controller display and concentration control according to system configuration Heat recovery ventilation unit only system (when multiple heat recovery ventilation units are connected in a group) The CO2 / PM2.5 concentration displayed on the remote controller (RBC-A*SU5*) is the concentration detected by the sensor connected to the header unit. Automatic fan speed control by sensor is only applicable to heat recovery ventilation units connected to a sensor. Heat recovery ventilation units not connected to sensors will run at a fixed ventilation fan speed setting when Fan speed [AUTO] is selected. (Refer to section 8) When system is linked with air conditioners The CO2 / PM2.5 concentration displayed on the remote controller (RBC-A*SU5*) is the concentration detected by the sensor connected to the heat recovery ventilation unit with the smallest indoor address. Automatic fan speed control by sensor is only applicable to heat recovery ventilation units connected to a sensor. Heat recovery ventilation units not connected to sensors will run at a fixed ventilation fan speed setting when Fan speed [AUTO] is selected. (Refer to section 8) 7 Minimum ventilation fan speed setting When running under automatic fan speed control, the minimum ventilation fan speed is set as [Low] but this can be changed to [Medium]. (In this case, the fan speed is controlled at 5 levels) DN code SET DATA 0000 0001 79B Concentration-controlled minimum ventilation fan speed Low (factory default) Medium 8 Fixed fan speed setting with no sensor equipped when there is a sensor failure In the system configuration in section 6 above, heat recovery ventilation units with no sensor equipped will run at a fixed ventilation fan speed setting when Fan speed [AUTO] is selected with the remote controller. In addition, for heat recovery ventilation units equipped with a sensor, the unit will also run at a fixed ventilation fan speed setting when the sensor performing concentration control fails (*1). This fixed ventilation fan speed setting can be set. DN code SET DATA 0000 0001 0002 79A Fixed ventilation fan speed setting High (factory default) Medium Low When this DN code is set to [High], the unit will run in the [High] mode even if the DN code "5D" is set to [Extra High]. If the fan speed needs to be set to [Extra High], see the installation manual of the heat recovery ventilation unit (5. Power setting for applied control) and set the DN code "750" and "754' to 100%. *1 If both CO2 and PM2.5 concentration control are enabled and either sensor fails, the unit will run at automatic fan speed control with the functioning sensor. 9 CO2 sensor calibration function settings The CO2 sensor uses the lowest CO2 concentration in the past 1 week as a reference value (equivalent to the general atmospheric CO2 concentration) to perform automatic calibration. When the unit is used in a location where the atmospheric CO2 concentration is always higher than the general reference value (along main roads etc.), or in an environment where the indoor CO2 concentration is always higher, the detected concentration may deviate greatly from the actual concentration due to the autocalibration effect, so either disable the automatic calibration function, or perform force calibration where necessary. DN code 564 SET DATA CO2 sensor automatic calibration function 0000 Autocalibration enabled Force calibration disabled (factory default) 0001 0002 Autocalibration disabled Force calibration disabled Autocalibration disabled Force calibration enabled DN code SET DATA 0000 0001 - 0100 No calibrate Calibrate with setting data × 20 ppm 565 CO2 sensor force calibration (factory default) concentration For force calibration, after setting the DN code "564" to 0002, set DN code "565" to a numeric value. To perform force calibration, a measuring instrument that can measure the CO2 concentration is required separately. Run the heat recovery ventilation unit at a time period during which the CO2 concentration is stable, and quickly set the CO2 concentration value measured at the air inlet (RA) with the remote controller using the prescribed method. Force calibration is performed once only after configuration ends. Not implemented periodically. 10 CO2 sensor altitude correction Correction of the CO2 concentration will be performed according to the altitude at which the heat recovery ventilation unit is installed. DN code SET DATA 0000 0000 - 0040 No correction (altitude 0 m) 563 CO2 sensor altitude correction (factory default) Setting data × 100 m altitude correction 11 Ventilation fan speed [AUTO] fixed operation setting For a system that is connected to an air conditioner, Fan speed [AUTO] cannot be selected from the remote controller. By changing the DN code "796" setting, it is possible to run the heat recovery ventilation unit at Fan speed [AUTO] regardless of the fan speed set by the remote controller. In this case, take note that the fan speed will be fixed as [AUTO]. DN code SET DATA 0000 0001 Invalid 796 Ventilation fan speed [AUTO] fixed operation (according to fan speed in remote controller settings) Valid (fixed at Fan speed [AUTO]) (factory default) List of check codes for CO2 · PM2.5 sensor Refer to the installation manual of the heat recovery ventilation unit for other check codes. Check code Typical cause of trouble Judging device Check points and description E30 Indoor unit - sensor board communication trouble Indoor When communication between the Indoor unit and sensor boards is not possible (operation continues) J04 CO2 sensor trouble Indoor When a CO2 sensor trouble is detected (operation continues) J05 PM sensor trouble Indoor When a PM2.5 sensor trouble is detected (operation continues) * "Indoor" in "Judging device" refers to the heat recovery ventilation unit or the air conditioner. EB28069101 3 4Acrobat Distiller 23.0 (Windows)