VTR8300 Series Installation Guide
Room Controller with Optional PIR sensor
Commercial and Hotel/Lodging HVAC Fan Coil Applications

CONTENTS

Installation

2

Location

2

Installation

2

Terminal, Identification and Function

3

Communication wiring to VC3xxxE Relay Pack

3

BACnet� Communication Wiring (if applicable)

3

Network wiring topology

3

How to Enter Setup Screen

4

Setup Screen Display

4

Specifications

5

Drawing and Dimensions

6

2
DISCLAIMERS

Installation Guide VTR8300 Series

� The VTR8300 series Room Controller is only to be used in conjunction with the VC3000 line voltage switching relay pack. Together they are used as operating controls for high voltage fan coil units.
� If replacing an existing Line Voltage FCU Controller, label the wires before removal of the Room Controller. � Electronic controls are static sensitive devices. Discharge yourself correctly before manipulating and installing the Room Controller. A
short circuit or wrong wiring may permanently damage the Room Controller or equipment. � All VTR8300 series Room Controllers are designed for use as operating controls only and are not safety devices. These instruments
have undergone rigorous tests and verification prior to shipping to ensure proper and reliable operation in the field. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user/installer/electrical system designer to incorporate safety devices such as relays, flow switches, thermal protections, and/or an alarm system to protect the entire system against any catastrophic failures. Tampering with the devices or unintended application of the devices results in a void of warranty. � If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. � These devices are not serviceable and must be returned to the supplier for any repair. � A switch or circuit breaker must be installed. It must be suitably located, easily reached, and marked as the disconnecting device � Never apply more than 9VDC to Room Controller. � This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
IMPORTANT SYMBOLS

Products marked with this symbol state that the manuals must be consulted in all cases to any hazards. This product has been tested to the requirements of CAN/CAS-C22.2 No. 61010-1, second edition, including Amendment 1, or a later version of the same standard incorporating the same level of testing requirements. Alternating Current Direct Current Equipment protected throughout by DOUBLE INSULATION or REINFORCED INSULATION

� 2015 Viconics Technologies Inc. All rights reserved.

VTR8300 Room Controller

VC3000 Relay Pack

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0414-02

www.viconics.com | sales@viconics.com

April 2015

Installation Guide VTR8300 Series

3

INSTALLATION
Location
� Do not install on outside wall. � Do not install in areas with direct heat source. � Do no install near any air discharge grill. � Do not install in areas exposed to direct sunlight. � Ensure Room Controller has sufficient air circulation. � Ensure wall surface is flat and clean.

Installation
1. Open unit by pulling on bottom side of Room Controller (Figure 1). 2. Read FCC ID and IC label installed in cover before installing any wireless product. 3. Ensure correct side of base faces up. 4. Pull cables 6in (15cm) out from wall. 5. Align base and mark location of two mounting holes on wall (Figure 2). 6. Install anchors in wall. 7. Insert cable in central hole of base. 8. Insert screws in mounting holes on each side of base. 9. Strip each wire 1/4in ( 0.6cm) from end. 10. Insert each wire according to wiring chart (next page). 11. Gently push excess wiring back into hole. 12. Gently align cover to top of base and snap in place from bottom (Figure 3). 13. Install security screw.

Figure-1 Open the cover

� 2015 Viconics Technologies Inc. All rights reserved.

� IfreplacinganexistingLineVoltageFCUController,labelthe wires before removal of the controller.
� Electroniccontrolsarestaticsensitivedevices.Discharge yourself properly before manipulating and installing the Room Controller.
� Ashortcircuitorwrongwiringmaypermanentlydamagethe Room Controller or the equipment.
� AllVTR8300seriesRoomControllersaredesignedforuseas operating controls only and are not safety devices. Tampering with the devices or unintended application of the devices will result in a void of warranty. This transmitter must be installed to provide a separation distance of at least 4in (10cm) from all persons and must not be collocated or operating in conjunction with any other antenna or transmitter.

Figure-2 Install the base

Figure-3 Reinstall cover

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0414-02

www.viconics.com | sales@viconics.com

April 2015

4

TERMINAL, IDENTIFICATION AND FUNCTION

Terminal Identification

All VTR83xxA Terminal Equipment Controller

Terminal 4

Tx � Rx Communication

Terminal 5

Power Hot 7.0 VDC

Terminal 6

Power Common

Terminal 13

BACnet +

Terminal 14

BACnet -

Terminal 15

BACnet REF

Terminal 16

BI 1 ( Configurable )

Terminal 17

BI 2 ( Configurable )

Terminal 18

Scom

NOTE: never use any terminal not mentioned in above table.

COMMUNICATION WIRING TO VC3XXXE RELAY PACK

VTR83xxA
Terminal Controller 4 - Tx / Rx
5 - 7 Vdc Power Hot
6 - Power Common

VC3504E
Relay Pack 1 - Tx / Rx
2 - 7 Vdc Power Hot
3 - Power Common

VC3300E
Relay Pack 1 - Tx / Rx
2 - 7 Vdc Power Hot
3 - Power Common

BACnet� Communication Shielded Wiring (if required)

To other VC3xxxE
Relay Pack

Installation Guide VTR8300 Series
Only ONE VC3xxxE Relay Pack with remote monitoring inputs can be used under a single VTR83xxA Controller. All other slave units must be VC3xxxE Relay Pack(s) WITHOUT remote inputs. A maximum of 10 VC3xxxE Relay Packs can be used for a single VTR83xxA Room Controller.
From VTR83xxA to first VC3xxxE Relay Pack � Usesexistingornewfieldwires � Aminimumof3wiresarerequired14-22Ga,
Solid or Stranded, shield not necessary
From first VC3xxxE to all other slave VC3xxxE Relay Pack(s) �Usesexistingornewfieldwires �Aminimumof2wiresarerequired14-22Ga,Solid
or Stranded �Shieldnotnecessary �Connectonlytwowires:Tx/Rx(1)andPower
Common (3).

VTR83xxA
Terminal Controller 13 - COM + 14 - COM -

VTR83xxA
Terminal Controller 13 - COM + 14 - COM -

NOTE: See VTR8300 BACnet� integration manual for more details
Network Wiring Topology

To others To others

Star Topology

Daisy Chained Topology

Mixed Daisy Chained & Star Topology

� 2015 Viconics Technologies Inc. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0414-02

www.viconics.com | sales@viconics.com

April 2015

Installation Guide VTR8300 Series

5

HOME SCREEN DISPLAY

Hospitality User Interface Shown

Date Occupancy Status
Indoor Temperature
Indoor Humidity Outdoor Temperature
System Mode Short Network
Message

Time System Status
Fan Status
Up Arrow Increase Temperature Setpoint
Actual Setpoint
Down Arrow Decrease Temperature Setpoint Help

Fan Mode

Language Selection

Temperature Units

Note: User HMI is configurable and allows display functions such as Date, Time, Humidity, Outdoor Temperature, Setpoint, and others to be enabled or disabled by setting various parameters.

� 2015 Viconics Technologies Inc. All rights reserved.

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0414-02

www.viconics.com | sales@viconics.com

April 2015

6
HOW TO ENTER SETUP SCREEN

Installation Guide VTR8300 Series

Touch and hold this point for 3 seconds to enter setup mode
Note: If a configuration / installer password is activated to prevent unauthorised access to the configuration menu parameters, a password entry prompt will appear to prevent access to the device configuration components.

SETUP SCREEN DISPLAY
1/2 Setup Network Configuration Setpoints - Display Setpoints view Test outputs Language Selection

Enter BACnet� & ZigBee� network settings Enter parameter configuration menu Enter setpoint & display settings Enter status and service view Enter output testing mode Enter language selection settings

Return to home screen

Discover Mode The Controller will become discoverable on the wireless ZigBee� network for 1 minute (this button is hidden if ZigBee� settings are not configured)

General Note:
Adjustable parameter Non-adjustable parameter

Viconics Technologies Inc. | 9245 Langelier Blvd. | St.-Leonard | Quebec | Canada | H1P 3K9 | Tel: (514) 321-5660 | Fax: (514) 321-4150

028-0414-02

www.viconics.com | sales@viconics.com

April 2015

� 2015 Viconics Technologies Inc. All rights reserved.

