Generac® QuietSource® Series Standby Generators
Model: QT027 (Gray) - 27 kW 60Hz
Standby Power Rating: 27 kW
Type: Liquid-Cooled Engine Generator Sets
Meets EPA Emission Regulations and CA/MA emissions Compliant.
Two Line LCD Tri-lingual Digital Nexus™ Controller
Isochronous Electronic Governor
Sound Attenuated Enclosure
Closed Coolant Recovery System
Smart Battery Charger
UV/Ozone Resistant Hoses
±1% Voltage Regulation
Natural Gas or LP Operation
2 Year Limited Warranty
UL 2200 Listed
Image Description: A Generac QuietSource Series QT027 standby generator, model QT027 (Gray), with a 27 kW standby power rating. It features a liquid-cooled engine, a sound-attenuated enclosure, and is shown with UL Listed and USA Engineered & Built certifications. It meets EPA and CA/MA emissions regulations.
Features
Innovative Design & Prototype Testing
Key components of GENERAC'S success in "IMPROVING POWER BY DESIGN." Total commitment to component testing, reliability testing, environmental testing, destruction and life testing, plus testing to applicable CSA, NEMA, EGSA, and other standards, ensures Generac Power Systems provide superior performance.
Test Criteria:
✔️ PROTOTYPE TESTED
✔️ SYSTEM TORSIONAL TESTED
✔️ NEMA MG1-22 EVALUATION
✔️ MOTOR STARTING ABILITY
Solid-State, Frequency Compensated Voltage Regulation
This state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge loads to the engine. Features an unequalled ±1% voltage regulation.
Single Source Service Response
Generac's extensive dealer network provides parts and service know-how for the entire unit, from the engine to the smallest electronic component.
Generac Transfer Switches
Long life and reliability are synonymous with GENERAC POWER SYSTEMS. The GENERAC product line includes its own transfer systems and controls for total system compatibility.
Application & Engineering Data
Generator Specifications
TYPE
Synchronous
ROTOR INSULATION
Class H
STATOR INSULATION
Class H
TELEPHONE INTERFERENCE FACTOR (TIF)
<50
ALTERNATOR OUTPUT LEADS 3 PHASE
4 wire
BEARINGS
Sealed Ball
COUPLING
Flexible Disc
LOAD CAPACITY (STANDBY RATING)
27 kW
EXCITATION SYSTEM
Direct
Voltage Regulation
TYPE
Electronic
SENSING
Single Phase
REGULATION
± 1%
Generator Features
Revolving field heavy duty generator
Directly connected to the engine
Operating temperature rise 120 °C above a 40 °C ambient
Insulation is Class H rated at 150 °C rise
All models are fully prototyped tested
Enclosure Features
TYPE
Aluminum weather protective enclosure
Ensures protection against mother nature. Electrostatically applied textured epoxy paint for added durability.
Enclosed critical grade muffler
Quiet, critical grade muffler is mounted inside the unit to prevent injuries.
Rating definitions: Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). (All ratings in accordance with BS5514, ISO3046, ISO8528, SAE J1349 and DIN6271).
Operating Data
KW RATING (LP/NG): 27/25
ENGINE SIZE: 2.4 Liter Inline 4
Generator Output Voltage/KW - 60Hz
kW LPG
AMP
kW Nat. Gas
AMP
CB Size (Both)
120/240V, 1-phase, 1.0 pf
27
112
25
104
125
120/208V, 3-phase, 0.8 pf
27
94
25
87
100
120/240V, 3-phase, 0.8 pf
27
81
25
75
90
Engine Fuel Consumption (Natural Gas) (Propane)
Natural Gas (ft³/hr.)
Propane (gal/hr.)
Propane (cu ft/hr)
Exercise cycle
42
0.44
16
25% of rated load
108
1.2
44
50% of rated load
197
2.1
78
75% of rated load
287
3.1
114
100% of rated load*
359
3.9
143
For Btu content, multiply ft³/hr x 2520 (LP) or ft³/hr x 1000 (NG)
Engine Cooling
Air flow (inlet air including alternator and combustion air)
2,400 ft³/min.
System coolant capacity
3 US gal.
Heat rejection to coolant
105,000 BTU/hr.
Max. operating air temp. on radiator
60 °C (150 °F)
Max. ambient temperature
50 °C (140 °F)
Combustion Air Requirements
Flow at rated power 60 Hz
68 cfm
Sound Emissions in dBA
Exercising at 7 meters
61
Normal operation at 7 meters
70
Exhaust
Exhaust flow at rated output 60 Hz
180 cfm
Exhaust temp. at muffler outlet
900 °F
Engine Parameters
Rated synchronous RPM
1800 (60 Hz)
Power Adjustment for Ambient Conditions
25
77
Temperature Deration
3% for every 10 °C above - °C
1.65% for every 10 °F above - °F
Altitude Deration
1% for every 100 m above - m
183
3% for every 1000 ft. above - ft.
600
Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and SCAQMD permitting purposes.
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice. KW rating is based on LPG Fuel and may derate with natural gas.
Interconnections
QT Series Engine Generator Connection Panel
Diagram Description: An electrical interconnection diagram showing the flow from the Utility Supply (via Service Disconnect) to the RTS Transfer Switch, then to the QT Series Engine Generator Connection Panel, and finally to the Customer Load (Distribution Panel). It illustrates connections for neutral wires, ground, and power leads, and highlights the Nexus™ control features.
Nexus™ Control Features
Feature
Description
2-Line Plain Text LCD Display
Simple user interface for ease of operation
Mode Switch
-Auto -Off -Manual/Test (start)
Programmable start delay between 10-30 seconds
Automatic Start on Utility failure. 7 day exerciser
Engine Start Sequence
Stops unit. Power is removed. Control and charger still operate.
Engine Warm-up
Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Engine Cool-Down
Standard
Starter Lock-out
Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration)
Smart Battery Charger
5 seconds
Automatic Voltage Regulation with Over and Under Voltage Protection
1 minute
Automatic Low Oil Pressure Shutdown
Starter cannot re-engage until 5 sec. after engine has stopped.
Overspeed Shutdown
Standard
High Temperature Shutdown
Standard
Overcrank Protection
Standard
Safety Fused
Standard
Failure to Transfer Protection
Standard
Low Battery Protection
Standard
50 Event Run Log
Standard
Future Set Capable Exerciser
Standard
Incorrect Wiring Protection
Standard
Internal Fault Protection
Standard
Common External Fault Capability
Standard
Governor Failure Protection
Standard
*Single and three phase connections may vary, refer to the owner's manual for specific connection information.
Installation Layout
Diagram Description: A top, front, rear, and side view of the Generac QT027 generator, detailing its physical dimensions, mounting hole locations, recommended concrete pad size (1041" W x 1892" L), access points for maintenance items (oil fill, dipstick, filter, radiator drain, air cleaner, spark plugs, mufflers, fan belt, battery), lifting provisions, and connection points for fuel lines and electrical leads. It also includes a service item accessibility chart.
Notes:
1) MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1041 (41.0") WIDE X 1892 (74 1/2") LONG. REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES.
2) ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE AND SERVICING, THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL, STATE AND LOCAL CODES FOR MINIMUM DISTANCES FROM OTHER STRUCTURES.
3) CIRCUIT BREAKER INFORMATION: SEE SPECIFICATION SHEET WITHIN OWNERS MANUAL.
4) INSIDE STUB-UP AREA FOR AC LOAD LEAD CONDUIT CONNECTION, NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX. CONNECTION, ACCESS TO TRANSFER SWITCH CONTROL WIRES, AND TRANSFER SWITCH CONNECTION (IF SO EQUIPPED). REMOVE FRONT COVER FOR ACCESS.
4A) ONE 1-1/2" NEMA ELECTRICAL KNOCKOUT AND TWO 1/2" NEMA ELECTRICAL KNOCKOUTS PROVIDED FOR OUTSIDE AC LOAD CONDUIT CONNECTION, NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX. CONNECTION, ACCESS TO TRANSFER SWITCH CONTROL WIRES, AND TRANSFER SWITCH CONNECTION (IF SO EQUIPPED). REMOVE FRONT COVER FOR ACCESS.
5) REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
6) REMOVE LIFT-OFF ENCLOSURE TO ACCESS EXHAUST MUFFLER.
Service Item Accessibility Chart:
SERVICE ITEM
ACCESS
OIL FILL CAP
THRU RIGHT DOOR
OIL DIP STICK
THRU RIGHT DOOR
OIL FILTER
THRU RIGHT DOOR
OIL DRAIN HOSE
THRU LEFT DOOR
RADIATOR DRAIN HOSE
THRU LEFT DOOR
AIR CLEANER ELEMENT
THRU LEFT DOOR
SPARK PLUGS
THRU LEFT DOOR
MUFFLERS
SEE NOTE 6
FAN BELT
THRU RIGHT DOOR
BATTERY
THRU LEFT DOOR
Weight Data:
MATERIAL (GENSET ONLY)
ENGINE/KW
ENCLOSURE
WEIGHT KG [LBS]
(SHIPPING CARTON/SKID) WEIGHT KG [LBS]
(GENSET, SKID, & CARTON) WEIGHT KG [LBS]
2.4L/27KW ALUMINUM
405 [891]
30 [66]
434 [957]
Available Accessories
Model #
Product
Description
5630
Cold Weather Kit
If the temperature regularly falls below 32° F, install a cold weather kit to maintain optimal battery temperature. Kit consists of battery warmer with thermostat built into the wrap.
5621
Auxiliary Transfer Switch Contact Kit
The auxiliary transfer switch contact kit allows the transfer switch to lock out a single large electrical load you may not need.
5616
Extreme Cold Weather Kit
Recommended where the temperature regularly falls below 32° F for extended periods of time. For liquid cooled units only.
5651
Base Plug Kit
Add base plugs to the base of the generator to keep out debris.
5704
Paint Kit
Medium Grey Kit
5656
Scheduled Maintenance Kit
The Liquid-Cooled Scheduled Maintenance Kits offer all the hardware necessary to perform a complete maintenance on Generac liquidcooled generators.
5928
Nexus Wireless Remote
Completely wireless and battery powered, Generac's Nexus wireless remote monitor provides you with instant status information without ever leaving the house.
5951
Advanced Nexus Wireless Remote
Remotely control generator functions with the advanced model's LCD display. In addition to remote testing of the generator, set the excercise cycle and maintenance interval reminders.
5937
DLM Load Control Module (50 Amps)
DLM Modules are used in conjunction with the Nexus Smart Switch to increase its load management capabilities. It gives the Nexus Smart Switch additional load management flexibility not found in any other transfer switch.