Generac® QuietSource® Series Standby Generators

Model: QT027 (Gray) - 27 kW 60Hz

Standby Power Rating: 27 kW

Type: Liquid-Cooled Engine Generator Sets

Meets EPA Emission Regulations and CA/MA emissions Compliant.

Includes:

  • Generac Naturally Aspirated Gaseous Fueled 2.4L Engine
  • Two Line LCD Tri-lingual Digital Nexus™ Controller
  • Isochronous Electronic Governor
  • Sound Attenuated Enclosure
  • Closed Coolant Recovery System
  • Smart Battery Charger
  • UV/Ozone Resistant Hoses
  • ±1% Voltage Regulation
  • Natural Gas or LP Operation
  • 2 Year Limited Warranty
  • UL 2200 Listed

Image Description: A Generac QuietSource Series QT027 standby generator, model QT027 (Gray), with a 27 kW standby power rating. It features a liquid-cooled engine, a sound-attenuated enclosure, and is shown with UL Listed and USA Engineered & Built certifications. It meets EPA and CA/MA emissions regulations.

Features

Innovative Design & Prototype Testing

Key components of GENERAC'S success in "IMPROVING POWER BY DESIGN." Total commitment to component testing, reliability testing, environmental testing, destruction and life testing, plus testing to applicable CSA, NEMA, EGSA, and other standards, ensures Generac Power Systems provide superior performance.

Test Criteria:

  • ✔️ PROTOTYPE TESTED
  • ✔️ SYSTEM TORSIONAL TESTED
  • ✔️ NEMA MG1-22 EVALUATION
  • ✔️ MOTOR STARTING ABILITY

Solid-State, Frequency Compensated Voltage Regulation

This state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge loads to the engine. Features an unequalled ±1% voltage regulation.

Single Source Service Response

Generac's extensive dealer network provides parts and service know-how for the entire unit, from the engine to the smallest electronic component.

Generac Transfer Switches

Long life and reliability are synonymous with GENERAC POWER SYSTEMS. The GENERAC product line includes its own transfer systems and controls for total system compatibility.

Application & Engineering Data

Generator Specifications

TYPESynchronous
ROTOR INSULATIONClass H
STATOR INSULATIONClass H
TELEPHONE INTERFERENCE FACTOR (TIF)<50
ALTERNATOR OUTPUT LEADS 3 PHASE4 wire
BEARINGSSealed Ball
COUPLINGFlexible Disc
LOAD CAPACITY (STANDBY RATING)27 kW
EXCITATION SYSTEMDirect

Voltage Regulation

TYPEElectronic
SENSINGSingle Phase
REGULATION± 1%

Generator Features

  • Revolving field heavy duty generator
  • Directly connected to the engine
  • Operating temperature rise 120 °C above a 40 °C ambient
  • Insulation is Class H rated at 150 °C rise
  • All models are fully prototyped tested

Enclosure Features

TYPEAluminum weather protective enclosureEnsures protection against mother nature. Electrostatically applied textured epoxy paint for added durability.
Enclosed critical grade mufflerQuiet, critical grade muffler is mounted inside the unit to prevent injuries.
Small, compact, attractiveMakes for an easy, eye appealing installation.
SAESound attenuated enclosure ensures quiet operation.

Engine Specifications

MAKEGenerac
MODELQT027
CYLINDERS4
DISPLACEMENT2.4 Liter
BORE3.41
STROKE3.94
COMPRESSION RATIO9.5:1
INTAKE AIR SYSTEMNaturally Aspirated
LIFTER TYPEHydraulic

Governor Specifications

TYPEElectronic
FREQUENCY REGULATIONIsochronous
STEADY STATE REGULATION± 0.25%

Engine Lubrication System

OIL PUMPGear
OIL FILTERFull flow spin-on cartridge
CRANKCASE CAPACITY4 Quarts

Engine Cooling System

TYPEClosed
WATER PUMPBelt driven
FAN SPEED1980
FAN DIAMETER18.1 inches
FAN MODEPusher

Fuel System

FUEL TYPENatural gas, propane vapor
CARBURETORDown Draft
SECONDARY FUEL REGULATORStandard
FUEL SHUT OFF SOLENOIDStandard
OPERATING FUEL PRESSURE5" - 14" H₂O

Electrical System

BATTERY CHARGE ALTERNATOR12V 30 Amp
STATIC BATTERY CHARGER2 Amp
RECOMMENDED BATTERYGroup 26, 525CCA
SYSTEM VOLTAGE12 Volts

Rating definitions: Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). (All ratings in accordance with BS5514, ISO3046, ISO8528, SAE J1349 and DIN6271).

Operating Data

KW RATING (LP/NG): 27/25

ENGINE SIZE: 2.4 Liter Inline 4

Generator Output Voltage/KW - 60Hz

kW LPGAMPkW Nat. GasAMPCB Size (Both)
120/240V, 1-phase, 1.0 pf2711225104125
120/208V, 3-phase, 0.8 pf27942587100
120/240V, 3-phase, 0.8 pf2781257590

Engine Fuel Consumption (Natural Gas) (Propane)

Natural Gas (ft³/hr.)Propane (gal/hr.)Propane (cu ft/hr)
Exercise cycle420.4416
25% of rated load1081.244
50% of rated load1972.178
75% of rated load2873.1114
100% of rated load*3593.9143

For Btu content, multiply ft³/hr x 2520 (LP) or ft³/hr x 1000 (NG)

Engine Cooling

Air flow (inlet air including alternator and combustion air)2,400 ft³/min.
System coolant capacity3 US gal.
Heat rejection to coolant105,000 BTU/hr.
Max. operating air temp. on radiator60 °C (150 °F)
Max. ambient temperature50 °C (140 °F)

Combustion Air Requirements

Flow at rated power 60 Hz68 cfm

Sound Emissions in dBA

Exercising at 7 meters61
Normal operation at 7 meters70

Exhaust

Exhaust flow at rated output 60 Hz180 cfm
Exhaust temp. at muffler outlet900 °F

Engine Parameters

Rated synchronous RPM1800 (60 Hz)

Power Adjustment for Ambient Conditions

2577
Temperature Deration3% for every 10 °C above - °C
1.65% for every 10 °F above - °F
Altitude Deration1% for every 100 m above - m183
3% for every 1000 ft. above - ft.600

Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and SCAQMD permitting purposes.

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice. KW rating is based on LPG Fuel and may derate with natural gas.

Interconnections

QT Series Engine Generator Connection Panel

Diagram Description: An electrical interconnection diagram showing the flow from the Utility Supply (via Service Disconnect) to the RTS Transfer Switch, then to the QT Series Engine Generator Connection Panel, and finally to the Customer Load (Distribution Panel). It illustrates connections for neutral wires, ground, and power leads, and highlights the Nexus™ control features.

Nexus™ Control Features

FeatureDescription
2-Line Plain Text LCD DisplaySimple user interface for ease of operation
Mode Switch-Auto
-Off
-Manual/Test (start)
Programmable start delay between 10-30 secondsAutomatic Start on Utility failure. 7 day exerciser
Engine Start SequenceStops unit. Power is removed. Control and charger still operate.
Engine Warm-upStart with starter control, unit stays on. If utility fails, transfer to load takes place.
Engine Cool-DownStandard
Starter Lock-outCyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration)
Smart Battery Charger5 seconds
Automatic Voltage Regulation with Over and Under Voltage Protection1 minute
Automatic Low Oil Pressure ShutdownStarter cannot re-engage until 5 sec. after engine has stopped.
Overspeed ShutdownStandard
High Temperature ShutdownStandard
Overcrank ProtectionStandard
Safety FusedStandard
Failure to Transfer ProtectionStandard
Low Battery ProtectionStandard
50 Event Run LogStandard
Future Set Capable ExerciserStandard
Incorrect Wiring ProtectionStandard
Internal Fault ProtectionStandard
Common External Fault CapabilityStandard
Governor Failure ProtectionStandard

*Single and three phase connections may vary, refer to the owner's manual for specific connection information.

Installation Layout

Diagram Description: A top, front, rear, and side view of the Generac QT027 generator, detailing its physical dimensions, mounting hole locations, recommended concrete pad size (1041" W x 1892" L), access points for maintenance items (oil fill, dipstick, filter, radiator drain, air cleaner, spark plugs, mufflers, fan belt, battery), lifting provisions, and connection points for fuel lines and electrical leads. It also includes a service item accessibility chart.

Notes:

  • 1) MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1041 (41.0") WIDE X 1892 (74 1/2") LONG. REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES.
  • 2) ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE AND SERVICING, THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL, STATE AND LOCAL CODES FOR MINIMUM DISTANCES FROM OTHER STRUCTURES.
  • 3) CIRCUIT BREAKER INFORMATION: SEE SPECIFICATION SHEET WITHIN OWNERS MANUAL.
  • 4) INSIDE STUB-UP AREA FOR AC LOAD LEAD CONDUIT CONNECTION, NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX. CONNECTION, ACCESS TO TRANSFER SWITCH CONTROL WIRES, AND TRANSFER SWITCH CONNECTION (IF SO EQUIPPED). REMOVE FRONT COVER FOR ACCESS.
  • 4A) ONE 1-1/2" NEMA ELECTRICAL KNOCKOUT AND TWO 1/2" NEMA ELECTRICAL KNOCKOUTS PROVIDED FOR OUTSIDE AC LOAD CONDUIT CONNECTION, NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX. CONNECTION, ACCESS TO TRANSFER SWITCH CONTROL WIRES, AND TRANSFER SWITCH CONNECTION (IF SO EQUIPPED). REMOVE FRONT COVER FOR ACCESS.
  • 5) REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
  • 6) REMOVE LIFT-OFF ENCLOSURE TO ACCESS EXHAUST MUFFLER.

Service Item Accessibility Chart:

SERVICE ITEMACCESS
OIL FILL CAPTHRU RIGHT DOOR
OIL DIP STICKTHRU RIGHT DOOR
OIL FILTERTHRU RIGHT DOOR
OIL DRAIN HOSETHRU LEFT DOOR
RADIATOR DRAIN HOSETHRU LEFT DOOR
AIR CLEANER ELEMENTTHRU LEFT DOOR
SPARK PLUGSTHRU LEFT DOOR
MUFFLERSSEE NOTE 6
FAN BELTTHRU RIGHT DOOR
BATTERYTHRU LEFT DOOR

Weight Data:

MATERIAL (GENSET ONLY)ENGINE/KWENCLOSUREWEIGHT KG [LBS](SHIPPING CARTON/SKID) WEIGHT KG [LBS](GENSET, SKID, & CARTON) WEIGHT KG [LBS]
2.4L/27KW ALUMINUM405 [891]30 [66]434 [957]

Available Accessories

Model #ProductDescription
5630Cold Weather KitIf the temperature regularly falls below 32° F, install a cold weather kit to maintain optimal battery temperature. Kit consists of battery warmer with thermostat built into the wrap.
5621Auxiliary Transfer Switch Contact KitThe auxiliary transfer switch contact kit allows the transfer switch to lock out a single large electrical load you may not need.
5616Extreme Cold Weather KitRecommended where the temperature regularly falls below 32° F for extended periods of time. For liquid cooled units only.
5651Base Plug KitAdd base plugs to the base of the generator to keep out debris.
5704Paint KitMedium Grey Kit
5656Scheduled Maintenance KitThe Liquid-Cooled Scheduled Maintenance Kits offer all the hardware necessary to perform a complete maintenance on Generac liquidcooled generators.
5928Nexus Wireless RemoteCompletely wireless and battery powered, Generac's Nexus wireless remote monitor provides you with instant status information without ever leaving the house.
5951Advanced Nexus Wireless RemoteRemotely control generator functions with the advanced model's LCD display. In addition to remote testing of the generator, set the excercise cycle and maintenance interval reminders.
5937DLM Load Control Module (50 Amps)DLM Modules are used in conjunction with the Nexus Smart Switch to increase its load management capabilities. It gives the Nexus Smart Switch additional load management flexibility not found in any other transfer switch.

Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com

©2012 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0187720SBY-J / Printed in U.S.A. 06/27/12