DYNAIR REA & REV Centrifugal Roof Fans - Technical Datasheet

REA & REV Centrifugal Roof Fans with External Rotor Motor

Centrifugal roof fans designed for efficient ventilation.

Product Overview

The REA and REV series are centrifugal roof fans featuring an external rotor motor, designed for direct or ducted ventilation in a wide range of civil, commercial, and industrial applications. These fans are characterized by their compact design and ease of installation.

Discharge Types:

  • REA: Horizontal discharge
  • REV: Vertical discharge

Compliance:

Conforms to ErP Directive 125/2009/CE and EU Regulation 1253/2014 [✅]

Operating Temperature:

Suitable for exhausting clean air with temperatures ranging from -10°C to +60°C.

Construction:

  • Base frame: Galvanized steel sheet.
  • Protection guard: Drawn steel rod, protected against atmospheric agents.
  • Impeller: Backward-curved wheel made of PA plastic, offering high aerodynamic efficiency and low noise levels.
  • Upper cover: Aluminum (REA models).
  • Outer deflector: ABS (REV models).

Motor:

External rotor motor, available in three-phase or single-phase. Protection rating is IP44 for models up to Size 254, and IP54 for larger models.

Available Accessories:

  • TS: Backdraught gravity shutter
  • GR: Silencer
  • CB: Counterbase for wall mounting
  • BA: Support base for corrugated roof coverings
  • Speed regulators and inverters
  • PB: Support base/Silenced reduction (not available for size 200)
  • CCr: Flat protection guard

Versions:

REA EC: Versions equipped with high-efficiency electronically controlled motors.

Performance Data

Air performances are measured in accordance with EN ISO 5801 / AMCA 210 standard with standard air density (1.2 kg/m³). Sound power level is obtained according to EN ISO 3746. Installation Type: C. Power supply options: 230V/1Ph/50Hz or 400V/3Ph/50Hz.

Key for Performance Tables:

  • U: Power Supply (Single/Three-phase)
  • P: Motor Poles (RPM: 2p=3000, 4p=1500, 6p=1000, 8p=750)
  • Pm (kW): Motor power rating
  • In (A): Full load current
  • IP/CL: Motor protection grade/Insulation class
  • Mot. (Gr): Motor size
  • Lp/Lw (dBA): Sound pressure and volume levels
  • Ps (Pa): Static pressure
  • Q (m³/h): Airflow volume

REA 200 Performance

CodeTypeModelUPPm (kW)In (A)IP/CLdB(A)Ps (Pa)Q (m³/h)
LwLp
1RE2042REA202 M20.060.2344/B684420050-500
Performance Curve: REA 200

Graph showing Static Pressure (Ps) in Pascals (Pa) versus Airflow Volume (Q) in cubic meters per hour (m³/h) for the REA 200 model.

REA - REV 250 Performance

CodeTypeModelUPPm (kW)In (A)IP/CLdB(A)Ps (Pa)Q (m³/h)
LwLp
1RE2545REA252 M20.200.6844/B77534800-1200
1RE2544REA254 M40.090.3944/B66433200-1200
1RV2550REV252 M20.200.9044/B77534800-1200
1RV2560REV254 M40.090.3944/B66433200-1200
Performance Curves: REA 250 & REV 250

Graphs showing Static Pressure (Ps) in Pascals (Pa) versus Airflow Volume (Q) in cubic meters per hour (m³/h) for REA 252 M, REA 254 M, REV 252 M, and REV 254 M models.

REA - REV 310 Performance

CodeTypeModelUPPm (kW)In (A)IP/CLdB(A)Ps (Pa)Q (m³/h)
LwLp
1RE0301REA314 M40.221.1054/F6137.52600-2700
1RE0300REA314 T40.220.5054/F6137.52600-2700
1RV3151REV314 M40.221.1044/B6137.52600-2700
1RV3156REV314 T40.210.5054/F6137.52600-2700
Performance Curves: REA 310 & REV 310

Graphs showing Static Pressure (Ps) in Pascals (Pa) versus Airflow Volume (Q) in cubic meters per hour (m³/h) for REA 314 M, REA 314 T, REV 314 M, and REV 314 T models.

REA - REV 350 Performance

CodeTypeModelUPPm (kW)In (A)IP/CLdB(A)Ps (Pa)Q (m³/h)
LwLp
1RE0351REA354 M40.582.6054/F6743.54000-5900
1RE0350REA354 T40.330.6854/F6339.53000-5900
1RV3551REV354 M40.582.6054/F6743.54000-5900
1RV3556REV354 T40.330.7054/F6339.53000-5900
Performance Curves: REA 350 & REV 350

Graphs showing Static Pressure (Ps) in Pascals (Pa) versus Airflow Volume (Q) in cubic meters per hour (m³/h) for REA 354 M, REA 354 T, REV 354 M, and REV 354 T models.

REA - REV 400 Performance

CodeTypeModelUPPm (kW)In (A)IP/CLdB(A)Ps (Pa)Q (m³/h)
LwLp
1RE0400REA404 T40.541.2054/F6743.54000-6000
1RV4056REV404 T40.541.2054/F6743.54000-6000
Performance Curves: REA 400 & REV 400

Graphs showing Static Pressure (Ps) in Pascals (Pa) versus Airflow Volume (Q) in cubic meters per hour (m³/h) for REA 404 T and REV 404 T models.

Dimensions

Dimensions are provided in millimeters (mm). Indicative weights are also listed.

REA Dimensions

REA Fan Dimensions Diagram

Technical drawing illustrating the external dimensions of REA fans, labeled ØA, B, C, D, E, F, G, ØH.

TIPO | TYPEØABCDEFGØHKg
REA 20039518023300265-2201256
REA 25049022038400360-25717810
REA 31055531038400360-30722014
REA 35069033538500450-38027025
REA 4008103603865060053047129640

REV Dimensions

REV Fan Dimensions Diagram

Technical drawing illustrating the external dimensions of REV fans, labeled ØA, B, C, D, E, F, G, ØH.

TIPO | TYPEØABCDEFGØHKg
REV 25065029038400360-25717810
REV 31065029038400360-30722015
REV 35080034038500450-38027032
REV 4009804003865060053047129645

Accessories

A range of accessories are available to enhance the functionality and installation of REA and REV fans.

GR Silencers

Silencers with a central pod designed to reduce fan noise. Constructed with mineral wool sound-absorbing material and a galvanized steel frame. Note: Using a silencer with the TS shutter requires the version with a lowered pod.

Noise Attenuation (dB per Octave Band):

Type63 Hz125 Hz250 Hz500 Hz1000 Hz2000 Hz4000 Hz8000 Hz
GR 252461016181511
GR 312461016181511
GR 353591119201814
GR 4034891815106
GR 4534891815106
GR 50451115161295
GR 56451115161295
GR 63345814973
GR 75345814973
GR 80345814973
GR Silencer Dimensions

Diagram showing the dimensions of GR silencers.

Code (I)Code (II)TipoABB (lowered)CDEFGØHKg
1SI03101SI0456GR 25-317506504503903609510050M828
1SI03501SI0457GR 3575065040049045012015050M837
1SI04001SI0454GR 4075065035064060014525050M842
1SI04001SI0454GR 4575065035064060014525050M842

(I) Standard version | (II) Version with lowered pod

TS Gravity Shutters

These shutters prevent unnecessary heat loss and have negligible pressure drop. The shutter flaps open due to the air depression generated by the fan and close by gravity when the fan stops. Constructed from galvanized steel sheet. If used with a silencer, the silencer with a lowered pod must be used.

TS Gravity Shutter Diagram

Diagram showing the dimensions and structure of the TS gravity shutter.

CodeTipo | TypeABB1CØDØEØFØGKg
1TS2010TS 20240220-110161101771851.5
1TS3010TS 25/31330307257158258102853062.5
1TS3510 (I)TS 35465380-222402104384645.0
1TS4010TS 40/45500471-222402104384646.0

(I) Not compatible with silencer 1SI0350 or others.

CB Counterbases to be Walled Up

The counterbase ensures effective anchorage to the duct shaft via masonry fixing of four specially designed metal strips. Manufactured from robust steel sheet with provisions for fixing to the fan base.

CB Counterbase Diagram

Diagram showing the dimensions of the CB counterbase, including anchor points.

CodeTipo | TypeABCØDKg
1CB2000CB 2029026530M8X301.5
1CB3000CB 2539036030M8X302.5
1CB3000CB 3139036030M8X302.5
1CB3500CB 3549045030M8X302.8
1CB4000CB 4063060030M8X303.2

BA Support Base for Roof Fans

The BA support bases and RD reduction pieces are suitable for installing roof fans on corrugated roof coverings. They prevent detrimental water stagnation around the fan and avoid costly carpentry work. The BA base is suitable for fans with a base of 930x930 mm or larger. With the RD reduction, the base can be used for fans with base dimensions down to 500x500 mm. The RD reduction is a single element that can be cut to fit the exact fan dimension.

Versions:

  • BA 10x177 (Cod. 5PL1008): Compatible with "EURO" type roof coverings with a pitch of 177 mm, height of 51 mm, and a slope of 10%.
  • BA 3x177 (Cod. 5PL1015): Compatible with "EURO" type roof coverings with a pitch of 177 mm, height of 51 mm, and a sheet curvature radius of 3 meters.
  • BA 10x146 (Cod. 5PL1009): Compatible with "INTERNATIONAL" type roof coverings with a pitch of 146 mm, height of 48 mm, and a slope of 10%.
  • Reduction RD (Cod. 5PL1010).

Construction: Made from polyester resins reinforced with stratified fiberglass. Finished in RAL 9002 (light grey). The external surface is treated to resist atmospheric agents over time.

Installation: Correct installation involves overlapping the downstream covering slab and under-exposure upstream. A side overlap of at least one and a quarter waves per side is also required.

BA Support Base Diagrams

Diagrams illustrating the BA support bases (BA 10x177, BA 3x177, BA 10x146) and the RD reduction piece, showing their dimensions and compatibility with different roof covering types.

PB Support Base/Silenced Reduction (Pulling Box)

The PB silenced support base (pulling box) is suitable for installing roof fans on flat coverings. It includes acoustic insulation on the fan's inlet side to reduce noise. Constructed from galvanized steel sheet with an internally lined acoustic material.

PB Pulling Box Diagram

Diagram showing the dimensions of the PB silenced support base.

CodeTipo | TypeABCD
5PB310025/31380360520780
5PB350035480450620880
5PB400040/456306007701030

CCr Inlet Protection Guard

These guards prevent accidental contact with the fan's moving parts. Manufactured from steel rod according to UNI 12499 standard and protected against atmospheric agents.

CCr Inlet Protection Guard Diagram

Diagram showing the dimensions of the CCr inlet protection guard.

CodeTipo | TypeØAKg
5RE9027CCr 253050.31
5RE9032CCr 313550.49
5RE0055CCr 355250.50
5RE0056CCr 406651.00
REA REV 4-9-25-1 Adobe InDesign 20.0 (Macintosh) Adobe PDF Library 17.0

Related Documents

Preview REA EC Centrifugal Roof Fans with External Rotor Motor | DYNAIR
Comprehensive product information for DYNAIR's REA EC centrifugal roof fans. This document details technical specifications, performance data, dimensions, construction, motor details, and available accessories, emphasizing EC motor technology for energy efficiency.
Preview Dynair FCP & FCP-V High Performance Centrifugal Roof Fans Datasheet
This document provides comprehensive technical specifications, performance data, dimensions, and accessory information for Dynair's FCP and FCP-V series of high-performance centrifugal roof fans, designed for efficient ventilation in various applications.
Preview Dynair FCP/FCP-V High Performance Centrifugal Roof Fans - Technical Specifications & Performance
Comprehensive technical data for Dynair's FCP and FCP-V series centrifugal roof fans, including product overview, construction details, motor specifications, detailed performance data (airflow, pressure, sound levels) for various models, dimensions, and available accessories like silencers, gravity shutters, and support bases. Suitable for industrial and commercial ventilation.
Preview Dynair S-CUBE P Backward Curved Centrifugal Box Fans - Technical Specifications
Comprehensive technical specifications, performance data, dimensions, and accessory details for Dynair's S-CUBE P series of backward-curved centrifugal box fans. Suitable for industrial, commercial, and civil ventilation applications, these fans offer high efficiency, quiet operation, and ease of installation.
Preview DYNAIR FC AT High-Temperature Centrifugal Roof Fans - Technical Specifications
Detailed technical specifications, performance data, dimensions, and accessories for DYNAIR FC AT series single-speed centrifugal roof fans designed for high-temperature air up to 200°C.
Preview Dynair AL Series Forward Curved Blade Centrifugal Fans - Technical Specifications
Comprehensive technical specifications, performance data, dimensions, and accessory details for the Dynair AL series of forward-curved blade centrifugal fans, designed for industrial and civil ventilation, heating, and conditioning applications.
Preview Dynair BOX-T Belt Driven Double Inlet Box Fans: Technical Specifications and Performance Data
Comprehensive technical specifications, performance data, operational limits, dimensions, and accessories for Dynair's BOX-T series of belt-driven double inlet box fans, designed for efficient and quiet air handling in industrial and civil applications.
Preview Dynair CC Duct Axial Fans: Product Catalog and Technical Specifications
Explore the Dynair CC series of duct axial fans, featuring detailed specifications, construction information, performance data, dimensions, and a comprehensive range of accessories for industrial ventilation applications. Includes ErP compliance and IE3 motor information.