AKR F-102 Temperature Controller Panel

F-102 Temperature Controller Panel Specifications
- វិមាត្រ: 150 x 56 x 18 ម។
- Set Temp Range: 15°C~35°C (59°F~95°F)
- Timer Range: 1~24 hours (Display hidden when set to 0 hour)
- Infrared Effective Range: 6~8 meters (May vary slightly depending on environment)
- Function Selection: COOL (Cooling), HEAT (Heating), FAN (Ventilation)
- °C/°F Switching:
- Via remote control or Hold both Temp +/- buttons simultaneously for 10 seconds after power-on
- Cooling Only / Heat-Cool (Low current, High current, 25A)
- Wireless Connection: Between control box and remote
F-102 Wireless Remote Controller / Receiver & Control Box
- Remote Controller: 150 x 56 x 18 mm
- Controller Dock: 76 x 63 x 23 mm
- ប្រអប់បញ្ជា៖ ៣៦០ x ២២០ x ១៣៥ ម។

F-102 Remote Control Operation Manual
New Battery Installation (RESET State)
When batteries are installed for the first time, all LCD segments will illuminate for 5 seconds to verify display functionality.
កំណត់លំនាំដើម:
- Operation Mode → COOL
- Set Temperature → 28°C
- Fan Speed → AUTO
- Sleep Function → OFF
- Airflow Direction → Not available (for chiller unit models)
- Timer Function → Disabled (0 hour)
ការជ្រើសរើសរបៀបប្រតិបត្តិការ
- Press the “Mode” button to cycle through: COOL (Cooling) → FAN (Ventilation) → HEAT (Heating)
Temperature Setting (SET TEMP)
- In COOL mode: Press ▲/▼ to adjust temperature (15°C~35°C).
- In HEAT mode: Press ▲/▼ to adjust temperature (15°C~35°C).
- In FAN mode: Temperature setting is disabled.
ការកំណត់ល្បឿនកង្ហារ
- Press the “Fan Speed” button to cycle through: HIGH → MED (Medium) → LOW → AUTO
Sleep Function (SLEEP)
- For use during sleep
- Effective in COOL mode only:
- បន្ទាប់ពីការធ្វើឱ្យសកម្ម
- Temperature increases by 1°C after 1 hour
- Increases another 1°C after 2 hours (total +2°C)
- No further adjustment afterward
- Returns to original set temperature after 8 hours
- Press again to cancel SLEEP function
Airflow Direction (OSC.)
Not available (for chiller unit models)
Auto-OFF Timer Setting (TIMER) While unit is ON
Press “Timer” button (▲/▼) to set desired shutdown time
Auto-ON Timer Setting (TIMER) While unit is OFF
Press “Timer” button (▲/▼) to set desired startup time
បើក/បិទ
- Press “POWER ON/OFF” button to toggle system power
ស្ថានភាពសូចនាករ LED អ្នកទទួល
- Power-on Confirmation → Blue and orange LEDs flash simultaneously once
- Blue LED Steady On → Water valve ON during operation
- Blue LED Slow Flash → Water valve OFF during operation (serves as power indicator)
- Blue LED Rapid Flash → Abnormal system status
- Green LED On → Comfort Sleep mode active
- Red LED On → Scheduled ON/OFF timer active
- Orange LED On → Sleep mode + scheduled OFF timer active
- Remote Signal Reception → Buzzer emits one short beep
Air Conditioning Functions
របៀបត្រជាក់
Valve Contact Operation
- Valve contact opens when:
- Room temperature ≥ (Set temperature + 0.5°C)
- Valve contact closes when:
- Room temperature ≤ (Set temperature – 0.5°C)
ការកំណត់ល្បឿនរបស់អ្នកគាំទ្រ
- AUTO (Automatic) → HIGH (High speed)
- MED (Medium speed) → LOW (Low speed)
ល្បឿនកង្ហារស្វ័យប្រវត្តិ
បី-សtage auto fan speed logic in cooling mode
| Δ = (Room – Set temp) | ល្បឿនកង្ហារ |
|---|---|
| Δ ≥ 3.0 | ខ្ពស់។ |
| 2.5 ≤ Δ ≥ 2.0 | Maintain Current Speed |
| Δ = 1.5 | មធ្យម |
| 1.0 ≥ Δ ≥ 0.5 | Maintain Current Speed |
| Δ ≤ 0 | ទាប |
ឯកតាសំខាន់
ON, Heater: OFF
របៀបកំដៅ
2-Pipe/DX Valve Operation
- Valve contact opens when Set temp ≥ (Room temp + 0.5°C).
- Valve contact closes when Set temp ≤ (Room temp – 0.5°C).
- Heater contact ON, Main unit contact ON.
4-Pipe/Electric Heater Operation
- Heater contact opens when Set temp ≥ (Room temp + 0.5°C).
- Heater contact closes when Set temp ≤ (Room temp – 0.5°C).
- Valve contact OFF, Main unit contact ON.
- Fan delay: After shutdown in heating mode, low-speed contact delays 30 sec before closing.
Selectable Fan Speed
- Auto → High → Medium → Low
1 Auto Fan Speed
២-សtage auto speed logic for heating mode
| Δ = (Room – Set temp) | ល្បឿនកង្ហារ |
|---|---|
| Δ ≥ 3.0 | ខ្ពស់។ |
| 2.5 ≤ Δ ≥ 2.0 | Maintain Current Speed |
| Δ = 1.5 | មធ្យម |
| 1.0 ≥ Δ ≥ 0.5 | Maintain Current Speed |
| Δ ≤ 0 | ទាប |
ម៉ូដែលពង្រីក
Additional Features for DX (Direct Expansion) AC Units
- 3-minute delay start protection for 3-way valve (optional high-current RELAY for compressor control)
- OSC. louver setting: Controls main unit RELAY → ON/OFF for louver function
Jumper Setting Table
| ប៉ារ៉ាម៉ែត្រ | មុខតំណែង | លំនាំដើម | ជួរកំណត់ |
|---|---|---|---|
| 1 : Power-on Behavior | SW1:5&4 Jumper | បិទថាមពល | SW1:5=Short, SW1:4=Short (Power-off) * SW1:5=Open, SW1:4=Short (Power-off) SW1:5=Short, SW1:4=Open (Power-on) SW1:5=Open, SW1:4=Open (Memory) |
| 2: Valve (3-way/Compressor) Delay Protection | SW1:3 Jumper | គ្មានការពន្យារពេល | * SW1:3=Short (No Delay) SW1:3=Open (3 min) |
| 3 : Coil Configuration | SW1:2 Jumper | 2-Pipe/DX | * SW1:2=Short (2-Pipe/DX) SW1:2=Open (4-Pipe/Electric) |
| 4 : Unit Interlock/ Louver Contact Function | SW1:1 Jumper | Unit Interlock | * SW1:1=Short (Unit Interlock) SW1:1=Open (Louver Function) |
ចំណាំ
- Configure jumper settings by cutting (Open) or connecting (Short) the corresponding SW1 jumpers on the control box.
- For louver (air direction) function [DX model]: Set SW1:1 to Open. The unit interlock contact will be converted to louver contact output (dry contact).
- * indicates factory default setting.
សំណួរគេសួរញឹកញាប់
How do I change the temperature setting?
Use the remote controller to adjust the temperature by pressing the Temp +/- buttons or via the temperature settings on the control box.