Kentec Electronics Ltd XT+ Releasing Control Unit
Product Information
The XT+ Releasing Control Unit is a product manufactured by Kentec Electronics Ltd. It is designed to provide control and monitoring capabilities for fire suppression systems. The unit features various terminals and wiring connections to facilitate the integration of different components.
Key Features
- Addressable modules with DIP switches for easy configuration
- Power supply connections for AC input and field terminations
- Standby batteries for backup power
- Alarm terminals for connecting audible loads
- Extinguishing circuits for controlling releasing agents
- Top and bottom terminals for various control and monitoring functions
- CIE serial communication for data transfer
Product Usage Instructions
- Setting the Module Address: Set the address DIP switches on each module to a unique address between 1 and 15.
- Power Supply: Connect 18 to 14 AWG wiring for all field terminations except the AC input. Connect 14 AWG wiring for line, neutral, and ground terminations of the AC input.
- Standby Batteries: Use two standby batteries wired in series. The batteries should be 12 VDC, valve-regulated lead acid type with a maximum amp hour capacity of 60 AH. Connect the batteries to the unit for standby operation. The battery charge voltage should be 27.6 VDC.
- Alarm Terminals: Use the provided terminals for connecting nonpulsing audible loads. Each terminal provides a regulated 24V DC, with a maximum output of 850 mA. Ensure to use a 10k Ohm resistor for the required end-of-line (EOL) connection.
- Extinguishing Circuits: Connect the Exting. 1 (Main) and Exting. 2 (Reserve) circuits to releasing agent control valves. Each circuit provides regulated 24V DC at a maximum output of 1A. Use an EOL diode for the required end-of-line connection.
- Top Terminals: The top terminals provide various power and control outputs. Refer to the product manual for detailed specifications of each terminal.
- Bottom Terminals: Remove the jumper LK1 from each module, unless it is the last device on the CIE serial bus. The bottom terminals are designed for different control and monitoring functions. Refer to the product manual for detailed specifications of each terminal.
- CIE Serial: Use a two-wire RS485 connection for CIE serial communication. Ensure that the data voltage is 3.3V and current-limited. The communication is supervised and operates in a Class B mode.
WIRE ROUTING
Because the fascia is hinged, route all wiring to the left as shown, so that the fascia can be opened without disconnecting the wiring. Power-limited conductors must be installed using Types FPL, FPLR, FPLP, or equivalent cables. When connecting field wiring, separate high and low voltage wiring in the enclosure with a minimum gap of 0.25”. Do not route low voltage cabling through the same conduit as AC lines. AC power lines should be threaded through a dedicated conduit. Refer to this illustration when connecting any wiring.
SETTING THE MODULE ADDRESS
Set the address DIP switches on each module to a unique address between 1 and 15.
POWER SUPPLY
Connect 18 to 14 AWG wiring for all field terminations except the AC input. Connect 14 AWG wiring for line, neutral, and ground terminations of the AC input.
AC SUPPLY CIRCUIT SPECIFICATIONS | |
L | AC Power 1.83 Amps Max @ 120 V, 50/60 Hz 0.915 Amps Max @ 240 V, 50/60 Hz |
N | Neutral |
G | Earth Ground |
STANDBY BATTERIES
RECHARGABLE BATTERY SPECIFICATIONS | |
Standby Battery Type | 12 VDC, valve-regulated lead acid |
Standby Battery Charging | Two standby batteries wired in series |
Maximum Amp Hour Capacity | 60 AH maximum |
Charge Current | 1.25 A Max |
Output Current | 4 A Max |
Standby Operating Time | 24 Hours |
Battery Charge Voltage | 27.6 VDC |
3RD STAGE ALARM / 2ND STAGE ALARM
- Each terminal provides a regulated 24V DC, 850 mA maximum output for non-pulsing audible loads.
- Required EOL: 10k Ohm Resistor (S2028)
- Maximum Line Loss: 4V
- Maximum RMS Current for any Single Appliance: 300 mA
EXTING. 1 (MAIN) AND EXTING. 2 (RESERVE)
- The Exting. 1 and Exting. 2 are class B circuits, each providing regulated 24V DC at 1A maximum. They can be connected to a releasing agent control valves as shown.
- Required EOL: EOL Diode (S2029)
TOP TERMINALS
TOP TERMINAL SPECIFICATIONS
TOP TERMINAL SPECIFICATIONS | |
24V Power | 24V Regulated, continuous (power input) |
Aux 24V | 24V Regulated @ 850mA Max, Power-limited |
Trouble | Volt-free contact rated at 30V DC, 1A, Resistive |
1st Stage | Volt-free contact rated at 30V DC, 1A, Resistive |
2nd Stage | Volt-free contact rated at 30V DC, 1A, Resistive |
3rd Stage (Released) | Volt-free contact rated at 30V DC, 1A, Resistive |
Supv. / Abort | Volt-free contact rated at 30V DC, 1A, Resistive |
Extract | Volt-free contact rated at 30V DC, 1A, Resistive |
3rd Stage Alarm | 24V Regulated @ 850mA Max, Power-limited |
2nd Stage Alarm | 24V Regulated @ 850mA Max, Power-limited |
Exting. 1 (Main) | 24V Regulated @ 1A Max, Power-limited |
Exting. 2 (Reserve) | 24V Regulated @ 1A Max, Power-limited |
BOTTOM TERMINALS
IMPORTANT! Remove the jumper LK1 from each module unless the module is the last device on the CIE serial bus.
BOTTOM TERMINAL SPECIFICATIONS | |
Man. Rel Abort Disable Mode Rel P. Sw Low Press. | Class B Supervised for opens, shorts, and grounds End-of-Line device: 6.8K Ohm resistor (S2027) Activation device: 470 Ohm resistor (S2051) Maximum Voltage / Current: 24V DC / 50 mA Maximum Wiring Impedance for Each Circuit: 50 Ohms Power-limited |
CIE Serial | Two wire, RS485 connection, Data 3.3 V, current-limited, Class B, supervised |
Status Serial | Two wire, RS485 connection, Data 3.3 V, current-limited, Class B, supervised |
Status Pow. | 24V Regulated @ 850mA Max, Power-limited |
ACCESSORIES | |
K1822-10 K1822-40 | Ancillary Board with Enclosure |
K1823-10 K1823-40 | Abort Switch, Suitable for Releasing |
K1821-11 K1821-12 K1821-13 K1821-14 K1821-41 K1821-42 K1821-43 K1821-44 | XT+ Status Unit Surface mount, Red Flush mount, Red Surface mount with Keyswitch, Red Flush mount with Keyswitch, Red Surface mount, Grey Flush mount, Grey Surface mount with Keyswitch, Grey Flush mount with Keyswitch, Grey |
K1832-10 K1832-40 | Manual Extinguishant Disablement Switch |
K1824-10 K1824-11 K1824-40 K1824-41 | Sequential Activator, Suitable for Releasing Standard cabinet, Red Large cabinet, Red Standard cabinet, Gray Large cabinet, Gray |
COMPATIBLE RELEASING DEVICES | |
ASCO | 8210G207 |
ASCO | HV2185328 |
Fire Eater | 305451 Ci IS8B Solenoid and Manual |
Fire Eater | 305450 Ci IS8B Solenoid |
Firetrace, TLX Technologies | Linear Actuator-FTF500125 or 01-501462; TLX Technologies PA0128-5 |
Firetrace | FTF500024, Solenoid, 24VDC, 11W |
Firetrace | FTF501224, Solenoid, 24VDC, 15W |
Janus | 18481 |
Kidde | B6793-859: The B6793-859 is equivalent to Kidde-Fenwall 81-100000-001 |
Kidde | K-45-8017: The K-45-8017 is equivalent to Kidde-Fenwall 486500-01 |
Safety Hi-Tech | SH21006404 |
Safety Hi-Tech | SH21006403 |
Sevo Systems. TLX Technologies | SOL EA45: The SOL EA45 is equivalent to Sevo Systems 510006 and TLX Technologies PA0036-3 |
Snap-Tite, Sevo Systems, Orient Chemori, Solenoid Solutions | 2823A-2NB-A4F6 |
Victaulic | Series 753-E FireLock |
Viking | 11596 |
Viking | 11595 |
Viking | 11592 |
Viking | 11602 |
Viking | 11601 |
Viking | 11591 |
SPECIAL RELEASING ACCESSORIES
SPECIAL RELEASING ACCESSORIES | |
Kentec Electronics Sequential Activator | K1824-10 or -40 (Red or Gray) K1824-11 or -41 (Red or Gray) FP-SA/GEN3.0 (Gray) FP-SA/GEN3.0R (Red) FP-SA/GEN3M8 (Gray) FP-SA/GEN3M8R (Red) |
FirePro Fixed Condensed Aerosol Extinguishing System Units | FP-20SE (FNX-20S) FP-20T (FNX-20T) FP-40S (FNX-40S) FP-40T (FNX-40T) FP-80S (FNX-80S) FP-80T (FNX-80T) FP-100S (FNX-100S) FP-200S (FNX-200S) FP-500S (FNX-500S) FP-1200 (FNX-1200) FP-1200S (FNX-1200S) FP-1200T (FNX-1200T) FP-1200TS (FNX-1200TS) FP-2000 (FNX-2000) FP-2000S (FNX-2000S) FP-2000T (FNX-2000T) FP-2000TS (FNX-2000TS) FP-3000 (FNX-3000) FP-3000S (FNX-3000S) FP-3000T (FNX-3000T) FP-3000TS (FNX-3000TS) FP-4200T (FNX-4200T) FP-4200TS (FNX-4200TS) FP-5700 (FNX-5700) FP-5700S (FNX-5700S) FP-5700T (FNX-5700T) FP-5700TS (FNX-5700TS) |
Please refer to instructions included with Sequential Activator for proper wiring. |
SPECIAL RELEASING ACCESSORIES (continued) | |
Fireway Inc. Stat-X, 30E | 15100 |
STAT-X Aerosol Fire Stat-X, 60E | 15110 |
Suppression System Stat-X, 60ME | 15111 |
Stat-X, 100E | 15120 |
Stat-X, 250E | 15130 |
Stat-X, 500E | 15140 |
Stat-X, 1000E | 15150 |
Stat-X, 1500E | 15160 |
Stat-X, 2500E | 15170 |
Stat-X EX, 30E, CLI DIV2/Zone 2, Brass Elbow | 11880 |
Stat-X EX, 30E, CLI DIV2/Zone 2, SS Elbow | 11885 |
Stat-X EX, 60E, CLI DIV2/Zone 2, Brass Elbow | 11890 |
Stat-X EX, 60E, CLI DIV2/Zone 2, SS Elbow | 11895 |
Stat-X EX, 60ME, CLI DIV2/Zone 2, Brass Elbow | 11900 |
Stat-X EX, 60ME, CLI DIV2/Zone 2, SS Elbow | 11905 |
Stat-X EX, 100E, CLI DIV2/Zone 2, Brass Elbow | 11910 |
Stat-X EX, 100E, CLI DIV2/Zone 2, SS Elbow | 11915 |
Stat-X EX, 250E, CLI DIV2/Zone 2, Brass Elbow | 11920 |
Stat-X EX, 250E, CLI DIV2/Zone 2, SS Elbow | 11925 |
Stat-X EX, 500E, CLI DIV2/Zone 2, Brass Elbow | 11930 |
Stat-X EX, 500E, CLI DIV2/Zone 2, SS Elbow | 11935 |
Stat-X EX, 1000E, CLI DIV2/Zone 2, Brass Elbow | 11940 |
Stat-X EX, 1000E, CLI DIV2/Zone 2, SS Elbow | 11945 |
Stat-X EX, 1500E, CLI DIV2/Zone 2, Brass Elbow | 11950 |
Stat-X EX, 1500E, CLI DIV2/Zone 2, SS Elbow | 11955 |
Stat-X EX, 2500E, CLI DIV2/Zone 2, Brass Elbow | 11960 |
Stat-X EX, 2500E, CLI DIV2/Zone 2, SS Elbow | 11965 |
Please refer to instructions included with Sequential Activator for proper wiring. REFERENCES Reference the following documentation for installing, operating, and configuring this device with the XT+ Releasing Control Unit:
|
For technical support, contact Kentec Electronics, Ltd at +44 (0)1322 222121 or techsupport@kentec.co.uk.
Kentec Electronics Ltd
- Units 25-26 Fawkes Avenue
- Questor, Dartford
- Kent DA1 1JQ United Kingdom
- +44 (0)1322 222121
- www.kentec.co.uk
Documents / Resources
![]() | Kentec Electronics Ltd XT+ Releasing Control Unit [pdf] Instruction Manual Man-1255KE, XT, XT Releasing Control Unit, Releasing Control Unit, Control Unit |