Set Point

  • PRESS & HOLD “SET” for 1 second. “SET POINT” value will be displayed
  • PRESS ARROW “UP” or “DOWN” to set the desired value. **
  • PRESS “SET” to confirm the value

Frequent (F) Parameters

PRESS & HOLD “SET” for approx 5 seconds “PS” will be displayed

  • A) PRESS “ARROW UP” or “DOWN” to select the parameter to be changed. eg rd = differential
  • B) PRESS “SET” The Value Set for this parameter will be displayed
  • C) PRESS ARROW “UP” or “DOWN” to set the desired value. **
  • D) PRESS “SET” to confirm the value
    REPEAT A-D until all desired parameters have been set
    PRESS & HOLD “SET” until temp is displayed (approx 5 seconds) to confirm all changes

All Parameters

  • PRESS & HOLD “SET” for approx 5 seconds “PS” will be displayed
  • PRESS “SET” then “ARROW UP” until the password value “22” is displayed
  • PRESS “SET” to confirm “PS” will be displayed
  • A) PRESS “ARROW UP” or “DOWN” to select the code of the parameter to be changed. eg rd = differential
  • B) PRESS “SET”. The Value Set for this parameter will be displayed
  • C) PRESS “ARROW UP” or “DOWN” to set the desired value.
  • D) PRESS “SET” to confirm the value
    • REPEAT A-D until all desired parameters have been set.
    • PRESS & HOLD “SET” until the temp is displayed (approx 5 seconds) to confirm all changes

Please note: Please read these instruction in conjunction with the parameter list. It is recommended that the controllers be programmed before connecting or activating the plant to be controlled (eg. compressors)
** If the controller is keypad locked the value will not change. See parameter H2.

Summary of Operating Parameters

CodeParameterUnitTypeMin.!Maxj Def.New
/2Probe measurement stability C1154 
/4Select display probe F131 
/5Select °Cor °F(0 = 0c) C0 0 
/6Decimal point (0 = enabled, 1 = disabled) C0 0 
/C1Calibration of probe 1oc/oFF-127+1270 
/C2Calibration of probe 2oc/oFF-127+1270 
/C3Calibration of probe 3oc/oFF-127+1270 
 
StTemperature set pointoc/oFsr1r24 
rdController differentialoc/oFF0192 
r1Minimum Set Point allowedoc/oFC-50r2-50 
r2Maximum Set Point allowedoc/oFCr1+15090 
r3Mode 0=cool with defrost,1=cool only, 2=heatingflagC020 
r4Value to increase Set Point by from Digital Inputoc/oFC0203 
 
coComp. and fan start delay at power upminC01000 
c1Minimum time between 2 comp startsminC01000 
c2Minimum compressor OFF timeminC01000 
c3Minimum compressor ON timeminC01000 
c4Duty settingminC01000 
ccDuration of continuous cyclehoursC0154 
c6Alarm bypass after continuous cyclehoursC0152 
 
d0Defrost type (0=elec I temp,1= H.Gas / temp C040 
 2 = elec I time, 3 = hot gas/ time … )      
diInterval between defrosts (if not using real time)hoursF01998 
dtEnd defrost temperature,(if d0 = 0 or 1)oc/oFF-501274 
dPMaximum defrost durationminF119930 
d4Defrost at power up (0 = no, 1 = yes) C0 0 
d5Defrost delay at power up (if d4=1)minC01990 
d6Display during def.(0=dF (flash),1=locked) C0 1 
ddDripping time after defrostminF0152 
d8Bypass alarms after defrosthoursF0151 
d8dAlarm delayafter door open – from dig inputhoursC02500 
d9Defrost priority over compressor protection C0 0 
d/Display defrost probe temp d/1=def P1,d/2=def P2)oc/oFF    
dCTime basis for defrost (0=hr/min, 1=min/sec) C0 0 
 
AOAlarm and fan differentialoc/oFC-20200 
ALLow alarm temp (if A0=<0 absolute, if A0>0 relative)oc/oFF-50150-50 
AHHigh alarm temp (if A0=<0 absolute, if A0>0 relative)oc/oFF-50150150 
AdLow and high temperature alarm delayminC01990 
A4Configuration of digital input 1 C0110 
A7External alarm delay if using digital inputminC01990 
A8Enable alarm ‘Ed’ (defrost end on time)flagC0 0 
AcHigh condenser temperature alarm set pointoc/oFC-5015070 
CodeParameterUnitTypeMin.!Maxj Def.New
AEHigh cond. temp. alarm differentialoc/oFC0.1205 
AcdHigh cond. temp. alarm delayminC02500 
 
F0Enable evaporator fan controlflagC0 0 
F1Evaporator fan control set pointoc/oFF-501275 
F2Fans cycle with comp (0=no, 1=yes)flagC0   
F3Fans in defrost (0 = on, 1 = off)flagC0   
FdFans delay after drippingminF015  
 
HOSerial address C02071 
H1AUX output configurationflagC030 
H2Enable keypad (0=enabled, 1 = disabled)flagC0 1 
H4Disable buzzer (0=enabled, 1 = disabled)flagC0 0 
H5ID code (read-only)flagF031  
EZYSelect set of default parameters C040 
EZY parameter
 
PJEZ (S, X)EZY = 1: normal temperature, no defrost
 EZY = 2: normal temperature with timed defrost
 EZY = 3: normal temperature, heating output
 EZY = 4: normal temperature, defrost controlled by temperature (d0 = 4)
 
PJEZ (C, Y)EZY = 1: low temperature with hot gas defrost
 EZY = 2:low temperature with automatic night-time set point variation via digital input
 EZY = 3: low temperature with management of alarm via digital input
 EZY = 4: low temperature, defrost controlled by temperature (d0 = 4
ALARM TABLE
Alarm codeBuzzer & alarm relayLEDDescriptionParameters involved
E0activeONprobe 1 error (control) 
E1not activeONprobe 2 error (defrost)[d0 = 0/1/4] [F0 = 1]
E2not activeONprobe 3 error (cond)[A4 = 10]
IAactiveONexternal alarm[A4 = 1] [+A7]
dORactiveONopen door alarm[A4 = 7/8] [+A7]
LOactiveONlow temperature alarm[AL] [Ad]
HIactiveONhigh temperature alarm[AH] [Ad]
EEnot activeONunit parameter error 
EFnot activeONoperating parameter error 
Ednot activeONdefrost ended by timeout[dP] [dt] [d4] [A8]
dFnot activeOFFdefrost running[d6 = 0]
chtnot activeONdirty condenser pre-alarm[A4 = 10]
CHtactiveONdirty condenser alarm[A4 = 10]
EtCnot activeONclock alarmif bands active

www.kegco.com