Kegco XCK-1 Control Panel
Set Point
- PRESS & HOLD “SET” for 1 second. “SET POINT” value will be displayed
- PRESS ARROW “UP” or “DOWN” to set the desired value. **
- PRESS “SET” to confirm the value
Frequent (F) Parameters
PRESS & HOLD “SET” for approx 5 seconds “PS” will be displayed
- A) PRESS “ARROW UP” or “DOWN” to select the parameter to be changed. eg rd = differential
- B) PRESS “SET” The Value Set for this parameter will be displayed
- C) PRESS ARROW “UP” or “DOWN” to set the desired value. **
- D) PRESS “SET” to confirm the value
REPEAT A-D until all desired parameters have been set
PRESS & HOLD “SET” until temp is displayed (approx 5 seconds) to confirm all changes
All Parameters
- PRESS & HOLD “SET” for approx 5 seconds “PS” will be displayed
- PRESS “SET” then “ARROW UP” until the password value “22” is displayed
- PRESS “SET” to confirm “PS” will be displayed
- A) PRESS “ARROW UP” or “DOWN” to select the code of the parameter to be changed. eg rd = differential
- B) PRESS “SET”. The Value Set for this parameter will be displayed
- C) PRESS “ARROW UP” or “DOWN” to set the desired value.
- D) PRESS “SET” to confirm the value
- REPEAT A-D until all desired parameters have been set.
- PRESS & HOLD “SET” until the temp is displayed (approx 5 seconds) to confirm all changes
Please note: Please read these instruction in conjunction with the parameter list. It is recommended that the controllers be programmed before connecting or activating the plant to be controlled (eg. compressors)
** If the controller is keypad locked the value will not change. See parameter H2.
Summary of Operating Parameters
Code | Parameter | Unit | Type | Min.!Maxj Def. | New | ||
/2 | Probe measurement stability | C | 1 | 15 | 4 | ||
/4 | Select display probe | F | 1 | 3 | 1 | ||
/5 | Select °Cor °F(0 = 0c) | C | 0 | 0 | |||
/6 | Decimal point (0 = enabled, 1 = disabled) | C | 0 | 0 | |||
/C1 | Calibration of probe 1 | oc/oF | F | -127 | +127 | 0 | |
/C2 | Calibration of probe 2 | oc/oF | F | -127 | +127 | 0 | |
/C3 | Calibration of probe 3 | oc/oF | F | -127 | +127 | 0 | |
St | Temperature set point | oc/oF | s | r1 | r2 | 4 | |
rd | Controller differential | oc/oF | F | 0 | 19 | 2 | |
r1 | Minimum Set Point allowed | oc/oF | C | -50 | r2 | -50 | |
r2 | Maximum Set Point allowed | oc/oF | C | r1 | +150 | 90 | |
r3 | Mode 0=cool with defrost,1=cool only, 2=heating | flag | C | 0 | 2 | 0 | |
r4 | Value to increase Set Point by from Digital Input | oc/oF | C | 0 | 20 | 3 | |
co | Comp. and fan start delay at power up | min | C | 0 | 100 | 0 | |
c1 | Minimum time between 2 comp starts | min | C | 0 | 100 | 0 | |
c2 | Minimum compressor OFF time | min | C | 0 | 100 | 0 | |
c3 | Minimum compressor ON time | min | C | 0 | 100 | 0 | |
c4 | Duty setting | min | C | 0 | 100 | 0 | |
cc | Duration of continuous cycle | hours | C | 0 | 15 | 4 | |
c6 | Alarm bypass after continuous cycle | hours | C | 0 | 15 | 2 | |
d0 | Defrost type (0=elec I temp,1= H.Gas / temp | C | 0 | 4 | 0 | ||
2 = elec I time, 3 = hot gas/ time … ) | |||||||
di | Interval between defrosts (if not using real time) | hours | F | 0 | 199 | 8 | |
dt | End defrost temperature,(if d0 = 0 or 1) | oc/oF | F | -50 | 127 | 4 | |
dP | Maximum defrost duration | min | F | 1 | 199 | 30 | |
d4 | Defrost at power up (0 = no, 1 = yes) | C | 0 | 0 | |||
d5 | Defrost delay at power up (if d4=1) | min | C | 0 | 199 | 0 | |
d6 | Display during def.(0=dF (flash),1=locked) | C | 0 | 1 | |||
dd | Dripping time after defrost | min | F | 0 | 15 | 2 | |
d8 | Bypass alarms after defrost | hours | F | 0 | 15 | 1 | |
d8d | Alarm delayafter door open – from dig input | hours | C | 0 | 250 | 0 | |
d9 | Defrost priority over compressor protection | C | 0 | 0 | |||
d/ | Display defrost probe temp d/1=def P1,d/2=def P2) | oc/oF | F | ||||
dC | Time basis for defrost (0=hr/min, 1=min/sec) | C | 0 | 0 | |||
AO | Alarm and fan differential | oc/oF | C | -20 | 20 | 0 | |
AL | Low alarm temp (if A0=<0 absolute, if A0>0 relative) | oc/oF | F | -50 | 150 | -50 | |
AH | High alarm temp (if A0=<0 absolute, if A0>0 relative) | oc/oF | F | -50 | 150 | 150 | |
Ad | Low and high temperature alarm delay | min | C | 0 | 199 | 0 | |
A4 | Configuration of digital input 1 | C | 0 | 11 | 0 | ||
A7 | External alarm delay if using digital input | min | C | 0 | 199 | 0 | |
A8 | Enable alarm ‘Ed’ (defrost end on time) | flag | C | 0 | 0 | ||
Ac | High condenser temperature alarm set point | oc/oF | C | -50 | 150 | 70 |
Code | Parameter | Unit | Type | Min.!Maxj Def. | New | ||
AE | High cond. temp. alarm differential | oc/oF | C | 0.1 | 20 | 5 | |
Acd | High cond. temp. alarm delay | min | C | 0 | 250 | 0 | |
F0 | Enable evaporator fan control | flag | C | 0 | 0 | ||
F1 | Evaporator fan control set point | oc/oF | F | -50 | 127 | 5 | |
F2 | Fans cycle with comp (0=no, 1=yes) | flag | C | 0 | |||
F3 | Fans in defrost (0 = on, 1 = off) | flag | C | 0 | |||
Fd | Fans delay after dripping | min | F | 0 | 15 | ||
HO | Serial address | C | 0 | 207 | 1 | ||
H1 | AUX output configuration | flag | C | 0 | 3 | 0 | |
H2 | Enable keypad (0=enabled, 1 = disabled) | flag | C | 0 | 1 | ||
H4 | Disable buzzer (0=enabled, 1 = disabled) | flag | C | 0 | 0 | ||
H5 | ID code (read-only) | flag | F | 0 | 31 | ||
EZY | Select set of default parameters | C | 0 | 4 | 0 |
EZY parameter | |
PJEZ (S, X) | EZY = 1: normal temperature, no defrost |
EZY = 2: normal temperature with timed defrost | |
EZY = 3: normal temperature, heating output | |
EZY = 4: normal temperature, defrost controlled by temperature (d0 = 4) | |
PJEZ (C, Y) | EZY = 1: low temperature with hot gas defrost |
EZY = 2:low temperature with automatic night-time set point variation via digital input | |
EZY = 3: low temperature with management of alarm via digital input | |
EZY = 4: low temperature, defrost controlled by temperature (d0 = 4 |
ALARM TABLE | ||||
Alarm code | Buzzer & alarm relay | LED | Description | Parameters involved |
E0 | active | ON | probe 1 error (control) | |
E1 | not active | ON | probe 2 error (defrost) | [d0 = 0/1/4] [F0 = 1] |
E2 | not active | ON | probe 3 error (cond) | [A4 = 10] |
IA | active | ON | external alarm | [A4 = 1] [+A7] |
dOR | active | ON | open door alarm | [A4 = 7/8] [+A7] |
LO | active | ON | low temperature alarm | [AL] [Ad] |
HI | active | ON | high temperature alarm | [AH] [Ad] |
EE | not active | ON | unit parameter error | |
EF | not active | ON | operating parameter error | |
Ed | not active | ON | defrost ended by timeout | [dP] [dt] [d4] [A8] |
dF | not active | OFF | defrost running | [d6 = 0] |
cht | not active | ON | dirty condenser pre-alarm | [A4 = 10] |
CHt | active | ON | dirty condenser alarm | [A4 = 10] |
EtC | not active | ON | clock alarm | if bands active |