Munters SyCool® Split - 250 kW

Indirect Economizer Thermosyphon Split-System

Munters SyCool Split provides an efficient cooling solution for new and retrofit installations where access to a suitable water supply may be limited, expensive or unreliable.

Advantages

The system nominal cooling capacity is 250 kW. Thermosyphon heat exchangers move heat from the data center to ambient through the evaporation of liquid refrigerant in the SyCool evaporator, and condensing of the same refrigerant in the SyCool condenser. The evaporator is connected to the condenser with refrigerant piping allowing up to 500' of separation. As long as the condenser receives air cooler than the evaporator, heat is exchanged passively for "free cooling" of the data center. A simplified version of the system is schematically shown in Figure 1.

The SyCool 250 thermal effectiveness is nominally 65%, which greatly exceeds that of competing refrigerant based economizer systems. For example, with air delivered to servers at 75°F and a 20°F delta T across the servers, SyCool achieves 100% free cooling when the ambient dry bulb temperature is 62°F or lower (operating at 75% load). As ambient temperature rises, SyCool transitions from passive to active by staging/modulating compressors located in the condenser section. Data center heat is rejected by the thermosyphon, passively or actively without the need for diverting valves, allowing seamless transition from economizer to active cooling. As the ambient temperature approaches the temperature from the servers, SyCool finally loses free cooling capacity. The high heat exchange effectiveness coupled with the ability to economize simultaneously with active refrigeration, yields best-in-industry economizer capture efficiency.

Figure 1: System schematic showing heat exchange between SyCool Condenser and SyCool Evaporator.

[Diagram: A schematic shows heat being exhausted to ambient from the SyCool Condenser. The condenser has a passive and active section, with a DX Condenser and a compressor. The SyCool Evaporator receives hot air from servers and returns cool air. The thermosyphon connects the condenser and evaporator via gas and liquid lines.]

SyCool 250 kW condenser

[Diagram: Elevation view and side elevation view of the SyCool 250 kW condenser unit, showing dimensions.]

SyCool 250 kW down flow evaporator

[Diagram: Elevation view (face and side) of the SyCool 250 kW down flow evaporator, showing dimensions. Two configurations are shown: bottom supply and horizontal supply.]

System notes:

*depending on interconnecting piping vertical and horizontal separation, plus # elbows

Performance Data - SyCool 250 kW down flow evaporator

Ambient (Deg. F) 19 Deg. Delta T 20 Deg. Delta T 21 Deg. Delta T
kW Capacity (Net) Input Power (kW) Peak pPUE kW Capacity (Net) Input Power (kW) Peak pPUE kW Capacity (Net) Input Power (kW) Peak pPUE
119.7 232 119 1.513 232 116 1.500 232 115 1.496
115 250 121 1.484 250 117 1.468 250 115 1.460
112.3 254 119 1.469 254 115 1.453 254 113 1.445
110 257 117 1.455 257 113 1.440 257 111 1.432
105 262 113 1.431 262 109 1.416 262 107 1.408
103.8 265 113 1.426 265 109 1.411 265 107 1.404
Ambient (Deg. F) 22 Deg. Delta T 23 Deg. Delta T 24 Deg. Delta T
kW Capacity (Net) Input Power (kW) Peak pPUE kW Capacity (Net) Input Power (kW) Peak pPUE kW Capacity (Net) Input Power (kW) Peak pPUE
119.7 232 114 1.491 232 112 1.483 232 111 1.478
115 250 113 1.452 250 112 1.448 250 111 1.444
112.3 254 111 1.437 254 110 1.433 254 108 1.425
110 257 109 1.424 257 108 1.420 257 106 1.412
105 262 105 1.401 262 103 1.393 262 102 1.389
103.8 265 105 1.396 265 103 1.389 265 102 1.385

Notes: 1000' elevation, 0.2" W.C. external static and clean filters, 75°F supply air

Models: SyCool Split 250 kW Indirect Economizer Thermosyphon Split System, SyCool, Split 250 kW Indirect Economizer Thermosyphon Split System, Indirect Economizer Thermosyphon Split System, Economizer Thermosyphon Split System, Thermosyphon Split System, Split System

File Info : application/pdf, 3 Pages, 1.66MB

PDF preview unavailable. Download the PDF instead.

product-sheet--sycool-split-250-kw

References

Adobe PDF Library 16.0.7

Related Documents

Preview Munters MKD-Series Dehumidifier User Manual
Comprehensive user manual for Munters MKD-series dehumidifiers, including models MK30D, MK45D, MK60D, and MK90D. Covers intended use, warranty, safety, installation, operation, maintenance, troubleshooting, technical specifications, wiring diagrams, and spare parts.
Preview Munters CT Evaporative Cooling System with End Tank Instruction Manual
This manual provides detailed instructions for the installation, operation, and maintenance of the Munters CT Evaporative Cooling System with End Tank, including models EC1642 and EC1606. It covers unpacking, system setup, plumbing, operation, and maintenance schedules.
Preview Munters ICA: Integrated Custom Air Handler Desiccant Dehumidifier
Explore the Munters ICA, an integrated custom air handler desiccant dehumidifier offering advanced humidity control, energy efficiency, and high configurability for industrial and manufacturing applications. Learn about its features, advanced design, and custom options.
Preview Munters Q2 2025 Interim Report: Solid Growth and Robust Margin
Munters Group AB's Q2 2025 interim report details strong financial performance with solid growth and robust margins across its AirTech, Data Center Technologies (DCT), and FoodTech business areas. The report covers key financial metrics, CEO commentary, strategic updates, and sustainability initiatives.
Preview Munters CC24-7 Ultra Plus User Manual - Environmental Control System
Detailed user manual for the Munters CC24-7 Ultra Plus environmental control system, providing setup, operation, and maintenance guidance for livestock building climate management.
Preview Munters Drive G2 Rotor Replacement Kit Installation Manual
This manual provides detailed instructions for installing the Munters Drive G2 Rotor Replacement Kit for ATS74 and CX74 Fans. It covers unpacking, parts list, and step-by-step installation procedures for both fan models.
Preview Munters Communicator 2.0 Plus: Installation and User Manual
Comprehensive guide to installing, configuring, and operating the Munters Communicator 2.0 Plus communication system for agricultural monitoring and data logging.
Preview Munters AX51 with G2 Munters Drive Instruction Manual
This instruction manual provides detailed information on the installation, operation, and maintenance of the Munters AX51 Air Circulation Fan with G2 Munters Drive. It covers electrical wiring, troubleshooting, and winterizing procedures for optimal performance and longevity.