Intesis Modbus RTU Interface for Toshiba Air Conditioners -

Modbus PTV [EIA-485] Interface for
Toshiba air conditioners

Compatible with Digital Inverter & VRF lines

USER MANUAL
Issue date: 04/2019 r2.7 ENGLISH

Intesis Modbus RTU Interface for Toshiba Air Conditioners - a

Intesis Modbus RTU Interface for Toshiba Air Conditioners - logo

Modbus RTU (EIA-485) Interface for Toshiba air conditioners Compatible with Digital Inverter & VRF lines

ORDER CODELEGACY ORDER CODE
INMBSTOS001R000TO-RC-MBS-1

Important User Information

Disclaimer

The information in this document is for informational purposes only. Please inform HMS Industrial Networks of any inaccuracies or omissions found in this document. HMS Industrial Networks disclaims any responsibility or liability for any errors that may appear in this document.

HMS Industrial Networks reserves the right to modify its products in line with its policy of continuous product development. The information in this document shall therefore not be construed as a commitment on the part of HMS Industrial Networks and is subject to change without notice. HMS Industrial Networks makes no commitment to update or keep current the information in this document.

The data, examples, and illustrations found in this document are included for illustrative purposes and are only intended to help improve understanding of the functionality and handling of the product. In view of the wide range of possible applications of the product, and because of the many variables and requirements associated with any particular implementation, HMS Industrial Networks cannot assume responsibility or liability for actual use based on the data, examples, or illustrations included in this document nor for any damages incurred during the installation of the product. Those responsible for the use of the product must acquire sufficient knowledge in order to ensure that the product is used correctly in their specific application and that the application meets all performance and safety requirements including any applicable laws, regulations, codes, and standards. Further, HMS Industrial Networks will under no circumstances assume liability or responsibility for any problems that may arise as a result of the use of undocumented features or functional side effects found outside the documented scope of the product. The effects caused by any direct or indirect use of such aspects of the product are undefined and may include e.g. compatibility issues and stability issues.

Presentation

The INMBSTOS001R000 interfaces allow complete and natural integration of Toshiba air conditioners into Modbus RTU (EIA-485) networks.
Compatible with Digital Inverter & VRF lines. Reduced dimensions.
93 x 53 x 58 mm
3.7” x 2.1” x 2.3”Intesis Modbus RTU Interface for Toshiba Air Conditioners - Toshiba

  • Quick and easy installation.
    Mountable on DIN rail, wall, or even inside the indoor unit of AC.
  • External power is not required.
  • Direct connection to Modbus RTU (EIA-485) networks. Up to 63 INMBSTOS001R000 devices can be connected to the same network.
    INMBSTOS001R000 is a Modbus slave device.
  • Direct connection to the AC indoor unit. Up to 16 AC indoor units can be connected to INMBSTOS001R000, controlling them as one (not individually).
  • Configuration from both on-board DIP switches and Modbus RTU.
  • Total Control and Supervision.
  • Real states of the AC unit’s internal variables.
  • Allows simultaneous use of the AC’s remote controls and Modbus RTU.

Intesis Modbus RTU Interface for Toshiba Air Conditioners - Allows simultaneous

* Up to 63 Intesis devices can be installed in the same Modbus RTU bus. However, depending on the configured speed, the installation of Modbus Repeaters may be required

Connection

The interface comes with a plug-in terminal block of 2 poles to establish a direct connection with the AC indoor unit. It comes as well with a plug-in terminal block of 2 poles to establish a direct connection with the Modbus RTU EIA-485 network.

Connect to the AC indoor unit

The INMBSTOS001R000 connects directly to the Toshiba AB Bus, which is not provided within the interface. The recommended connection’ methods are the following ones  (details in Figure 2. 1):

  • Wired remote control available.
  • No remote control is available

Maximum AB bus length is 500 m / 1,640.42 ft. The bus has no polarity sensitivity.

Important: If a wired remote controller of the AC manufacturer is connected to the same bus, communication may shut down.

Intesis Modbus RTU Interface for Toshiba Air Conditioners - Important

Figure 2. 1 ,INMBSTOS001R000 connection diagram

Connection to the EIA-485 bus

Connect the EIA-485 bus wires to the plug-in terminal block of INMBSTOS001R000 and keep the polarity on this connection (A+ and B-). Make sure that the maximum distance to the bus is 1,200 meters (3,937 ft). Loop or star typologies are not allowed in the case of the EIA-485 bus. A terminator resistor of 120Ω must be present at each end of the bus to avoid signal reflections. The bus needs a fail-safe biasing mechanism (see section 4.7 for more details).

Quick Start Guide

  1. Disconnect the air conditioning from the Mains Power.
  2. Attach the interface next to the AC indoor unit (wall mounting) following the instructions of the diagram below or install it inside the AC indoor unit (respect the safety instructions given).
  3. Connect the AB bus between the interface and the AC indoor unit following the instructions of the diagram. Screw each bare cable end in the corresponding AB terminals of each device.
  4. Connect the EIA-485 bus to the connector EIA485 of the interface.
  5. Close the AC indoor unit. 6. Check the DIP-Switch configuration of the Intesis interface and make sure it matches the current installation’s parameters (see section 4.4).

By default, the interface is set to:

Intesis Modbus RTU Interface for Toshiba Air By default

▪ Modbus Slave Address ➔ 1
▪ Modbus baud rate ➔ 9600 bps

These parameters can be modified from SW4 and SW3 DIP-Switches.
All other switch positions are set at a low level (Off position) by default.
NOTE: All changes on the DIP-Switch configuration require a system power cycle to be applied.

7. Connect the AC system to Mains Power.
IMPORTANT: The Intesis interface requires to be connected to the AC unit (powered) to start communicating.

Modbus Interface Specification

Modbus physical layer

INMBSTOS001R000 implements a Modbus RTU (Slave) interface, to be connected to an EIA-485 line. It performs 8N2 communication (8 data bits, no parity, and 2 stop bit) with several available baud rates (2400 bps, 4800 bps, 9600 bps -default-, 19200 bps, 38400 bps, 57600 bps, 76800 bps, and 115200 bps). It also supports 8N1 communication (8 data bits, no parity, and 1 stop bit).

4.2 Modbus Registers

All registers are type “16-bit unsigned Holding Register” and they use the Modbus big-endian notation.

4.2.1 Control and status registers
Register Address
(protocol address)
Register Address
(PLC address)
R/WDescription
01R/WAC unit On/Off
♦ 0: Off
♦ 1: On
12R/WAC unit Mode 1
♦ 0: Auto
♦ 1: Heat
♦ 2: Dry
♦3: Fan
♦4: Cool
23R/WAC unit Fan Speed 1
0: Auto
♦ 1: Low
♦ 2: Mid
♦ 3: High
34R/WAC unit Vane Position 1
♦1: POS1 (Horizontal)
♦ 2: POS2 (Horizontal)
♦ 3: POS3 (Medium)
♦ 4: POS4 (Vertical)
♦ 5: POSS (Vertical)
♦ 6: POS6
♦7: POS7
♦ 10: Swing
45R/WAC unit Temperature Setpoint 1,2,3
♦ -32768 (Initialization value)
♦16..320C (0C/x100C)
♦ 61..900F
  1. Available values will depend on the AC unit mode. Check the AC unit model functions in its user manual to know the possible values for this register.
  2. The magnitude for this register can be adjusted to Celsius x 1ºC, Celsius x 10ºC (default), or Fahrenheit. See section 4.3.6 for more information.
  3. It is not possible to turn to x10 the value shown in Fahrenheit.
Register Address
(protocol address)
Register Address
(PLC address)
R/WDescription
56R/WAC unit Temperature reference 1.2,3

· 32768: Initial value. Value invalid, which comes from the IU’s sensor. If the value that is shown in register 22 (23 PLC) is valid, the address is going to take this value.
· Ranges are specific from Manufacturer (°C/×10°C/°F)

67R/WWindow Contact
· 0: Closed (Default)
· 1: Open
78R/WINMBSTOS001R000 Disablement 4
· 0: INMBSTOS001R000 enabled (Default)
·1: INMBSTOS001R000 disabled
39R/WAC Remote Control Disablement 4
·0: Remote Control enabled (Default)
·1: Remote Control disabled
910R/WAC unit Operation Time 4
· 0..65535 (hours). Counts the time the AC unit is in “On” state.
1011RAC unit Alarm Status
· 0: No alarm condition
·1: Alarm condition
1112RError Code s
·0: No Error active
·65535 (-1): Error in the communication of INMBSTOS001R000 with the AC indoor unit.
·Any other error present, see the table at the end of this document.
2223R/WIndoor unit’s ambient temperature from external sensor (at Modbus side) 1,2,3,6
·-32768: Initialization value. No temperature is being provided from an input sensor. There’s no input sensor.
·Any other: (°C/×10°C/°F)

23

24RAC Real temperature setpoint 1236
There’s no Virtual Temperature. The value equals to the value of register 5 (6 PLC). The value which is introduced by the user is the one that the machine uses (the external sensor is able to write directly over the machine to do this operation).
·Ranges are specific from Manufacturer  (°C/×10°C/°F)
9798R/WBlock Periodic Sendings 4178

· 0: Non-blocked (Default value)
· 1: Blocked

4 . This value is stored in non-volatile memory
5. See section 7 for possible error codes and their explanation
6. See section 4.3.6 for more information
7. If the register is configured as “0:Non-blocked”, all commands received from Modbus will be sent to the AC system. If “1: Blocked”, commands from Modbus will only be sent to the AC system if they differ from the previous value.
8. This register applies to firmware version 2.3 onwards

4.2.2 Configuration Registers

Register Address
(protocol address)13
Register Address
(PLC address)14
R/W
R/W
Description

“Open Window” switch-off timeout 9

· 0..30 (minutes)

·  Factory setting: 30 (minutes)

1415RModbus RTU baud-rate 10

· 2400bps

·4800bps

9600bps (Default)

· 19200bps

·38400bps

· 57600bps

· 76800bps

· 115200bps

1516RModbus Slave Address
· 1..63
2122RMax number of fan speeds
4950RDevice ID: Ox1F00
5051RSoftware version

While the initialization is ongoing, some Modbus registers indicate an undetermined value. Once the normal operation starts, they acquire its corresponding value. It is important to keep in mind that any change done during the initialization process will not have effect until it has been finished.

4.3 Modbus Registers for Advanced Functions

4.3.1 Advanced registers for Indoor Unit status

These registers are only available when the indoor unit’s type selected on SW1 is different from the default value. Please, check the Section 4.4 for more information.

NOTE: IU stands for Indoor Unit’s Index

Register Address
(Protocol address)
Register Address
(PLC address)
R/W Description Priority 
(IU – 1) * 25 + 4000(IU – 1) * 25 + 4001RIndoor Unit exist
▪ 0: Doesn’t exist
▪ 1: Exist
0
(IU – 1) * 25 + 4001(IU – 1) * 25 + 4002RIndoor Unit address
▪ MSB – OU address ; LSB – IU
address
0
(IU – 1) * 25 + 4002(IU – 1) * 25 + 4003RIndoor Unit duty
▪ 0..15
1
(IU – 1) * 25 + 4003(IU – 1) * 25 + 4004RIndoor Unit defrost
▪ 0: Off
▪ 1: On
1

9. Once window contact is open, a count-down to switch off the AC Unit will start from this configured value.
10. The range 38400bps-115200bps applies to firmware version 2.3 onwards

Register Address
(Protocol address)
Register Address
(PLC address)
R/WDescriptionPriority
(IU – 1) * 25 + 4004(IU – 1) * 25 + 4005RIndoor Unit filter alarm
▪ 0: No alarm
▪ 1: Alarm
1
(IU – 1) * 25 + 4005(IU – 1) * 25 + 4006RIndoor Unit 11hermos ON.
▪ 0: Cool
▪ 1: Heat
1
(IU – 1) * 25 + 4010(IU – 1) * 25 + 4011RRoom temperature (During
Control)
▪ x1 ºC
2
(IU – 1) * 25 + 4011(IU – 1) * 25 + 4012RRoom temperature (Remote
Controller)
▪ x1 ºC
2
(IU – 1) * 25 + 4012(IU – 1) * 25 + 4013RIndoor suction temperature (TA)
▪ x1 ºC
1
(IU – 1) * 25 + 4013(IU – 1) * 25 + 4014RIndoor fan coil temperature (TCJ)
▪ x1 ºC
1
(IU – 1) * 25 + 4014(IU – 1) * 25 + 4015RIndoor fan coil temperature
(TC2)
▪ x1 ºC
1
(IU – 1) * 25 + 4015(IU – 1) * 25 + 4016RIndoor fan coil temperature
(TC1)
▪ x1 ºC
1
(IU – 1) * 25 + 4016(IU – 1) * 25 + 4017RIndoor discharge temperature
(TF)
▪ x1 ºC
▪ Only for VRF systems
0
(IU – 1) * 25 + 4017(IU – 1) * 25 + 4018RRevolutions indoor fan
▪ RPS
▪ Only for RAV systems
0
(IU – 1) * 25 + 4018(IU – 1) * 25 + 4019RIndoor PMV opening
▪ x1, x10 Pulses
▪ Only for VRF systems
1
(IU – 1) * 25 + 4019(IU – 1) * 25 + 4020RRunning hours indoor fan
▪ x100 hours
▪ Only for RAV systems
0
(IU – 1) * 25 + 4020(IU – 1) * 25 + 4021RTime filtersign
▪ Hours
▪ Only for RAV systems
0
(IU – 1) * 25 + 4021(IU – 1) * 25 + 4022REstimated supply air temperature
▪ x1 ºC
▪ Only for RAV systems
0

4.3.2 Advanced registers for Outdoor Unit Status on VRF-SMMSi Systems

These registers are only available when the indoor unit’s type selected on SW1 is different from the default value. Please, check section 4.4 for more information.

Register Address
(protocol address)
Register Address
(PLC address)
R/WDescriptionPriority
42004201ROutdoor Unit duty
▪ 15
1
Register Address
(Protocol address)
Register Address
(PLC address)
R/WDescriptionPriority
42104211RHigh-pressure sensor detention
pressure (Pd)
▪ X100 Mpa
2
42114212RLow-pressure sensor detention
pressure (Ps)
▪ X100 Mpa
2
42124213RCompressor  1 discharge temperature  (Td1)
▪ x1 ºC
2
42134214RCompressor  2 discharge  temperature (Td2)  ▪ x1 ºC2
42144215RCompressor
3 discharge
temperature (Td3)
▪ x1 ºC
2
42154216RSuction temperature (TS)
▪ x1 ºC
2
42164217ROutdoor fan coil temperature 1
(TE1)
▪ x1 ºC
2
42174218ROutdoor fan coil temperature 2(TE2)
▪ x1 ºC
1
42184219RTemperature at liquid side (TL)
▪ x1 ºC
2
42194220ROutside ambient temperature
(TO)
▪ x1 ºC
1
42204221RPMV1 + 2 opening
▪ x1 Pulse
2
42214222RPMV4 opening
▪ x1 Pulse
2
42224223RCompressor 1 current (I1)
▪ x10 A
1
42234224RCompressor 2 current (I2)
▪ x10 A
2
42244225RCompressor 3 current (I3)
▪ x10 A
2
42254226ROutdoor fan current (Ifan)
▪ x10 A
2
42264227RCompressor 1 revolutions
▪ x10 RPS
2
42274228RCompressor 2 revolutions
▪ x10 RPS
2
42284229RCompressor 3 revolutions
▪ x10 RPS
2
42294230ROutdoor fan mode
▪ x1 mode
2
42304231RCompressor IPDU 1 heat sink
temperature
▪ x1 ºC
2
42314232RCompressor IPDU 2 heat sink
temperature
▪ x1 ºC
2
42324233RCompressor IPDU 3 heat sink
temperature
▪ x1 ºC
2
42334234ROutdoor fan IPDU heat sink
temperature
▪ x1 ºC
2
42344235RHeating/cooling
recovery
controlled ∗5
▪ 0: Normal
▪ 1: Recovery controlled
2
42354236RPressure release ∗5
▪ 0: Normal
▪ 1: Recovery controlled
2
42364237RDischarge temperature release ∗5
▪ 0: Normal
▪ 1: Recovery controlled
2
42374238RFollower unit release (U2/U2/U4outdoor units) ∗5
▪ 0: Normal
▪ 1: Recovery controlled
2
42384239ROutdoor unit horsepower
▪ x1 HP
0

4.3.3 Advanced registers for Outdoor Unit Status on VRF-SHRM/SMMS Systems

These registers are only available when the indoor unit’s type selected on SW1 is different from the default value. Please, check section 4.4 for more information

Register Address
(protocol address)
Register Address
(PLC address)
R/WDescriptionPriority
42004201ROutdoor Unit duty

▪ 15

1
42104211RTdl-Compressor 1 Discharge Temp.

▪ x1 ºC

2
42114212RTd2-Compressor 2 Discharge Temp.

▪ x1 ºC

2
42124213RPd – High Pressure Sensor

▪ Mpa

2
42134214RPS – Low Pressure Sensor

▪ Mpa

2
42144215RTS – Suction Temp.

▪ x1 ºC

2
42154216RTE – Outdoor Heat Exchanger Temp.

▪ x1 ºC

2
42164217RTL – Liquid Temp.

▪ x1 ºC

2
42174218RTO – Outside ambient temperature

▪ x1 ºC

1
42184219RTU – Low Pressure Saturated Temp.

▪ x1 ºC

2
Register Address
(protocol address)
Register Address
(PLC address)
R/WDescriptionPriority
42194220RCompressor 1 Current
▪ A
1
42204211RCompressor 2 Current
▪ A
2
42214222RPMV1 + 2 Opening
▪ 0..100
2
42234224RCompressor 1, 2
▪ 0: Off
▪ 1: On
2
42244225ROutdoor Fan Mode
▪ 0..31
2
42254226ROutdoor Unit Size
▪ HP
2

4.3.4 Advanced registers for Outdoor Unit Status on RAV Systems

These registers are only available when the indoor unit’s type selected on SW1 is different from the default value. Please, check section 4.4 for more information

Register Address
(protocol address)
Register Address
(PLC address)
R/WDescriptionPriority
44004401ROutdoor Unit duty

▪ 0..15

1
44104411RTE temperature (evaporator)

▪ x1 ºC

2
44114412RTO temperature outdoor

▪ x1 ºC

1
44124413RCompressor              discharge

temperature

▪ x1 ºC

2
44134414RSuction temperature TS

x1 ºC

2
44144415RTemperature thyristor THS

▪ x1 ºC

0
44154416RCompressor current

▪ A

1
44164417RTemperature at liquid side TL

▪ x1 ºC

2
44174418RCompreRpsssor revolutions

▪ RPS

2
44184419RRevolutions lowest Fan

▪ RPS

0
44194420RRevolutions upper Fan

▪ RPS

0
44204221RRunning hours compressor

▪ x100 hours

2

4.3.5 Advanced registers for Indoor Unit Type and Refresh Time adjustment

Register Address
(protocol address)
Register Address
(PLC address)
R/WDescriptionPriority
44504451RIndoor Unit Type
▪ 0: Not defined (extra signals
disabled)
▪ 1: RAV
▪ 2: VRF (SMMSi)
▪ 3: VRF (SHRM/SMMS)
0
44514452R/WRefresh Time Adjust
▪ 1..4

This parameter indicates the cadence when reading priority signals. Priorities are defined as follows and can’t be modified:

0: Update on start-up

  1. High priority
  2. Low priority

The higher the value, the fastest the priority signals are going to update. The cadence is defined by:

  • One high priority signal and one low priority signal’s poll.
  • Two high-priority signals and one low-priority signal’s poll.
  • Three high-priority signals and one low-priority signal’s poll.
  • Four high-priority signals and one low-priority signal’s poll.

4.3.6 Considerations on Temperature Registers

  • AC unit temperature setpoint (R/W)
    (register 4 – in Protocol address / register 5 – in PLC address):
    This is the adjustable temperature setpoint value that must be required by the user.
    This register can be read (Modbus function 3 or 4) or written (Modbus functions 6 or 16). A remote controller connected to the Toshiba indoor unit will report the same temperature setpoint value as this register.
  • AC unit temperature reference (R)
    (register 5 – in Protocol address / register 6 – in PLC address):
  • This register reports the temperature that is currently used by the Toshiba indoor unit as the reference of its own control loop.
    If the value on the register 22 is valid (different from 0x8000), it will report the value from this register. If not, it will show the indoor unit reference temperature.
    It is a read-only register (Modbus functions 3 or 4).
    Depending on the mode selected, the register shows a different value:
    Heat Mode:
    Temperature reference = Ambient temperature +0.50C
    Dry Mode / Fan Mode / Cool mode:
    Temperature reference = Ambient temperature -0.50C
    When the mode changes from Heat to anyone else, or from anyone else to Heat, the register updates the value using the intervals +0.5°C/-0.5°C
  • AC unit external temperature reference (Modbus) (R/W)
    (register 22 – in Protocol address / register 23 – in PLC address):
    This register reports the temperature from an external sensor in the Modbus side. If valid value is received, the Modbus register will indicate a 0x8000 value.
    This register can be read (Modbus function 3 or 4) or written (Modbus functions 6 or 16).
  • AC Real temperature setpoint (R)
    (register 23 – In Protocol address / register 24 – in PLC address):
    This register will show the same value as in register 4 (protocol address). The reference temperature from the remote controller is sent directly to the AC unit to be applied in the control loop.
    It is a read-only register (Modbus functions 3 or 4).
    Moreover, notice that temperature’s values of all these four registers are expressed according to the temperature´s format configured through its onboard DIP-Switches (See “4.4 -DIP-switch Configuration Interface”). The following formats are possible:• Celsius value: Value in Modbus register is the temperature value in Celsius (i.e. a value “22” in the Modbus register must be interpreted as 22ºC)
    • Decicelsius value: Value in Modbus register is the temperature value in decicelsius (i.e. a value “220” in the Modbus register must be interpreted as 22.0ºC)
    • Fahrenheit value: Value in Modbus register is the temperature value in Fahrenheit (i.e. a value “72” in the Modbus register must be interpreted as 72ºF (~22ºC).

4.4 DIP-switch Configuration Interface

All the configuration values on INMBSTOS001R000 can be written and read from Modbus interface. Otherwise, some of them can also be setup from its on-board DIP-switch interface. The device has DIP-switches SW1, SW3 and SW4 on the following locations:
Intesis Modbus RTU Interface for Toshiba Air Conditioners - DIP-switch Configuration

The following tables apply to the interface´s configuration through DIP-switches:
SW1 – AC indoor unit’s features

Intesis Modbus RTU Interface for Toshiba Air AC indoor unit’s features

Table 4.1 SW1: AC indoor unit´s features

SW3/SW4 – Baud rate configuration
Intesis Modbus RTU Interface for Toshiba Air Conditioners -Baud rate configuration

Table 4.2 SW3-SW4: Modbus baud rate

SW4 – Degrees/Decidegrees (x10), temperature magnitude (ºC/ºF), and EIA-485 termination resistor.Intesis Modbus RTU Interface for Toshiba Air Conditioners - DIP-switch temperature

Table 4.3 SW4: Temperature and termination resistor configuration

SW3 – Modbus Slave addressIntesis Modbus RTU Interface for Toshiba Air Modbus Slave address

Table 4.4 SW3: Modbus slave address

4.5 Implemented Functions

INMBSTOS001R000 implements the following standard Modbus functions:

▪ 3: Read Holding Registers
▪ 4: Read Input Registers
▪ 6: Write Single Register
▪ 16: Write Multiple Registers (Despite this function is allowed, the interface does not allow to write operations on more than 1 register with the same request, this means that the length field should always be 1 when this function is being used in case of writing)

4.6 Device LED indicator

The device includes two LED indicators to show all the possible operational states. In the following table there are written the indicators which can be performed and their meaning.

L1 (green LED)

Device status

LED indication        ON / OFF Period 

       Description

During not normal operationLED blinking500ms ON / 500ms OFFCommunication error
During normal operationLED flashing100ms ON / 1900ms OFFNormal operation (configured and working properly)

L2 (red LED)

Device statusLED indicationON / OFF PeriodDescription
During not normal operationLED Pulse3sec ON / — OFFUnder voltage

L1 (green LED) & L2 (red LED)

Device statuED indication   ON / OFF Period Description
During normal operationLED Pulse5sec ON / — OFFDevice Start-up
During not normal operationLED alternatively blinking500ms ON / 500ms OFFEEPROM failure

4.7 EIA-485 bus. Termination resistors and Fail-Safe Biasing mechanism

EIA-485 bus requires a 120Ω terminator resistor at each end of the bus to avoid signal reflections.

In order to prevent fail status detected by the receivers, which are “listening” the bus, when all the transmitters’ outputs are in three-state (high impedance), it is also required a fail-safe biasing mechanism. This mechanism provides a safe status (a correct voltage level) in the bus when all the transmitters’ outputs are in three-state. This mechanism must be supplied by the Modbus Master.

The INMBSTOS001R000 device includes an onboard terminator resistor of 120Ω that can be connected to the EIA-485 bus by using DIP-switch SW4. Some Modbus RTU EIA-485 Master devices can provide also an internal 120Ω terminator resistor and/or fail-safe biasing mechanism (Check the technical documentation of the Master device connected to the EIA-485 network in each case).

EnclosurePlastic, type PC (UL 94 V-0)
Net dimensions (dxwxh):
93 x 53 x 58 mm / 3.7” x 2.1” x 2.3”
Color: Light Grey. RAL 7035
Operation
Temperature
0ºC to +60ºC
Weight85 g.Stock
Temperature
-20ºC to +85ºC
MountingWall
DIN rail EN60715 TH35.
Operational
Humidity
<95% RH, non-condensing
Terminal Wiring (for low-voltage signals)For terminal: solid wires or stranded wires (twisted or with ferrule)
1 core: 0.5mm 2 … 2.5mm 2
2 cores: 0.5mm 2 … 1.5mm 2
3 cores: not permitted
Stock Humidity<95% RH, non-condensing
Modbus RTU port1 x Serial EIA485 Plug-in screw terminal block (2 poles):
A, B
Compatible with Modbus RTU EIA-485 networks
Isolation voltage1500 VDC
AC unit port1 x AB bus Plug-in screw terminal block
(2 poles):
A, B
Compatible with Toshiba networks
Isolation
resistance
1000 MΩ
Switch 1 (SW1)1 x DIP-Switch for AC featuresProtectionIP20 (IEC60529)
Switch 3 (SW3)1 x DIP-Switch for Modbus RTU settingsLED indicators2 x Onboard LED – Operational status
Switch 4 (SW4)1 x DIP-Switch for extra functions

Intesis Modbus RTU Interface for Toshiba Air Conditioners - Electrical

List of supported AC Unit Types.

A list of Toshiba indoor unit model references compatible with INMBSTOS001R000 and their available features can be found in:
intesis_inxxxtos001rx00_compatibility-list [PDF]

Error Codes

Error
Code
Decimal
Error
Code
Hex
Error In
Remote
Controller
Error categoryError Description
00N/AINMBSTOS001R000No active error
3321CO1Central Controller IssuesDuplicated setting of control address
3422CO2Central control number of units mis-matched
3523CO3Incorrect wiring of central control
3624C04Incorrect connection of central control System Controller fault, error in transmitting comms signal, i/door or o/door unit not working, wiring fault
3725CO5
3826C06System Controller fault, error in receiving comms signal, i/door or o/door unit not working, wiring fault, CN1 not connected correctly
442CC12Batch alarm by local controller
4830C16Transmission error from adaptor to unit
4931C17Reception error to adaptor from unit
5032C18Duplicate central address in adaptor
5133C19Duplicate adaptor address
5234C20Mix of PAC & GHP type units on adaptor
5335C21Memory fault in adaptor
5436C22Incorrect address setting in adaptor
5537C23Host terminal software failure
5638C24Host terminal hardware failure
5739C25Host terminal processing failure
583AC26Host terminal communication failure
603CC28Reception error of S-DDC from host terminal
613DC29Initialization failure of S-DDC
633FC31Configuration change detected by adaptor
6541E01Addressing and Communication
Problems
Remote control detecting error from indoor unit, Address not set/Auto address failed. Check interconnecting wiring etc. Re-address system.
6642E02Remote detecting error from indoor unit,
6743E03Indoor unit detecting error from remote,
6844E04Indoor seeing error from outdoor. Qty of i/d units connected are less than qty set. Check; all i/d units are ON, reset turn off all units wait 5min power up
6945E05Indoor unit detecting error from outdoor unit, Error in sending comms signal
7046E06Outdoor unit detecting error from indoor unit, Error in receiving comms signal
7147E07Outdoor unit detecting error from indoor unit, Error in sending comms signal
7248E08Incorrect setting indoor/controller, Indoor address duplicated
7349E09Incorrect setting indoor/controller, Remote address duplicated or IR wireless controller not disabled
744AEl0Indoor unit detecting error from ‘option’ plug, Error in sending comms signal
754BEllIndoor unit detecting error from ‘option’ plug, Error in receiving comms signal
764CE12Auto addressing failed, Auto address connector CN100 shorted during auto addressing
774DE13Indoor unit failed to send signal to remote
784EE14Setting Failure, Duplication of master indoor units
794FE15Auto addressing failed, Number of indoor units connected are less than number set
8050E16Auto addressing failed, Number of indoor units connected are more than number set
8151E17Addressing and
Communication
Problems
Group control wiring error, Main indoor unit not sending signal for sub indoor units
8252E18Group control wiring error, Main indoor unit not receiving signal for sub indoor units
8353E19Outdoor header units quantity error
8454E20Auto addressing failed, No indoor units connected
8757E23Sending error in communication between outdoor units
8858E24Auto addressing failed, Error on sub outdoor unit
8959E25Auto addressing failed, Error on outdoor unit address setting
905AE26Auto addressing failed, Quantity of main and sub outdoor units do not correspond to the number set on main outdoor unit P.C.B.
925CE28Follower outdoor unit error
93SDE29Auto addressing failed, Sub outdoor unit not receiving comms for main outdoor unit
955FE31Between units, Comms failure with MDC, does E31 remain after power is re-instated? If so replace PCB. & power PCB
9761F01Sensor FaultsIndoor Heat Exch inlet temp sensor failure (El)
9862F02Indoor Heat Exch freeze temp sensor failure (E2)
9963F03Indoor Heat Exch outlet temp sensor failure (E3)
10064F04Outdoor Discharge temp sensor failure (TD) or (DISCHI)
10165F05Outdoor Discharge temp sensor failure (DISCH2)
10266F06Outdoor Heat Exch temp sensor failure (C1) or (EXG1)
10367F07Outdoor Heat Exch temp sensor failure (C2) or (EXL1)
10468F08Outdoor Air temp sensor failure (TO)
1066AFIOIndoor inlet temp sensor failure
10768F11Indoor outlet temp sensor failure
1086CF12Outdoor Intake sensor failure (TS)
1096DF13GHP – Cooling water temperature sensor failure
1116FF15Outdoor temp. sensor misconnection (TE1,TL)
11270F16Outdoor High pressure sensor failure
11371F17GHP – Cooling water temperature sensor fault
11472F18GHP – Exhaust gas temperature sensor fault
11674F20GHP Clutch coil temperature fault
11977F23Outdoor Heat Exch temp sensor failure (EXG2)
12078F24Outdoor Heat Exch temp sensor failure (EXL2)
1257DF29Indoor EEPROM error
1267EF30Clock Function (RTC) fault
1277FF31Outdoor EEPROM error
12981H01Compressor IssuesCompressor Fault, Over current (Compl)
13082H02Compressor Fault, Locked rota current detected (Comp1)
13183H03Compressor Fault, No current detected (Compl)
13284H04Comp-1 case thermo operation
13385H05Compressor Fault, Discharge temp not detected (Compl)
13486H06Compressor Fault, Low Pressure trip
13587H07Compressor Fault, Low oil level
13688H08Compressor Fault, Oil sensor Fault (Compl)
13988H11Compressor Fault, Over current (Comp2)
1408CH12Compressor Fault, Locked rota current detected (Comp2)
1418DH13Compressor Fault, No current detected (Comp2)
1428EH14Comp-2 case thermo operation
1438FH15Compressor Fault, Discharge temp not detected (Comp2)
14490H16Oil level detection circuit error / Magnet switch error /Overcurrent relay error
14995H21Compressor Fault, Over current (Comp3)
150961122Compressor Fault, Locked rota current detected (c.3)
15197H23Compressor IssuesCompressor Fault, No current detected (Comp3)
15399H25Compressor Fault, Discharge temp not detected (Comp3)
15598H27Compressor Fault, Oil sensor fault (Comp2)
1569CH28Compressor Fault. Oil sensor (connection failure)
1599FH31Compressor Fault. IPM trip (IMP current on temperature)
193CILO1Incorrect SettingsSetting Error, Indoor unit group setting error
194C2L02Setting Error, Indoor/outdoor unit type/model miss-matched
195C3L03Duplication of main indoor unit address in group control
196C4L04Duplication of outdoor unit system address
197C5LO52 or more controllers have been set as ‘priority’ in one system – shown on controllers set as ‘priority’
198C6L062 or more controllers have been set as ‘priority’ in one system – shown on controllers not set as ‘priority’
199C7LO7Group wiring connected on and individual indoor unit
200C8LOSIndoor unit address/group not set
201C9L09Indoor unit capacity code not set
202CAL10Outdoor unit capacity code not set
203CBL11Group control wiring incorrect
205CDL13Indoor unit type setting error, capacity
207CFL15Indoor unit paring fault
208DOL16Water heat exch. unit setting failure
209D1L17Miss-match of outdoor unit with different refrigerant
210D2L184-way valve failure
211D3L19Water heat exch. unit duplicated address
212D4L20Duplicated central control addresses
213D5L21Gas type setup failure
220DC1_28Maximum number of outdoor units exceeded
221DDL29No. of IPDU error
222DEL30Auxiliary interlock in indoor unit
223DFL31IC error
225ElP01Indoor Unit ProblemsIndoor unit fault, Fan motor thermal overload
226E2P02Outdoor unit fault, Compressor motor thermal overload, over or under voltage
227E3P03Outdoor unit fault, Compressor discharge temperature too high (Comp’) over 111 0C. Low on ref gas, exp. valve, pipework damage.
228E4PO4Outdoor unit fault, High pressure trip
229E5P05Outdoor unit fault, Open phase on power supply. Check power on each phase, inverter PCB, control PCB
231E7P07Heat sink overheat error
233E9P09Indoor unit fault, Ceiling panel incorrectly wired
234EAP10Indoor unit fault, Condensate float switch opened
235EBP11GHP – Water Heat exch. low temp (frost protection) fault
236ECP12Indoor unit fault, Fan DC motor fault
237EDP13Outdoor liquid back detection error
238EEP14Input from leak detector (If fitted)
239EFP15Refrigerant loss, high discharge temp and EEV wide open and low compressor current draw.
240FOP16Outdoor unit fault, Open phase on compressor power supply
241FlP17Outdoor unit fault, Compressor discharge temperature too high (Comp2) over 1110C. Low on ref gas, exp. valve, pipework damage.
242F2P18Outdoor unit fault, By-pass valve failure
243F3P19Outdoor unit fault, 4 way valve failure, i/door
temp rises in cooling or fills in heating. Check
wiring, coil, PCB output, valve operation.
Ref gas, high temp/pressure fault, heat exch. temp high C2, 55-60 0C, cooling over-load, sensor fault.
244F4P20Outdoor unit fan motor fault, fan blade jammed, check connections, does fan turn freely, motor resistance 30-40ohm on each pair, no fan fault, yes PCB fault.
246F6P22Outdoor unit fault, Compressor overcurrent – check winding resistance, Inverter failure – check internal resistance term HIC + & – to UVW 200-300Kohm or more
250FAP26Outdoor unit fault, Inverter circuit fault –
252FCP29Motor-current Detection Circuit (MDC) fault, check comp windings, sensors Cl & TS, if ok possible PCB failure
253FDP30Indoor unit fault, System controller detected fault on sub indoor unit
255FFP31Simultaneous operation multi control fault, Group controller fault
65535 (1)N/AINMBSTOSOO1R000Error in the communication of INMBSTOS001R000 with the AC unit

In case to detect an error code not listed, contact your closest Toshiba technical support service.

© HMS Industrial Networks S.L.U. – All rights reserved This information is subject to change without notice
URL https://www.intesis.com

Documents / Resources

Intesis Modbus RTU Interface for Toshiba Air Conditioners [pdf] User Manual
Intesis, EIA-485

References

Leave a comment

Your email address will not be published. Required fields are marked *