Cheta na: This information supplements the nameplate markings affixed to the product and the LCP200 instruction manual (D104296X012), available from your Emerson sales office or Fisher.com Always refer to the nameplate itself to identify the appropriate certification. LCP200 instruments with an IIC rating may have different hardware than IIB-rated instruments; be sure to order the appropriately rated instrument based on your application and wiring practices.
ỊDỌ AKA NA NTỊ: Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion, or area re‐classification.
Nchekwa n'ime ime
Ọnọdụ ojiji akọwapụtara
- Install the unit in the area of low risk from mechanical hazards. To prevent the risk of electrostatic sparking, the non-metallic surface shall be cleaned with a damp akwa.
Notes
Ambient temperature rating: -40C ≤ Ta ≤ +65°C
- Install per drawing GG55194, shown in Figures 1, 2, 3, and 4, as indicated on the nameplate.
- Nnọchi nke ngwa nwere ike imebi nchekwa dị n'ime.
- The enclosure contains non-metallic enclosure parts. To prevent the risk of electrostatic sparking, the non-metallic surface shall be cleaned with a damp akwa.
- Refer to table 1 for approval information.
Table 1. Approval Information, ATEX/IECEx
Akwụkwọ | Asambodo Enwetara | Ngosipụta akụrụngwa | okpomọkụ Usoro |
ATEX IECEx |
ATEX: FM17ATEX0071X II 1 GD IECEx: IECEx FMG 17.0028X
Intrinsically Safe Gas Ex ia IIC Ga Dust Ex ia IIIC Da Install Per Drawing GG55194 (shown in figure 1, 2, 3, and 4) |
Per Drawing GG55194 (shown in figure 1, 2, 3, and 4) |
Gas: T6 Dust: T85 C |
Figure 1. Intrinsically Safe, LOOP Power, ATEX/IECEx
- Wiring Configuration A (LOOP-Powered only) From Barrier to Digital Valve Controller and LCP200 See Notes in figure 3 and Notes 1, 2, 3, 4, and 5 in Figure 4.
Figure 2. Intrinsically Safe, External Power 24V, ATEX/IECEx
- Wiring Configuration B (External 24V Only) From Barrier to Digital Valve Controller and LCP200 See Notes in figure 3 and Notes 1, 2, 4, and 5 in Figure 4.
Figure 3. Notes
THE INTRINSIC SAFETY ENTITY CONCEPT ALLOWS THE INTERCONNECTION OF TWO APPROVED INTRINSICALLY SAFE DEVICES, WITH ENTITY PARAMETERS NOT SPECIFICALLY EXAMINED IN COMBINATION AS A SYSTEM WHEN: Uo Ui, Io
Ii, Co
Ci + Cable, Lo
Li + Liable, Po
Pi. DUST-TIGHT SEAL MUST BE USED WHEN INSTALLED IN DUST-PROTECTED ENVIRONMENTS. EACH CONNECTION BETWEEN THE LCP200 AND THE ASSOCIATED INTRINSICALLY SAFE APPARATUS SHALL BE SEPARATELY SHIELDED FROM THE OTHER CONNECTIONS. WHEN CALCULATING THE ENTITY COMBINATIONS THAT INCLUDE THE DVC6000/DVC6200, THE SUMMATION OF THE Ci + Cable AS WELL AS THE Li + Lcable FOR THE DVC6000/DVC6200 AND THE LCP200 SHALL BE USED. ASSOCIATED APPARATUS MANUFACTURERS’ INSTALLATION DRAWINGS MUST BE FOLLOWED WHEN INSTALLING THIS EQUIPMENT.
Figure 4. Notes
Refer to Notes 1, 2, 3, 4, and 5 for Figure 1. Intrinsically Safe, LOOP Power, ATEX/IECEx Wiring Configuration A (LOOP-Powered only) From Barrier to Digital Valve Controller and LCP200 Refer to Notes 1, 2, 4, and 5 for Figure 2. Intrinsically Safe, External Power 24V, ATEX/IECEx Wiring Configuration B (External 24V Only) From Barrier to Digital Valve Controller and LCP200.
ndetu
- FOR Ex ia APPLICATIONS THE FOLLOWING INFORMATION SHALL BE OBSERVED:
- THE OVERALL GAS GROUP RATING OF THE INTRINSICALLY SAFE CIRCUIT WILL BE THE LOWEST GAS GROUPING OF ALL APPARATUS FORMING) THE CIRCUIT. FOR EXAMPLE, A CIRCUIT WITH BOTH IIB AND IIC APPARATUS WILL HAVE AN OVERALL CIRCUIT GAS GROUP RATING OF IIB.
- THE LEVEL OF PROTECTION OF THE INTRINSICALLY SAFE CIRCUIT WILL BE THE LOWEST LEVEL OF ALL APPARATUS FORMING THE CIRCUIT. FOR EXAMPLE, A CIRCUIT WITH BOTH “ia” AND “ib” WILL HAVE AN OVERALL PROTECTION LEVEL OF “ib”.
- THE LOWEST PERMISSIBLE INPUT VOLTAGE (Ui), INPUT CURRENT (Ii), AND INPUT POWER (Pi) OF EACH APPARATUS SHALL BE GREATER THAN OR EQUAL TO THE OUTPUT VOLTAGE (Uo), OUTPUT CURRENT (Io), AND OUTPUT POWER (Po) OF THE ASSOCIATED APPARATUS (BARRIER). THE SUM OF THE MAX UNPROTECTED CAPACITANCE (Ci) AND MAX UNPROTECTED INDUCTANCE (Li), INCLUDING THE INTERCONNECTED CABLING CAPACITANCE (Cable) AND CABLING INDUCTANCE (Liable), MUST BE LESS THAN THE ALLOWABLE CAPACITANCE (Ca) AND INDUCTANCE (La) DEFINED BY THE ASSOCIATED APPARATUS. IF THE ABOVE CRITERIA ARE MET THAN THE COMBINATION MAY BE CONNECTED.
- INSTALLATION OF THE LCP200 IS SUCH THAT ITS LOOP TERMINALS WILL BE CONNECTED IN PARALLEL WITH OTHER INTRINSICALLY SAFE APPARATUS LOOP TERMINALS. THE WIRING COMING FROM THE BARRIER INTO THE HAZARDOUS LOCATION MAY BE TERMINATED AT EITHER THE INTRINSICALLY SAFE APPARATUS, OR AT THE LCP200.
- Oke mpaghara nchekwa VOLTAGE MUST NOT EXCEED 250 VRMS
- THE ENCLOSURE CONTAINS NON-METALLIC ENCLOSURE PARTS. TO PREVENT THE RISK OF ELECTROSTATIC SPARKING, THE NON-METALLIC SURFACE SHALL BE CLEANED WITH A DAMP UWU.
Figure 5. LCP200 ATEX/IECEx Nameplate, Intrinsically Safe
Mgbawa gbawara
Ọnọdụ ojiji akọwapụtara
- The enclosure contains non-metallic enclosure parts. To prevent the risk of electrostatic sparking, the non-metallic surface shall be cleaned with a damp akwa.
- The flameproof joints of the equipment are not intended to be repaired. Consult the manufacturer if repair of the joints is necessary.
- The electronics compartment rear cover is assembled and torqued at the factory and is not to be removed by the end user.
- Consult the manufacturer for genuine replacement terminal cover fasteners. The fasteners are 316 stainless steel, bolt class A4-70, sized M6 x 1 mm x 15 mm.
Notes
Ambient temperature rating: -40C ≤ Ta ≤ +65°C
- Install unit in the area of low risk from mechanical hazards.
- Install per drawing GG55194, shown in Figures 6, 7, and 8, as indicated on the nameplate.
- Nnọchi nke ngwa nwere ike imebi nchekwa dị n'ime.
- Refer to table 2 for approval information.
Table 2. Approval Information, ATEX/IECEx
Akwụkwọ | Asambodo Enwetara | Mbanye Ndokwa | okpomọkụ Usoro |
ATEX IECEx |
ATEX: FM21ATEX0024X IECEx: IECEx FMG 21.0016X
Ex eb ia mb IIC T6 Gb Ex ta IIIC T85°C Da Ex db ia IIB T6 Gb Ex db ia IIC T6 Gb Install Per Drawing GG55194 (shown in figure 6, 7, and 8) |
Per Drawing GG55194 (shown in figure 6, 7, and 8) |
Gas: T6 Dust: T85 C |
Figure 6. Explosion-proof, LOOP Power, ATEX/IECEx
- Wiring Configuration A (LOOP-Powered only) See Figure 8 Notes
Figure 7. Explosion-proof, External Power 24V, ATEX/IECEx
- Wiring Configuration B (External 24V Only) See Figure 8 Notes
Figure 8. Notes
kwuru, sị: ASSOCIATED APPARATUS MANUFACTURER’S INSTALLATION DRAWING MUST BE FOLLOWED WHEN INSTALLING THIS EQUIPMENT.
- EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE CANADIAN ELECTRIC CODE, PART 1 OR NEC NFPA AND ANSI/ISA RP12.06.01.
- THE ENCLOSURE CONTAINS NON-METALLIC ENCLOSURE PARTS TO PREVENT THE RISK OF ELECTROSTATIC SPARKING. THE NON-METALLIC SURFACE SHALL BE CLEANED WITH A DAMP UWU.
- DUST-TIGHT CONDUIT SEAL MUST BE INSTALLED WITHIN 18” WHEN INSTALLED IN CLASS II AND CLASS III ENVIRONMENTS.
- THE NAMEPLATE IS PROVIDED WITH BOXES THAT THE END USER/INSTALLER MUST CHECK OR ETCH FOR THE PROTECTION METHOD USED ACCORDING TO THE INSTALLATION.
- NKWUTA: USE FASTENERS WITH YIELD STRESS
450MPa.
- THE END USER SHALL CLOSE ANY UNUSED ENTRIES WITH SUITABLY CERTIFIED BLANKING ELEMENTS.
- FOR ZONES APPLICATIONS, CONNECTION OF THE INTERNAL GROUND IS REQUIRED AS CONNECTION OF THE EXTERNAL GROUP IS OPTIONAL.
Figure 9. LCP200 ATEX/IECEx Nameplate, Explosion-proof, Group IIC
Figure 10. LCP200 ATEX/IECEx Nameplate, Explosion-proof, Group IIB
Emerson, Emerson Automation Solutions, ma ọ bụ nke ọ bụla n'ime ha nwere mmekọ na-eburu ibu ọrụ maka nhọrọ, ojiji ma ọ bụ ndozi nke ngwaahịa ọ bụla. Ibu ọrụ maka nhọpụta kwesịrị ekwesị, ojiji, na mmezi nke ngwaahịa ọ bụla ka ga-abụrịrị onye zụrụ na onye njedebe ikpeazụ.
Fisher is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
Edere ọdịnaya nke akwụkwọ a naanị maka ebumnuche ozi, yana ebe ọ bụ na emerela mbọ niile iji hụ na ha ziri ezi, ekwesighi ịkọwa ha dị ka ikike ma ọ bụ nkwa, kwupụta ma ọ bụ gosipụta, gbasara ngwaahịa ma ọ bụ ọrụ ndị akọwapụtara ebe a ma ọ bụ iji ha eme ihe ma ọ bụ itinye n'ọrụ. Ahịa niile na-achịkwa usoro na ọnọdụ anyị, nke dị na arịrịọ. Anyị debere ikike ịgbanwe ma ọ bụ melite atụmatụ ma ọ bụ nkọwa nke ụdị ngwaahịa a n'oge ọ bụla na-enweghị ọkwa.
Emerson akpaaka Solutions
- Okwu: Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 France Dubai, United Arab Emirates Singapore 128461 Singapore
- www.ịja.ik
2018, 2021 Fisher Controls International LLC. Ikike niile echekwabara.
Akwụkwọ / akụrụngwa
![]() |
EMERSON LCP200 Local Control Panel [pdf] Akwụkwọ ntuziaka LCP200 Local Control Panel, LCP200, Local Control Panel, Control Panel, Panel |
![]() |
EMERSON LCP200 Local Control Panel [pdf] Akwụkwọ ntuziaka LCP200 Local Control Panel, LCP200, Local Control Panel, Control Panel |