Honeywell - LOGOEVS-INT50W
internal Amplifier
Product Installation Document

Description

The EVS-INT50W Internal Amplifier is used to amplify the audio message for distribution throughout the facility for the Emergency Voice System.
The EVS-INT50W Internal Amplifier can fit inside the 5820XL-EVS or 6820EVS cabinets.
1.1 Compatibility
The EVS-INT50W is compatible with the following Silent Knight Series FACPs. For more information, refer to the FACP Installation Manual or the EVS Series Manual (PN:LS10062-001SK-E).

  • 6820EVS
  • 5820XL-EVS

1.2 Specifications

  • Standby Current: 52mA
  • EVS-INT50W only Alarm Current @ 25V: 275mA; @ 70V: 310mA
  • Full Alarm load current @ 25V: 2840mA; @ 70V: 2900mA

Board Layout

Honeywell EVS-INT50W Internal Amplifier

Installation

NOTE: Installation and wiring of this device must be done in accordance with NFPA 72 and local ordinances.
To mount the , refer to the following steps.

  1. Remove AC power and disconnect backup batteries from the main control panel.
  2. To mount the EVS-INT50W inside the FACP cabinet below the main board (above the batteries), align the board with the mounting holes and secure the board to the enclosure with the eight supplied screws.

Wiring

4.1 FACP Wiring

See Figure 2 to properly wire the to the FACP. The Internal Amplifier must be powered by a NAC programmed as Constant Auxiliary Power. Refer to the FACP Installation Manual.Honeywell EVS-INT50W Internal Amplifier - Wiring the Tto the FACP

4.2 VBUS Wiring
The VBUS is an analog voice bus that carries the recorded voice messages from the EVS-VCM to the EVS-INT50W amplifiers, or the voice messages generated from a system microphone to the EVS-INT50W.
The maximum resistance on the VBUS is 20W.
Connect the VBUS from the EVS-VCM to the EVS-INT50W amplifiers as shown in Figure 3.Honeywell EVS-INT50W Internal Amplifier - VBUS Wiring

Setting the Device Address

Use the onboard DIP switches to select an ID number for the EVS-INT50W. Refer to Figure 4 to see how to set the DIP switches for the desired ID number. Once the ID number is set, add the EVS-INT50W to the system through panel programming. Note that Address 0 is an invalid number and cannot be used.
NOTE: The EVS-INT50W is powered by a NAC on the FACP or by an auxiliary power supply. It will not be found using JumpStart AutoProgramming.Honeywell EVS-INT50W Internal Amplifier - DIP Switch Settings

Speaker Wiring

Each EVS-INT50W supplies one circuit for speaker connection. The speaker circuit can be supervised and wired for Class B or Class A. The speaker circuit is capable of 50 watts of power at 25 Vrms or 70.7 Vrms. Refer to the Silent Knight Device Compatibility Document P/N LS10167-004SK for compatible speakers.

Number Of SpeakersTotal LoadWire Distance in Feet
@ ½ W@1WVrmsWatts18 AWG16 AWG14 AWG12 AWG
10525Vrms5W39006200986015680
70Vrms250003970063200100520
201025Vrms10W2125338053758540
70Vrms15200241503840061100
301525Vrms15W1460232036905870
70Vrms11000175002780044200
402025Vrms20W1100175027804420
70Vrms8500135102150034175
522625Vrms26W760120019203050
70Vrms610097001540024520
804025Vrms40W55087513902200
70Vrms410065001036016480
1005025Vrms50W45071511301800
70Vrms35005560885014070

Table 1 Wire Lengths
NOTE: The above table assumes a uniform distribution of the speakers, and that a max of 20% voltage drop on the last speaker is allowed.
Figure 5 illustrates how to wire speakers to the control panel using Class B or Class A supervision.Honeywell EVS-INT50W Internal Amplifier - Speaker Configurations

Honeywell Silent Knight
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161
www.silentknight.com
LS10120-001SK-E | D | 02/22
©2022 Honeywell International Inc.

Documents / Resources

Honeywell EVS-INT50W Internal Amplifier [pdf] Instruction Manual
EVS-INT50W Internal Amplifier, EVS-INT50W, Internal Amplifier, Amplifier

References

Leave a comment

Your email address will not be published. Required fields are marked *