Honeywell Connect Balancing App User Guide

Connect Balancing App

Product Information

Specifications:

  • Designed for Variable Air Volume (VAV) balancing
  • Integrated Bluetooth technology for easy access
  • Utilizes Bluetooth Low Energy (BLE) for connection
  • Compatible with BACnetTM network
  • Range: 20-30 meters for BLE connection

Product Usage Instructions:

1. Connect to VAV Controllers:

To access the functions of VAV controllers, follow these
steps:

  1. The configured device name will be displayed in the list of BLE
    devices.
  2. The list is organized based on signal strength, with the
    strongest signals at the top.

Note: Ensure the Mobile Device and the
controller are within the BLE range (20-30 meters). Only the first
21 characters of the Device name will be displayed due to BLE
advertisement character limitation.

2. Single Controller Balancing:

To balance a single controller:

  • Select ‘Balance This Controller’ option.
  • If the controller is already balanced, you can choose to clear
    before rebalancing.
  • Non-Alerton controllers support 2 calibration types – Flow
    Calibration factor (default 1) & Manufacturer K factor.

3. Multiple Controller Balancing:

To balance multiple controllers:

  • Filter properties to display unbalanced, balanced, zeroed
    controllers, or those that are not zeroed.
  • Select ‘Multiple Controllers’ and perform operations on
    selected controllers.

4. View Controller:

To view or update controller properties and settings:

  • Choose ‘View Controller’ option.
  • View or update the controller by following operations.

5. Move Damper Operation:

Adjust the position of VAV dampers for airflow
redistribution:

  • ‘Move Damper by Airflow’: Command/set damper to a specific
    target airflow.
  • ‘Move Damper by Position’: Set the damper to a specific
    position based on a percentage.

6. Zero Calibration:

Ensure accuracy and efficiency of VAV controller operations by
managing calibrations and settings effectively through Zero
Calibration option.

Frequently Asked Questions (FAQ):

Q: What is the range for Bluetooth Low Energy (BLE)
connection?

A: The BLE connection range is 20-30 meters. Ensure the mobile
device and controller are within this range for proper
connectivity.

Q: How can I view or update controller properties?

A: Select ‘View Controller’ option in the app to access and
modify controller properties and settings accordingly.

“`

CONNECT MOBILE APP
QUICK START GUIDE

Quick Start Guide
Table of Contents
Connect Mobile App……………………………………………………………………………………………………………………………………………………………….3 System Overview……………………………………………………………………………………………………………………………………………………………………..4 Connect To VAV Controllers…………………………………………………………………………………………………………………………………………………5 Single Controller Balancing…………………………………………………………………………………………………………………………………………………6 Multiple Controller Balancing…………………………………………………………………………………………………………………………………………….7 View Controller …………………………………………………………………………………………………………………………………………………………………………8 Move Damper Operation………………………………………………………………………………………………………………………………………………………9 Zero Calibration …………………………………………………………………………………………………………………………………………………………………….10 Clear Zero And Balance, Resume To Normal………………………………………………………………………………………………………………11 Generate Report……………………………………………………………………………………………………………………………………………………………………12 View Report……………………………………………………………………………………………………………………………………………………………………………..13 Alerton Standard Applications – Point Mapping ……………………………………………………………………………………………………….14
Connect Mobile App | www.honeywell.com 2

Quick Start Guide
Connect Mobile App
The application is designed specifically for Variable Air Volume (VAV) balancing, offering users streamlined access to the IP VAV controller through integrated Bluetooth technology. By utilizing Bluetooth Low Energy (BLE), the app enables a straightforward connection to the controller and facilitates the discovery of other controllers within the same BACnetTM network, as the Bluetooth-enabled controller serves as a router to this network.
Air Balancing Connect Mobile App
· Users can connect to the controller via Bluetooth. · Single and Multi Controller balancing capabilities. · Precise calibration of zero velocity cutoff. · Manual calibration for accurate VAV operation. · Adjust damper settings for position and airflow. · Resume normal operation and clear adjustments. · Generate shareable reports for improved efficiency and documentation in VAV
system management.
Connect Mobile App | www.honeywell.com 3

Quick Start Guide
System Overview
1 Configure the Controller

2 Connect via BLE

3 Balance the Controller

4 Generate Report

Connect Mobile App | www.honeywell.com 4

Quick Start Guide
Connect To VAV Controllers
Connect the mobile device to VAV controllers to access their functions. 1. The configured device name will be displayed in the list of BLE devices. 2. The list is organized based on signal strength, with the strongest signals at the
top.
Note: Ensure the Mobile Device and the controller are within the BLE range (20-30 meters). Due to BLE advertisement character limitation, only the first 21 characters of Device name will be displayed in the list.
Connect Mobile App | www.honeywell.com 5

Quick Start Guide
Single Controller Balancing
This Method refers to the process of calibrating and adjusting the airflow for one specific VAV controller. This method is typically used when a precise adjustment is needed for individual units. · Select Controller · Connect to Controller · Enter Parameters · Start Balancing · Review Results
Select Balance This Controller option.
Note: If controller is already balanced, you can choose to clear before rebalancing. Non-Alerton controllers support 2 calibration types – Flow Calibration factor (default 1) & Manufacturer K factor.
Connect Mobile App | www.honeywell.com 6

Quick Start Guide
Multiple Controller Balancing
This Method allows users to adjust and calibrate several VAV controllers simultaneously. This feature is efficient for operations requiring mass updates or inspections. Maximum 5 devices are supported for multi-controller balancing. · Select Controllers · Input Common Parameters · Initiate the Balancing Process · Monitoring Progress · Review Results for Each Controller
Filter Properties: : Displays only the
unbalanced controllers. : Displays only the
balanced controllers. : Displays only the
zeroed controllers. : Displays only the
controllers which are not zeroed.
Select Multiple Controllers
Select Go To Tasks and perform the operations on the selected controllers. For more details refer to Clear Zero And Balance, Resume To Normal.
Connect Mobile App | www.honeywell.com 7

Quick Start Guide
View Controller
Choose `View Controller’ option to view or update controller properties and settings.
Select View Controller option and view or update the controller by following operations:
· Balance: Fine-tune airflow for effective system performance.
· Move: Manually reposition dampers for optimization.
· Properties: View Controller Properties.
· Fan: Control Fan settings during balancing.
· Heat: Control Heat settings during balancing.
Connect Mobile App | www.honeywell.com 8

Quick Start Guide
Move Damper Operation
Move Damper Operation is a feature that allows users to adjust the position of VAV (Variable Air Volume) dampers. This helps in redistributing airflow within a duct system, which is crucial for optimizing HVAC system performance and ensuring effective climate control.
Move Damper by Airflow: This Allows users to command/set damper to a specific target airflow. Move Damper by Position: This allows the user to set the damper to a specific position based on a percentage.
Connect Mobile App | www.honeywell.com 9

Quick Start Guide
Zero Calibration
Zero Calibration option is critical for maintaining the accuracy and efficiency of VAV controller operations, allowing users to manage calibrations and settings effectively.

ZERO to physically close the damper and adjust the Zero velocity cut off %.
MOVE FOR BALANCING screen directly.

Connect Mobile App | www.honeywell.com 10

Quick Start Guide
Clear Zero And Balance, Resume To Normal
Perform resume to normal, clear zero or balancing options for one or more controllers.
Resume to Normal: It will clear any overrides performed during balancing process.
Clear Zero and Balance: It clears both zero cut off velocity and balancing – calibration factor.
Clear Zero: It clears the zero cut off velocity.
Connect Mobile App | www.honeywell.com 11

Quick Start Guide
Generate Report
Generate a report by selecting the controllers you want to include. A .csv file will be generated and stored locally in your app.
Give a Name and Description to your report.
Note: Controller connectivity is needed only to generate the report. However, once generated, the reports can be accessed from the Hamburger menu at any time, even without needing to connect to the controller.
Connect Mobile App | www.honeywell.com 12

Quick Start Guide
View Report
The report will include Balancing status at controller levels, allowing you to Share it with your team.
Connect Mobile App | www.honeywell.com 13

Alerton Standard Applications – Point Mapping
Refer to the BACnet points used in Alerton Standard applications during the balancing process.

Point Mapping
PROPERTY
K -Factor Drive Time Max Setpoint Min Setpoint Airflow Fan Speed Command Fan Command Reheat/Fan Setpoint Lock Damper Box Size Heating Valve Command Velocity Cutoff (%) Damper Position Force To Max Setpoint Force To Min Setpoint Force Damper To Open Force Damper To Close Force To Reheat Setpoint

AV/BV POINT
AV 252 AV 64 AV 67 AV 68 AI 10 AV 174 BV 193 AV 66 BV 16 AV 250 AV 172 AV 251 AV 9 BV 11 BV 9 BV 13 BV 12 BV 10

Note: Please refer to the Controller IOG documentation for guidance on using custom objects for balancing.

By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.

Honeywell Building Automation
715 Peachtree Street, N.E., Atlanta, Georgia, 30308, United States. https://hwll.co/BuildingControlSolutions

@U.S. Registered Trademark © 2025 Honeywell International Inc. 31-00839-01 | Rev. 08-25