Honeywell Home T6590A Fan-Coil Controller Installation Guide
Honeywell Home T6590A Fan-Coil Controller

Installation

Installation Inductions
Installation Inductions
Installation Inductions

Wiring

Application 0: Two Pipes, Heating only

Wiring Inductions

Application 1: Two Pipes, Cooling only

Wiring Inductions

Application 2: Two pipes, Heating or Cooling, Manual changeover

Wiring Inductions

Application 3: Two pipes, Heating or Cooling, Auto changeover

Wiring Inductions

Application 4, 5 & 7 (T6590B ONLY / SEULEMENT T6590B / T6590B SOLTANTO / SOLO T6590B): Four pipes, Heating & Cooling, Manual or Auto changeover

Wiring Inductions

Application 6 (T6590B ONLY / SEULEMENT T6590B / T6590B SOLTANTO / SOLO T6590B) : Two pipes, Heating or Cooling with Auxiliary electric heater

Wiring Inductions

Applications

T6590A (2 Pipe Model)

Application

DescriptionChangeoverFan speedRemote sensorPipe sensorRemote setbackAuxiliary HeaterOutput type
02 pipe system, heating onlyON/OFF, 1/2/3, AUTO

ON, OFF

1

2 pipe system, cooling onlyON/OFF, 1/2/3, AUTOON, OFF

2

2 pipe system, 1 stage heat or 1 stage coolManualON/OFF, 1/2/3, AUTO

ON, OFF

3

2 pipe system, 1 stage heat or 1 stage cool, auto changeoverSeasonal ChangeoverON/OFF, 1/2/3, AUTO

ON, OFF

T6590B (4 Pipe Mode)

Application

DescriptionChangeoverFan speedRemote sensorPipe sensorRemote setbackAuxiliary Heater

Output type

0

2 pipe system, heating onlyON/OFF, 1/2/3, AUTOON, OFF
12 pipe system, cooling onlyON/OFF, 1/2/3, AUTO

ON, OFF

2

2 pipe system, 1 stage heat or 1 stagecoolManualON/OFF, 1/2/3, AUTOON, OFF
32 pipe system, 1 stage heat or 1 stage cool, auto changeoverSeasonal Changeover

 

ON/OFF, 1/2/3, AUTO

ON, OFF

4

4 pipe system 1 stage heat and 1 stage coolManualON/OFF, 1/2/3, AUTO

ON, OFF

5

4 pipe system 1 stage heat and 1 stage cool auto changeoverAuto changeoverON/OFF, 1/2/3, AUTOON, OFF
62 pipe system, 1 stage heat or 1 stage cool with auxiliary electric heaterManual with seasonal changeoverON/OFF, 1/2/3, AUTO

ON, OFF

7

4 pipe system, mixed manual and autoManual / Auto changeoverON/OFF, 1/2/3, AUTO

ON, OFF

Installer Setup Mode

The T6590 is delivered with a set of pre-configured operational values that will allow the device to function immediately. However, in order to make the device compatible with a specific system, some of the internal settings may need to be changed. For information on the default values and the configurable options, please refer to the “Installer Parameter Table”.

  1. To enter the Installer Setup Mode, press the (Icons) and Icons buttons together for 3 seconds.
    Installer Setup Mode
  2. To index between the individual Parameters, use the (Icons) button. It is only possible to move upwards through the parameters.
    Installer Setup Mode
  3. To change a selected parameter, use the Icons or Icons button.
    Installer Setup Mode
  4. To save the altered settings, exit the Installer Setup Mode by Pressing the (Icons) and Icons buttons together for 3 seconds. NB: If the Installer Setup Mode is exited by time-out (approximately 120 seconds), then the newly changed values will not be saved.
    Installer Setup Mode

Installer Parameters Table

Parameter NoParameterSetting
1System Type0 = 2 Pipe system Heat Only
1 = 2 Pipe system Cool Only
2 = 2 Pipe system 1H1C manual changeove
3 = 2 Pipe system 1H1C auto changeover (default on T6590A)
4 = 4 pipe system with manual changeover (not available on T6590A)
5 = 4 Pipe system auto changeover (default on T6590B
6 = 2 pipe system 1H1C with Auxiliary Heater. Manual changeover
7 = 4 pipe system, mixed manual and automatic changeover (not available on T6590A)
2Valve output type0 = NO* ON/OFF (Default)
1 = NC** ON/OFF
3Sensor Type0 = Onboard Sensor (Default)
1 = Remote Sensor
4Pipe sensor (Note: This item will be automatically populated based on Parameter No.2)0 = NO* input (Default = Heat
1 = NO* input (Default = Cool)
2 = NC** input (Default = Heat)
3 = NC** input (Default = Cool)
4 = Analogue input (Default) (NTC20K, T7414C1012)
5Threshold for pipe sensor cooling10 – 18°C (Default)
6Threshold for pipe sensor heating24 – 32°C (Default)
7Fan control type

Fan stops in deadband

0 = Cycle or Constant (Default) (3 speed: Low->Med->High->Auto-> Low)
1 = Constant only (3 speed: Low->Med->High-> Low)
8Dead band for four pipes1 – 5°C (Default = 2°C) (not available on T6590A)
9Cycles Per Hour (CPH) value for heating1 – 12 CPH (Default)
10Cycles Per Hour (CPH) value for cooling1 – 6 CPH (Default)
11Cycles Per Hour(CPH) value for Auxiliary Heater1 – 12 CPH (Default)
12Display Temperature adjustment-2 to +2°C (Default)
13Temperature Display mode0 = Room Temperature only
1 = Setpoint only
2 = Room Temperature and Setpoint (Default)
14Heating setpoint Range Stops10 – 32°C (Default)
15Cooling setpoint Range Stops10 – 32°C (Default)
16Keypad Lockout0 = All keys available (Default)
1 = System button Locked out
2 = Fan and System button Locked out
3 = All buttons locked out
17Remote setback1 = Hotel card NO*, with 1 second software delay going from Unoccupied to Occupied; 2 minute delay going from Occupied to Unoccupied
2 = Hotel card NC**, with 1 second software delay going from Unoccupied to Occupied; 2 minute delay going from Occupied to Unoccupied
3 = Hotel Card enabled, NO*, with 1 second software delay going from Unoccupied to Occupied; 30 minute delay going from Occupied to Unoccupied
4 = Hotel Card enabled, NC**, with 1 second software delay going from Unoccupied to Occupied; 30 minute delay going from Occupied to Unoccupied
18Remote setback heating setpoint10 – 21°C (Default)
19Remote setback cooling setpoint22 – 32°C (Default)
20Activity Sensing (If no key is pressed after a certain period which is configured in this item, the system will enter Unoccupied mode)0 = Disabled (Default)
1 = 4 Hour Sensing
2 = 12 Hour Sensing
3 = 24 Hour Sensing. NB: Anytime the thermostat is not touched (no single key pressed), the thermostat will automatically fall back into Unoccupied setpoints. When any key is pressed, thermostat controls to occupied mode
21Freeze Protection0 = Disabled (Default)
211 = Enabled – Thermostat Cycles On Heat when room temperature reaches 4°C and disables Heat when room temperature reaches below 8°C. This feature can not activate if the application is cool only
22Auto Fan Reset1 = Reset back to Auto after 2 hours (Not allowed when constant fan is selected in Parameter No.7). The start time is calculated after the initial call for heat
2 = Reset back to Auto after 4 hours (Not allowed when constant fan is selected in Parameter No.7). The start time is calculated after the initial call for heat/cool
23Fan run-on time after auxiliary heater is switched off0 – 600 Sec. (Default)

Support

resideo logo
www.resideo.com

Ademco 1 GmbH
Hardhofweg 40
74821 Mosbach
Phone: +49 1801 466 388
info.de@resideo.com
homecomfort.resideo.com

@2020 Resideo Technologies, Inc. All rights reserved. The Honeywell Home trademark is used under license from Honeywell International Inc. This product is manufactured by Resideo Technologies, Inc and its affiliates.