Instructions for WEINTEK models including: A173UH, A2A, A2U, A2AS, A2USH, A3U, Mitsubishi A173UH PLC Connection Via Ethernet Tutorial, Mitsubishi, A173UH PLC Connection Via Ethernet Tutorial, Connection Via Ethernet Tutorial, Via Ethernet Tutorial, Ethernet Tutorial

PLC Connection Guide

Nina

Mitsubishi A173UH/A2A/A2U/A2AS/A2USH/A3U

Weintek, драйверы контроллеров ПЛК PLC совместимых с Weintek

[PDF] Mitsubishi A173UH/A2A/A2U/A2AS/A2USH/A3U

RS422 25P. D-Sub Male. Rx. TX. TX . 2 RX . Tx. RX. RX . 3 TX . GND. GND. DTR . 4 DSR . RTS. CTS. GND. 7 GND. CTS. RTS. TX-. 15 RX-. RX-. 16 TX-. DTR-. 17 DSR-.


File Info : application/pdf, 4 Pages, 125.97KB

PDF preview unavailable. Download the PDF instead.

Mitsubishi A173UH A2A A2U A2AS A2USH A3U
PLC Connection Guide
Mitsubishi A173UH/A2A/A2U/A2AS/A2USH/A3U
Supported Series: Mitsubishi A173UH,A2A,A2U,A2AS,A2USH,A3U Website: http://www.mitsubishi-automation.com/

HMI Setting:

Parameters Recommended

Options

PLC type

Mitsubishi A173UH/A2A/A2U/A2AS/A2USH/A3U

PLC I/F

RS232

Baud rate

9600

Data bits

8

Parity

Odd

Stop bits

1

PLC sta. no. 0

File register 0

0 ~ 8

Device type A2A / A2U

A2A/A2U/A2AS/A2USH/ A173UH/A3U

*Note: Parameter -> Memory capacity -> File register

Notes *Note

Device Address:

Bit/Word B B B B B W W W W W

Device type X Y M B F TV CV D W R

Format HHHH HHHH DDDD HHHH DDDDD DDD DDD DDDD HHHH DDDDD

PLC Connection Guide

Range 0 ~ 270f 0 ~ 270f 0 ~ 9999 0 ~ ffff 0 ~ 65535 0 ~ 2047 0 ~ 1023 0 ~ 9999 0 ~ ffff 0 ~ 65535

Memo Input Relay Output Relay Auxiliary Relay
Timer Memory Counter Memory Data Register

Pass-through:
When the PC reboots or virtual com port is reinstalled, it needs to be re-initialized for pass-through.

Wiring Diagram:

PLC Connection Guide

Use the RS422 to RS232 PLC programming cable (shown as follows)

MITSUBISHI AnS CPU

Note: Due to hardware limitations, this PLC is not supported by HMI models without RTS/CTS.

Diagram 1

PLC Connection Guide

RS-232

The serial port pin assignments may vary between HMI models, please click the following

link for more information.

HMI

PLC

Link

PLC Programming Converter

RS422 25P D-Sub Male

Rx

TX

TX+

2 RX+

Tx

RX

RX+

3 TX+

GND

GND

DTR+

4 DSR+

RTS

CTS

GND

7 GND

CTS

RTS

TX-

15 RX-

RX-

16 TX-

DTR-

17 DSR-

Diagram 2
cMT-G01, cMT-G02, cMT-SVR-100/200, cMT-FHDX-820, cMT-SVRX-820 connection diagram

HMI

PLC

Link
RS485-4W

A Series PLC CPU 25 pin

8 TX+ 9 TX6 RX+ 7 RX1 Data+ 4 Data5 GND

2 RX+ 15 RX3 TX+ 16 TX4 CTS+ 17 CTS7GND 20 21 Short

