LENNOX V0CTRL86P-3 VRF BACnet Gateway

Cov ntaub ntawv tseem ceeb
Phau ntawv no yuav tsum tau nrog tus tswv rau yav tom ntej siv
Cov npe khoom siv
Pob 1 ntawm 1 muaj xws li:
1 - BACnet rooj vag
1 - DIN rail
1 – Phau ntawv qhia thiab daim ntawv thov
General
Lennox VRF, Mini-VRF thiab Mini-Split BACnet Gateway tso cai rau kev sib txuas ntawm cov kab ke mus rau lub tsev tswj hwm (BMS) siv BACnet raws tu qauv. Kev teeb tsa tuaj yeem ua tiav los ntawm kev siv a web browser thiab PC nrog lub network chaw nres nkoj.
Kev teeb tsa tsis raug, kev hloov kho, hloov kho, kev pabcuam lossis kev saib xyuas tuaj yeem ua rau muaj kev puas tsuaj rau cov khoom, tus neeg mob lossis lub neej poob. Kev teeb tsa thiab kev pabcuam yuav tsum tau ua los ntawm ib tus kws tshaj lij HVAC installer lossis sib npaug, lub koomhaum pabcuam, lossis tus xa khoom roj.
Tsis txhob siv cov khoom siv tes ntub dej.
Ua ntej sim ua ib qho kev pabcuam lossis kev saib xyuas, tig lub zog hluav taws xob mus rau chav tsev OFF ntawm kev hloov pauv.
Tsis txhob nruab cov cuab yeej nyob rau hauv cov cheeb tsam uas hnyav roj, vapor, los yog gases uas muaj leej faj los yog tus maub los yuav puas.
Cov cuab yeej siv huv huv, damp daim ntaub. Tsis txhob tsuag tshuaj ntxuav rau ntawm lossis ib ncig ntawm lub cuab yeej.
Cov lus qhia no yog npaj los ua cov lus qhia dav dav thiab tsis txhob hloov cov lej hauv zos hauv txhua txoj kev. Tham nrog cov tub ceev xwm uas muaj kev txiav txim siab ua ntej kev teeb tsa. Nyeem tag nrho cov ntaub ntawv hauv phau ntawv no ua ntej siv cov cuab yeej no.
Kev teeb tsa Network
Muaj Ethernet interface hauv lub cuab yeej (Eth0). Lub Hoobkas teeb tsa cov khoom siv chaw nyob yog 192.168.1.8.
Kev ruaj ntseg
Default Admin Tus Neeg Siv Lub Npe: admin
Default Admin Password: 123456
Specifications
| Muaj nuj nqi | Kev piav qhia |
| Input Supply Lub Zog | 24 VAC ua |
| Kev sib txuas BACnet | BACnet/IP |
| I/O | 4 chaw nres nkoj 485 interface |
| Kev khiav hauj lwm qhov kub thiab txias | 32 ° F ~ 104 ° F (0 ° C ~ 40 ° C) |
| Kev khiav hauj lwm Humidity Range (Rh) | 25% ~ 90% |
| Qhov ntev | 10-1/2" X 10" X 2-3/8" (26 cm X 25 cm X 6 cm) |
| DIN Mounted | |
Lub V0CTRL86P-3 Lennox BACnet rooj vag tuaj yeem saib xyuas thiab tswj txog 320 VRB & VPB VRF systems nrog txog 960 VRF sab nraum zoov thiab 2560 VRF sab hauv tsev. Saib Daim Ntawv Ntxiv A.
Tag nrho Lennox VRF P3 sab nraum zoov thiab sab hauv tsev tuaj yeem txuas nrog V0CTRL86P-3 Lennox BACnet rooj vag.
Saib LVM thiab BACnet Gateway installation manual (507897) rau cov lus qhia rau cov ncauj lus kom ntxaws txog kev sib txuas.
Kev sib txuas ntawm qhov system
Qhov chaw nyob BACnet yog tus lej plaub tus lej uas qhia txog BACnet lub rooj vag tsheb npav (chaw nres nkoj), hom chav tsev (tsev nyob sab hauv lossis sab nraum zoov) thiab chav tsev nyob. Device ID = XXXX
| X | X | X | X | |
| BACnet Bus (Port) Number | Chav tsev hom | Chav Nyob | ||
| (0-3) XIV | 0 | Chav nyob sab hauv | (Tshooj 0-63)
(Tshooj Sab Nraud 0-31) |
|
| 1 | Sab nraum zoov | |||
Example – 0001 qhia BACnet ntaus ntawv tooj 0, chav tsev nyob sab hauv tsev, chav nyob sab hauv tsev naj npawb 01.
Txuas ncaj qha nrog PC los ntawm PC network chaw nres nkoj mus rau lub rooj vag Ethernet kev twb kev txuas - Configure PC network chaw nres nkoj nrog rau cov chaw tsim nyog thiab siv ib tug web browser txuas - nkag mus rau tus IP chaw nyob 192.168.1.8 thiab koj yuav raug ceeb toom kom nkag mus rau lub npe / tus password. ib zaug txuas koj yuav pom cov kev xaiv rau teeb tsa Gateway nyob ntawm koj lub bacnet network. Thaum txuas nrog koj yuav pom cov kev xaiv rau kev teeb tsa Gateway kom nyob ntawm koj lub bacnet network.
Tus neeg siv lub npe = admin
Tus neeg siv Password = 123456

| Yam khoom | Cov ntawv luv |
| Cov Lus Qhia Kev Koom Tes | AI |
| Analog tso zis | AO |
| Tus nqi analog | AV |
| Binary Input | BI |
| Binary tso zis | BO |
| Binary Tus Nqi | BV |
| Multi-state Input | MI |
| Multi-state Output | MO |
| Ntau lub xeev tus nqi | MV |
BACnet Object Points List
| Khoom ID | Yam khoom npe | Tus nqi | R/W | Kev piav qhia |
| TIAB SA 1 | On/Off Teeb | “0-OFF 1-ON” |
R/W | Chav tsev nyob sab hauv ON / OFF teeb tsa |
| MV 1 | Kev teeb tsa hom | “1-OFF 2-Xov xwm 3-Txias 4-Cua sov 5-Auto 6-Dry” |
R/W | Kev teeb tsa chav nyob sab hauv tsev |
| MV 2 | Ntxuam Ceev Teeb | “1/2-Low 3/4-Medium 5/6/7-High 8-Auto 9-OFF” |
R/W | Sab hauv tsev kiv cua ceev teeb tsa |
| AV 1 | Kev ntsuas kub | 62 ~ 86F (17 ~ 30C) | R/W | Chav nyob sab hauv tsev teeb tsa rau cua txias, cua sov thiab hom qhuav |
| AV 2 | Dual Point (Txias) Teeb | 62 ~ 86F (17 ~ 30C) | R/W | Nyob sab hauv tsev nws pib hom cua txias qhov chaw teeb tsa |
| AV 3 | Dual Point (Heating) Kev teeb tsa | 62 ~ 86F (17 ~ 30C) | R/W | Nyob sab hauv tsev nws pib hom cua sov qhov chaw teeb tsa |
| AV 4 | Txias Temperature Limit Setting | 62 ~ 86F (17 ~ 30C) | R/W | Chav tsev nyob sab hauv qis qis qis ntawm qhov cua txias, nws pib txias thiab qhuav setpoint |
| AV 5 | Tshav kub qhov txwv qhov chaw | 62 ~ 86F (17 ~ 30C) | R/W | Chav tsev nyob sab hauv qhov txwv ntawm cua sov thiab nws pib cua sov setpoint |
| MV 3 | Hom txwv qhov chaw | “0-Xauv
1-Xauv rau hauv hom txias 2-Xauv hauv hom cua sov" |
R/W | Sab hauv chav tsev hom xauv / xauv qhov chaw |
| MV 5 | Ntxuam Xauv / Xauv Chaw | “1/2-Xauv hauv qis ceev 3/4-Xauv hauv nruab nrab ceev 5/6/7-Xauv hauv kev kub ceev\ 8-Xauv” |
R/W | Sab hauv tsev kiv cua ceev xauv / xauv qhov chaw |
| TIAB SA 4 | Chaw taws teeb tswj xauv chaw | “0-Xauv 1-Wireless tswj xauv " |
R/W | Wireless controller xauv / xauv qhov chaw |
| TIAB SA 5 | Controller Xauv Chaw | “0-Xauv 1-Wired tswj xauv " |
R/W | Wired maub los xauv / xauv qhov chaw |
| IB 1 | Chav ntsuas kub | Tus nqi tiag tiag | R | Nyob sab hauv tsev chav tsev kub sensor tus nqi |
| IB 2 | Tswb Indication | "0-Tsis muaj malfunction code 1-Malfunciton code" | R | Yog hais tias muaj qhov yuam kev code rau chav tsev sab hauv |
| AWM 7 | Cov cuab yeej tso tawm yuam kev thiab cov lus piav qhia sib txuas | 95 | FE Tsis muaj chaw nyob | R | Sab hauv chav tsev yuam kev code |
| 61 | E0 Hom kev tsis sib haum xeeb | ||||
| 62 | E1 Kev sib txuas lus yuam kev ntawm chav tsev sab hauv thiab sab nraum zoov | ||||
| 63 | E2 T1 (Room kub sensor) malfunction | ||||
| 64 | E3 T2 (nruab nrab ntawm evaporator sensor) ua haujlwm tsis zoo | ||||
| 65 | E4 T2B (Qhov hluav taws xob ntawm evaporator sensor) ua haujlwm tsis zoo | ||||
| 66 | E5 T2A (Inlet ntawm evaporator sensor) malfunction | ||||
| 67 | E6 DC kiv cua yuam kev | ||||
| 68 | E7 EEPROM tsis ua haujlwm | ||||
| 72 | Eb EXV malfunction | ||||
| 74 | Ed Outdoor Unit Fault | ||||
| 75 | EE Lub tswb dej siab | ||||
| 1 | A0 Emergency nres | ||||
| IB 9 | EXV Qhib | Tus nqi tiag tiag | R | Indoor unit EEV qhib | |
| IB 10 | Software Version | Tus nqi tiag tiag | R | Sab hauv tsev software version | |
| IB 11 | Hom sab hauv tsev | “1-(V33B) Plaub-txoj kev cassette 2-(VWMB)Wall mounted 3-(VMDB) Nruab nrab zoo li qub siab duct 5-(VVCB)Vertical air handler 6-(VHIB) High static pressure duct 7-(V22B)Compact plaub-txoj kev cassette 8-(VCFB)Ceiling/Floor 11-(VOSB)Dedicated sab nraum cua duct 14-(VOWA)One way cassette 21-AHU tswj cov khoom siv " |
R | Sab hauv chav tsev series npe | |
| IB 12 | Sab Hauv Tsev Muaj Peev Xwm | “8-7Kbtu/h 10-9Kbtu/h 12-12Kbtu/h 17-15Kbtu/h 20-18Kbtu/h 25-24Kbtu/h 32-30Kbtu/h 40-36Kbtu/h 50-48Kbtu/h 60-54Kbtu/h 65-60Kbtu/h 80-72Kbtu/h
100-96 Kbtu / h |
R | Sab hauv chav tsev muaj peev xwm | |
Outdoor Units Points List
| Khoom ID | Yam khoom npe | Tus nqi | R/W | Kev piav qhia |
| SIB 1 | Hom xwm txheej |
|
R | Sab nraum zoov chav ua haujlwm hom xwm txheej. |
| IB 1 | On/Off Status | “0-OFF 1-ON” |
R | Sab nraum chav tsev ON/OFF raws li txoj cai |
| IB 1 | Ambient Kub | Tus nqi tiag tiag | R | Sab nraum chav tsev ambient kub |
| IB 2 | Compressor 1 zaus. | Tus nqi tiag tiag | R | Sab nraum chav tsev lub ntsiab compressor zaus (Hz) |
| IB 3 | Compressor 2 zaus. | Tus nqi tiag tiag | R | Chav tsev sab nraum zoov sub compressor zaus (Hz) |
| IB 4 | Compressor 1 Discharge Temp. | Tus nqi tiag tiag | R | Sab nraum chav tsev lub ntsiab compressor tawm kub |
| IB 5 | Compressor 2 Discharge Temp. | Tus nqi tiag tiag | R | Sab nraum zoov chav tsev sub compressor tawm kub |
| IB 6 | Siab Siab | Tus nqi tiag tiag | R | Sab nraum chav tsev tso tawm siab (psi) |
| IB 7 | Tsawg Siab | Tus nqi tiag tiag | R | Sab nraum chav tsev suction siab (psi) |
| IB 9 | Ntxuam 1 Ceev | Tus nqi tiag tiag | R | Sab nraum zoov chav ntxuam-1 ceev kauj ruam, tsis yog qhov tseeb RPM |
| AWM 8 | Cov cuab yeej tso tawm yuam kev thiab cov lus piav qhia sib txuas | 61 | E0 Kev sib txuas lus yuam kev ntawm chav nyob sab nraum zoov | R | Sab nraum chav tsev yuam kev code | |
| 62 | E1 Fais fab theem poob yuam kev | |||||
| 63 | E2 Kev sib txuas lus yuam kev ntawm chav tsev sab hauv thiab sab nraum zoov | |||||
| 65 | E4 Sab nraum zoov ambient kub sensor (T4 / T10) thiab condenser yeeb nkab kub sensor (T3A / T3B) yuam kev | |||||
| 66 | E5 Voltage yuam kev | |||||
| 67 | E6 Inverter module kub sensor yuam kev | |||||
| 68 | E7 Discharge temp sensor yuam kev | |||||
| 69 | E8 Incorrect ENC 1 Main
- Sub Configuration |
|||||
| 70 | E9 Compressor tsav tsheb yuam kev | |||||
| 101 | H0 Kev sib txuas lus yuam kev ntawm lub ntsiab tswj nti thiab inverter tsav nti | |||||
| 103 | H2 Muaj nuj nqis ntawm chav nyob sab nraum zoov txo qis | |||||
| 104 | H3 Ntau chav nyob sab nraum zoov tau nce | |||||
| 105 | H4 Compressor inverter module tiv thaiv tshwm peb zaug hauv 60 feeb, X stands rau coj module | |||||
| 106 | H5 Tsis tshua muaj siab tiv thaiv xauv tawm (P2 3X hauv 60 feeb) | |||||
| 107 | H6 Compressor Discharge Temperature Protection (P4 3X hauv 100 feeb) | |||||
| 108 | H7 Tus naj npawb ntawm chav tsev sab hauv poob qis | |||||
| 109 | H8 Kev kub siab sensor yuam kev | |||||
| 110 | H9 DC Ntxuam Module Tiv Thaiv (P9 10X hauv 120 feeb) | |||||
| 112 | Hb Tsis tshua muaj siab sensor yuam kev | |||||
| 114 | Hd Sub ODU yuam kev (Y yuav yog 1 lossis 2, sawv rau sub 1 lossis sub 2 ODU) | |||||
| 48 | C7 Inverter Module Temperature Protection (1PL / 2PL 3X hauv 100
feeb) |
||||
| 82 | F1 PTC ntawm lim board yuam kev | ||||
| 84 | F3 Sab nraum zoov chav tsev Subcooler Qhov hluav taws xob kub sensor yuam kev | ||||
| 86 | F5 Sab nraum zoov chav tsev Subcooler Inlet Kub Sensor yuam kev | ||||
| 87 | F6 EEV A/B/C yuam kev (Y yuav yog 1, 2 lossis 3, sawv cev rau A, B, C) | ||||
| 90 | F9 Kev sib txuas lus yuam kev ntawm cov khoom siv cua txias qis (LAC cov khoom siv) thiab PCB sab nraum zoov | ||||
| 182 | P1 Kev Tiv Thaiv Kev Kub Siab, CI / CO = 4.4 / 3.2 Mpa lossis 638 / 464 psig | ||||
| 183 | P2 Kev Tiv Thaiv Tsis Txaus Siab, CI/CO =.05/.15 Mpa lossis 7.25/21.8 psig | ||||
| 184 | P3 Kev tiv thaiv tam sim no ntawm inverter compressor | ||||
| 185 | P4 Compressor tso tawm temp tiv thaiv, CI / CO = 120/90 ° C los yog 248/194 ° F | ||||
| 186 | P5 Condenser kub tiv thaiv, CI / CO = 65/55 ° C lossis 149/131 ° F | ||||
| 190 | P9 Ntxuam module tiv thaiv | ||||
| 198 | PL Kub tiv thaiv ntawm inverter module, CI / CO = 80/60 ° C los yog 176/140 ° F | ||||
| IB 10 | Ntxuam 2 Ceev | Tus nqi tiag tiag | R | Sab nraum zoov chav ntxuam-2 ceev kauj ruam, tsis yog qhov tseeb RPM | |
| IB 2 | Tswb Indication | "0-Tsis muaj malfunction code 1-Malfunciton code" | R | Yog tias muaj qhov yuam kev cai rau chav nyob sab nraum zoov. | |
| IB 11 | T3 | Qhov kub thiab txias | R | Sab nraum zoov sab laug condenser kub | |
| IB 12 | t3 ib | Qhov kub thiab txias | R | Sab nraum zoov txoj cai condenser kub | |
| IB 4 | SIB 2 | “0-OFF
1-ON” |
R | Sab nraum zoov SV2 (Solenoid valve) xwm txheej |
| IB 6 | SIB 4 | “0-OFF
1-ON” |
R | Sab nraum zoov SV4 (Solenoid valve) xwm txheej |
| IB 11 | SIB 1 | "0-Tsis muaj zog 1-Energized" | R | Sab nraum zoov ST1 (Rov qab valve) xwm txheej |
| IB 12 | SIB 2 | "0-Tsis muaj zog 1-Energized" | R | Sab nraum zoov ST2 (Rov qab valve) xwm txheej |
| IB 13 | Version | Tus nqi tiag tiag | R | Sab nraum zoov chav tsev tseem ceeb PCB software version |
| IB 14 | Sab nraum zoov hom | "0-Mini VRF 1-VRF" | R | Sab nraum zoov chav tsev hom |
| IB 15 | Sab nraum zoov nees | Tus nqi tiag tiag | R | Sab nraum zoov chav tsev muaj peev xwm (Ton) |
| IB 16 | Exv1 qhib | Tus nqi tiag tiag | R | Sab nraum zoov EEV A qhib (pulse) |
| IB 17 | Exv2 qhib | Tus nqi tiag tiag | R | Sab nraum zoov EEV B qhib (pulse) |
| TIAB SA 1 | Nres Thaum Muaj Xwm Ceev | "0-Tsis muaj 1-Lub zog nres" | W | Emergency stop command |
Kev pab txhawb nqa
1-800-4 LENOX
(1-800-453-6669 Ib)
technicalsupport@lennoxind.com
LennoxCommercial.com
Rub tawm VRF thiab Mini-Split app
los ntawm Apple App Store lossis Google Play Store

Cov ntaub ntawv / Cov ntaub ntawv
![]() |
LENNOX V0CTRL86P-3 VRF BACnet Gateway [ua pdf] Cov neeg siv phau ntawv qhia V0CTRL86P-3, V0CTRL86P-3 VRF BACnet Gateway, VRF BACnet Gateway, BACnet Gateway, Rooj vag |