EMERSON LCP200 Local Control Panel

EMERSON-LCP200-Local-Control-Panel-PRODUCT

Kev faib tawm thaj chaw muaj kev puas tsuaj thiab cov lus qhia tshwj xeeb rau "kev siv nyab xeeb" thiab kev teeb tsa hauv qhov chaw txaus ntshai

Cov ntawv sau npe yuav muaj ntau dua ib qho kev pom zoo, thiab txhua qhov kev pom zoo yuav muaj qhov tshwj xeeb ntawm kev teeb tsa / xaim hluav taws xob thiab / lossis cov xwm txheej ntawm "kev siv nyab xeeb". Cov lus qhia tshwj xeeb rau "kev siv nyab xeeb" yog ntxiv rau, thiab tuaj yeem hla dhau, cov txheej txheem kev teeb tsa tus qauv. Cov lus qhia tshwj xeeb raug teev los ntawm kev pom zoo.

Nco ntsoov: This information supplements the nameplate markings affixed to the product and the LCP200 instruction manual (D104296X012), available from your Emerson sales office or Fisher.com Always refer to the nameplate itself to identify the appropriate certification. LCP200 instruments with an IIC rating may have different hardware than IIB-rated instruments; be sure to order the appropriately rated instrument based on your application and wiring practices.

CEEB TOOM: Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion, or area re‐classification.

Intrinsically Safe

Tej yam kev mob ntawm kev siv

  1. Install the unit in the area of low risk from mechanical hazards. To prevent the risk of electrostatic sparking, the non-metallic surface shall be cleaned with a damp daim ntaub.

Sau ntawv

Ambient temperature rating: -40 ° C ≤ Ta ≤ +65 ° C

  1. Install per drawing GG55194, shown in Figures 1, 2, 3, and 4, as indicated on the nameplate.
  2. Kev hloov cov khoom siv tuaj yeem cuam tshuam kev nyab xeeb ntawm tus kheej.
  3. The enclosure contains non-metallic enclosure parts. To prevent the risk of electrostatic sparking, the non-metallic surface shall be cleaned with a damp daim ntaub.
    1. Refer to table 1 for approval information.

Table 1. Approval Information, ATEX/IECEx

Daim ntawv pov thawj Certification Tau txais Qhov Chaw Ntsuas Kub Code
 

 

 

ATEX IECEx

ATEX: FM17ATEX0071X  II 1 GD IECEx: IECEx FMG 17.0028X

Intrinsically Safe Gas

Ex ia IIC Ga Dust

Ex ia IIIC Da

Install Per Drawing GG55194 (shown in figure 1, 2, 3, and 4)

 

 

 

Per Drawing GG55194 (shown in figure 1, 2, 3, and 4)

 

 

Gas: T6 Dust: T85 C

Figure 1. Intrinsically Safe, LOOP Power, ATEX/IECEx

  • Wiring Configuration A (LOOP-Powered only) From Barrier to Digital Valve Controller and LCP200 See Notes in figure 3 and Notes 1, 2, 3, 4, and 5 in Figure 4.

EMERSON-LCP200-Local-Control-Panel-fig-1

Figure 2. Intrinsically Safe, External Power 24V, ATEX/IECEx

  • Wiring Configuration B (External 24V Only) From Barrier to Digital Valve Controller and LCP200 See Notes in figure 3 and Notes 1, 2, 4, and 5 in Figure 4.

EMERSON-LCP200-Local-Control-Panel-fig-2

Figure 3. Notes

THE INTRINSIC SAFETY ENTITY CONCEPT ALLOWS THE INTERCONNECTION OF TWO APPROVED INTRINSICALLY SAFE DEVICES, WITH ENTITY PARAMETERS NOT SPECIFICALLY EXAMINED IN COMBINATION AS A SYSTEM WHEN: UoEMERSON-LCP200-Local-Control-Panel-fig-3 Ui, IoEMERSON-LCP200-Local-Control-Panel-fig-3 Ii, CoEMERSON-LCP200-Local-Control-Panel-fig-4 Ci + Cable, LoEMERSON-LCP200-Local-Control-Panel-fig-4 Li + Liable, PoEMERSON-LCP200-Local-Control-Panel-fig-3 Pi. DUST-TIGHT SEAL MUST BE USED WHEN INSTALLED IN DUST-PROTECTED ENVIRONMENTS. EACH CONNECTION BETWEEN THE LCP200 AND THE ASSOCIATED INTRINSICALLY SAFE APPARATUS SHALL BE SEPARATELY SHIELDED FROM THE OTHER CONNECTIONS. WHEN CALCULATING THE ENTITY COMBINATIONS THAT INCLUDE THE DVC6000/DVC6200, THE SUMMATION OF THE Ci + Cable AS WELL AS THE Li + Lcable FOR THE DVC6000/DVC6200 AND THE LCP200 SHALL BE USED. ASSOCIATED APPARATUS MANUFACTURERS’ INSTALLATION DRAWINGS MUST BE FOLLOWED WHEN INSTALLING THIS EQUIPMENT.

Figure 4. Notes

Refer to Notes 1, 2, 3, 4, and 5 for Figure 1. Intrinsically Safe, LOOP Power, ATEX/IECEx Wiring Configuration A (LOOP-Powered only) From Barrier to Digital Valve Controller and LCP200 Refer to Notes 1, 2, 4, and 5 for Figure 2. Intrinsically Safe, External Power 24V, ATEX/IECEx Wiring Configuration B (External 24V Only) From Barrier to Digital Valve Controller and LCP200.

LUS CIM

  1. FOR Ex ia APPLICATIONS THE FOLLOWING INFORMATION SHALL BE OBSERVED:
    • THE OVERALL GAS GROUP RATING OF THE INTRINSICALLY SAFE CIRCUIT WILL BE THE LOWEST GAS GROUPING OF ALL APPARATUS FORMING) THE CIRCUIT. FOR EXAMPLE, A CIRCUIT WITH BOTH IIB AND IIC APPARATUS WILL HAVE AN OVERALL CIRCUIT GAS GROUP RATING OF IIB.
    • THE LEVEL OF PROTECTION OF THE INTRINSICALLY SAFE CIRCUIT WILL BE THE LOWEST LEVEL OF ALL APPARATUS FORMING THE CIRCUIT. FOR EXAMPLE, A CIRCUIT WITH BOTH “ia” AND “ib” WILL HAVE AN OVERALL PROTECTION LEVEL OF “ib”.
  2. THE LOWEST PERMISSIBLE INPUT VOLTAGE (Ui), INPUT CURRENT (Ii), AND INPUT POWER (Pi) OF EACH APPARATUS SHALL BE GREATER THAN OR EQUAL TO THE OUTPUT VOLTAGE (Uo), OUTPUT CURRENT (Io), AND OUTPUT POWER (Po) OF THE ASSOCIATED APPARATUS (BARRIER). THE SUM OF THE MAX UNPROTECTED CAPACITANCE (Ci) AND MAX UNPROTECTED INDUCTANCE (Li), INCLUDING THE INTERCONNECTED CABLING CAPACITANCE (Cable) AND CABLING INDUCTANCE (Liable), MUST BE LESS THAN THE ALLOWABLE CAPACITANCE (Ca) AND INDUCTANCE (La) DEFINED BY THE ASSOCIATED APPARATUS. IF THE ABOVE CRITERIA ARE MET THAN THE COMBINATION MAY BE CONNECTED.
  3. INSTALLATION OF THE LCP200 IS SUCH THAT ITS LOOP TERMINALS WILL BE CONNECTED IN PARALLEL WITH OTHER INTRINSICALLY SAFE APPARATUS LOOP TERMINALS. THE WIRING COMING FROM THE BARRIER INTO THE HAZARDOUS LOCATION MAY BE TERMINATED AT EITHER THE INTRINSICALLY SAFE APPARATUS, OR AT THE LCP200.
  4. MAXIMUM SAFE AREA VOLTAGE MUST NOT EXCEED 250 VRMS
  5. THE ENCLOSURE CONTAINS NON-METALLIC ENCLOSURE PARTS. TO PREVENT THE RISK OF ELECTROSTATIC SPARKING, THE NON-METALLIC SURFACE SHALL BE CLEANED WITH A DAMP Khaub ncaws.

Figure 5. LCP200 ATEX/IECEx Nameplate, Intrinsically Safe

EMERSON-LCP200-Local-Control-Panel-fig-5

Tawg-pov thawj

Tej yam kev mob ntawm kev siv
  1. The enclosure contains non-metallic enclosure parts. To prevent the risk of electrostatic sparking, the non-metallic surface shall be cleaned with a damp daim ntaub.
  2. The flameproof joints of the equipment are not intended to be repaired. Consult the manufacturer if repair of the joints is necessary.
  3. The electronics compartment rear cover is assembled and torqued at the factory and is not to be removed by the end user.
  4. Consult the manufacturer for genuine replacement terminal cover fasteners. The fasteners are 316 stainless steel, bolt class A4-70, sized M6 x 1 mm x 15 mm.
Sau ntawv

Ambient temperature rating: -40 ° C ≤ Ta ≤ +65 ° C

  1. Install unit in the area of low risk from mechanical hazards.
  2. Install per drawing GG55194, shown in Figures 6, 7, and 8, as indicated on the nameplate.
  3. Kev hloov cov khoom siv tuaj yeem cuam tshuam kev nyab xeeb ntawm tus kheej.
    1. Refer to table 2 for approval information.

Table 2. Approval Information, ATEX/IECEx

Daim ntawv pov thawj Certification Tau txais Loop Schematic Kub Code
 

 

 

ATEX IECEx

ATEX: FM21ATEX0024X IECEx: IECEx FMG 21.0016X

Ex eb ia mb IIC T6 Gb Ex ta IIIC T85°C Da

Ex db ia IIB T6 Gb Ex db ia IIC T6 Gb

Install Per Drawing GG55194 (shown in figure 6, 7, and 8)

 

 

 

Per Drawing GG55194 (shown in figure 6, 7, and 8)

 

 

Gas: T6 Dust: T85 C

Figure 6. Explosion-proof, LOOP Power, ATEX/IECEx

  • Wiring Configuration A (LOOP-Powered only) See Figure 8 Notes

EMERSON-LCP200-Local-Control-Panel-fig-6

Figure 7. Explosion-proof, External Power 24V, ATEX/IECEx

  • Wiring Configuration B (External 24V Only) See Figure 8 Notes

EMERSON-LCP200-Local-Control-Panel-fig-7

Figure 8. Notes

LUS CIM: ASSOCIATED APPARATUS MANUFACTURER’S INSTALLATION DRAWING MUST BE FOLLOWED WHEN INSTALLING THIS EQUIPMENT.

  1. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE CANADIAN ELECTRIC CODE, PART 1 OR NEC NFPA AND ANSI/ISA RP12.06.01.
  2. THE ENCLOSURE CONTAINS NON-METALLIC ENCLOSURE PARTS TO PREVENT THE RISK OF ELECTROSTATIC SPARKING. THE NON-METALLIC SURFACE SHALL BE CLEANED WITH A DAMP Khaub ncaws.
  3. DUST-TIGHT CONDUIT SEAL MUST BE INSTALLED WITHIN 18” WHEN INSTALLED IN CLASS II AND CLASS III ENVIRONMENTS.
  4. THE NAMEPLATE IS PROVIDED WITH BOXES THAT THE END USER/INSTALLER MUST CHECK OR ETCH FOR THE PROTECTION METHOD USED ACCORDING TO THE INSTALLATION.
  5. CEEV FAJ: USE FASTENERS WITH YIELD STRESSEMERSON-LCP200-Local-Control-Panel-fig-4 450 Mpa ua.
  6. THE END USER SHALL CLOSE ANY UNUSED ENTRIES WITH SUITABLY CERTIFIED BLANKING ELEMENTS.
  7. FOR ZONES APPLICATIONS, CONNECTION OF THE INTERNAL GROUND IS REQUIRED AS CONNECTION OF THE EXTERNAL GROUP IS OPTIONAL.

Figure 9. LCP200 ATEX/IECEx Nameplate, Explosion-proof, Group IIC

EMERSON-LCP200-Local-Control-Panel-fig-8

Figure 10. LCP200 ATEX/IECEx Nameplate, Explosion-proof, Group IIB

EMERSON-LCP200-Local-Control-Panel-fig-9

Neither Emerson, Emerson Tsis Siv Neeg Cov Teeb Meem, thiab tsis muaj ib lub koom haum koom nrog kev lees paub rau kev xaiv, siv lossis tswj cov khoom lag luam. Lub luag haujlwm rau cov kev xaiv tsim nyog, kev siv, thiab kev saib xyuas ntawm ib qho khoom lag luam tsuas yog ua tiav nrog cov neeg yuav khoom thiab tus neeg siv khoom kawg.

Fisher yog ib lub cim uas muaj los ntawm ib lub tuam txhab hauv Emerson Automation Solutions lag luam chav tsev ntawm Emerson Electric Co. Emerson Automation Solutions, Emerson, thiab Emerson logo yog cov cim lag luam thiab cov kev pabcuam ntawm Emerson Electric Co. Tag nrho lwm cov cim yog cov cuab yeej ntawm lawv. raws li tus tswv.

Cov ncauj lus ntawm kev tshaj tawm no tsuas yog nthuav tawm rau cov ntaub ntawv xov xwm nkaus xwb, thiab thaum txhua qhov kev mob siab tau ua kom ntseeg tau lawv qhov raug, lawv tsis yog txhais tau tias yog kev lav lossis lav, qhia tawm lossis siv, txog cov khoom lossis kev pabcuam tau piav qhia hauv no lossis lawv siv lossis kev siv tau. Txhua qhov kev muag khoom yog tswj hwm los ntawm peb cov lus thiab cov haujlwm, uas tau muaj thaum thov. Peb muaj txoj cai hloov pauv lossis txhim kho cov qauv tsim lossis cov kev qhia tshwj xeeb ntawm cov khoom lag luam txhua lub sijhawm yam tsis tau ceeb toom.

Emerson Kev Ua Lag Luam Solutions

  • chaw nyob: Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 Fabkis Dubai, Teb chaws As Mes Lis Kas Teb Sab Hnub Tuaj Singapore 128461 Singapore
  • www.Fishing.com

2018, 2021 Fisher Controls International LLC. Txhua txoj cai.

Cov ntaub ntawv / Cov ntaub ntawv

EMERSON LCP200 Local Control Panel [pdf] Phau Ntawv Qhia
LCP200 Local Control Panel, LCP200, Local Control Panel, Control Panel, Panel
EMERSON LCP200 Local Control Panel [pdf] Phau Ntawv Qhia
LCP200 Local Control Panel, LCP200, Local Control Panel, Control Panel