STANDARD FEATURES

  • Variable speed compressor
  • High efficiency ECM fan motor
  • Factory installed base pan heater
  • Factory installed crankcase heater
  • Low voltage controls
  • Auto-restart function
  • Condenser high temp protection
  • Quiet operation
  • Anti-corrosive fin coating

COMPATIBLE WITH:

  • DLFLAB Air Handler
  • DLFLCB Cassette
  • DLFLFA Console
  • DLFLDA Ducted

Outdoor Heat Pump Unit
Inverter Compressor
Sizes: 36 / 48 / 58

KEY FEATURES

Premium Efficiency
Enjoy increased energy savings with a unit equipped with inverter technology that delivers first-rate comfort and efficiency.
Simple Maintenance
With convenient access to the control compartment through both top and side panels, this outdoor unit makes servicing and maintenance a breeze.
QUIETCOMFORT SERIES


DLCLRC OUTDOOR UNIT
SPECIFICATIONS:
DLCLRC Outdoor Unit
Heat Pump
System
Size 36K 48K 58K
Outdoor Model DLCLRCH36AAK DLCLRCH48AAK DLCLRCH58AAK
Electrical
Voltage-Phase-Cycle V-Ph-Hz 208/230-1-60 208/230-1-60 208/230-1-60
MCA A. 30 35 35
MOCP – Fuse Rating A. 50 50 50
Operating Range
Cooling Outdoor DB Min – Max ° F (° C) -22~130 (-30~55) -22~130 (-30~55) -22~130 (-30~55)
Heating Outdoor DB Min – Max ° F (° C) -22~86 (-30~30) -22~86 (-30~30) -22~86 (-30~30)
Piping
Total Piping Length ft (m) 213 (65) 213 (65) 213 (65)
Piping Lift* ft (m) 98 (30) 98 (30) 98 (30)
Pipe Connection Size – Liquid in (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Pipe Connection Size – Suction in (mm) 5/8 (16) 5/8 (16) 7/8 (22)
Refrigerant
Type R410A R410A R410A
Charge lbs (kg) 6.72 (3.05) 9.26 (4.2) 10.58 (4.8)
Compressor
Type Rotary Inverter Rotary Inverter Rotary Inverter
Outdoor
Unit Width in (mm) 37.24 (946) 37.48 (952) 37.48 (952)
Unit Height in (mm) 31.89 (810) 52.48 (1333) 52.48 (1333)
Unit Depth in (mm) 16.14 (410) 16.34 (415) 16.34 (415)
Net Weight lbs (kg) 148.59 (67.4) 219.14 (99.4) 217.15 (98.5)
Airflow CFM 2,130 4,500 4,500
Sound Pressure dB(A) 63 62.5 61.2

*Condensing unit above or below indoor unit.
COMPATIBILITY:

Indoor Unit Outdoor Unit
DLCLRCH36AAK DLCLRCH48AAK DLCLRCH58AAK
Air Handler DLFLABH36XAK
DLFLABH48XAK
DLFLABH60XAK
Cassette DLFLCBH36XAK
DLFLCBH48XAK
Console DLFLFAH36XAK
DLFLFAH48XAK
DLFLFAH58XAK
Ducted DLFLDAH36XAK
DLFLDAH48XAK
DLFLDAH58XAK

Manufacturer reserves the right to discontinue, or change at any time, specification or designs without notice or incurring obligations.

PERFORMANCE

DLFLAB Air Handler

Size 36K 48K 60K
Indoor Model DLFLABH36XAK DLFLABH48XAK DLFLABH60XAK
Cooling System Tons 3.0 4.0 4.8
Cooling Rated Capacity Btu/h 36,000 48,000 57,000
Cooling Cap. Range Min – Max Btu/h 11,600-41,000 11,800~51,900 11,000~60,000
SEER 17.0 16.2 17.0
EER 8.8 8.6 10.0
Heating Rated Capacity (47° F) Btu/h 38,000 55,000 60,000
Heating Rated Capacity (17° F) Btu/h 25,600 37,500 34,000
Heating Maximum Capacity (17° F) Btu/h 27,000 37,500 34,600
Heating Maximum Capacity (5° F) Btu/h 22,000 31,000 33,000
Heating Cap. Range Min – Max Btu/h 9,200-43,000 11,900~58,000 12,000~60,400
HSPF 11.3 10.8 10.4
COP (47° F) W/W 3.35 3.03 3.2
COP (17° F) W/W 2.61 2.46 2.52
COP (5° F) W/W 1.9 1.75 1.81

PERFORMANCE:
DLFLCB Cassette

Size 36K 48K
Indoor Model DLFLCBH36XAK DLFLCBH48XAK
Cooling System Tons 3.0 4.0
Cooling Rated Capacity Btu/h 36,000 48,000
Cooling Cap. Range Min – Max Btu/h 12,400~36,000 16,600~48,000
SEER 18.2 17.8
EER 9.0 9.5
Heating Rated Capacity (47° F) Btu/h 38,000 50,000
Heating Rated Capacity (17° F) Btu/h 23,000 28,000
Heating Maximum Capacity (17° F) Btu/h 25,300 37,900
Heating Maximum Capacity (5° F) Btu/h 22,300 30,200
Heating Cap. Range Min – Max Btu/h 11,200~38,000 11,850~52,000
HSPF 10.6 11.5
COP (47° F) W/W 3.01 3.1
COP (17° F) W/W 1.9 1.8
COP (5° F) W/W 2.02 1.92

PERFORMANCE:
DLFLFA Console

Size 36K 48K 58K
Indoor Model DLFLFAH36XAK DLFLFAH48XAK DLFLFAH58XAK
Cooling System Tons 3.0 4 4.5
Cooling Rated Capacity Btu/h 36,000 48,000 54,000
Cooling Cap. Range Min – Max Btu/h 11,400~36,000 15,800~48,000 15,000~54,000
SEER 17.0 18.0 18.0
EER 8.0 9.3 9.8
Heating Rated Capacity (47°F) Btu/h 38,000 50,000 60,000
Heating Rated Capacity (17° F) Btu/h 23,000 29,000 35,000
Heating Maximum Capacity (17° F) Btu/h 23,000 29,000 35,000
Heating Maximum Capacity (5° F) Btu/h 22,000 28,000 30,000
Heating Cap. Range Min – Max Btu/h 11,400~38,000 12,000~50,000 17,000~62,000
HSPF 10.0 11.0 10.0
COP (47°F) W/W 2.8 2.5 3
COP (17° F) W/W 2.34 2.52 2.49
COP (5° F) W/W 1.8 1.95 1.9

PERFORMANCE:
DLFLDA Ducted

Size 36K 48K 58K
Indoor Model DLFLDAH36XAK DLFLDAH48XAK DLFLDAH58XAK
Cooling System Tons 3.0 4.0 4.8
Cooling Rated Capacity Btu/h 36,000 48,000 57,000
Cooling Cap. Range Min – Max Btu/h 5,900~36,000 12,000~48,000 13,000~59,000
SEER 16.7 17.4 18.0
EER 9.0 9.2 10.0
Heating Rated Capacity (47° F) Btu/h 40,000 50,000 60,000
Heating Rated Capacity (17° F) Btu/h 27,000 29,000 35,400
Heating Maximum Capacity (17° F) Btu/h 25,000 29,000 35,400
Heating Maximum Capacity (5° F) Btu/h 22,000 32,000 35,000
Heating Cap. Range Min – Max Btu/h 12,700~40,000 11,600~50,000 12,000~61,000
HSPF 11.5 10.3 10.0
COP (47° F) W/W 3.37 3 3.5
COP (17° F) W/W 2.63 2.57 2.5
COP (5° F) W/W 1.9 1.95 2.01


A Proud Member of the Carrier Family
Heil-HVAC.com
PO Box 128 Lewisburg, TN 37091
©2022 Carrier. All Rights Reserved.
Midea is a registered trademark owned by Midea Group Co., Ltd.
Part No. DLS-012-HL-00

Documents / Resources

HEIL DLCLRC Outdoor Heat Pump Unit Inverter Compressor [pdf] User Guide
DLCLRC Outdoor Heat Pump Unit Inverter Compressor, DLCLRC, Outdoor Heat Pump Unit Inverter Compressor, Heat Pump Unit Inverter Compressor, Inverter Compressor, Compressor

Recent Posts

MikroStar Tech Palarum Beetle v3 Medical Device User Manual

Palarum Beetle v3 Medical Device Palarum Beetle V3 Palarum Beetle V3 Modes of Operations Manual…

1 min ago

YASKAWA AC Drive A1000 Vector Control Drive User Manual

YASKAWA AC Drive A1000 Vector Control Drive User Manual

7 mins ago

DELL Latitude 7440 2 In 1 Laptop User Guide

Latitude 7440 2 In 1 Laptop Product Information: Latitude 7440 2-in-1 The Latitude 7440 2-in-1…

7 mins ago

DELL Latitude 7640 Laptop User Guide

Latitude 7640 Laptop

7 mins ago

GYS IRB 2600 Industrial Robots N Degree 10 Kit Instruction Manual

IRB 2600 Industrial Robots N Degree 10 Kit Product Information Model Number: 71142 Quantity: x4…

8 mins ago

VIDEX VLF-A156R LED Rechargeable Flashlight User Manual

VLF-A156R LED Rechargeable Flashlight Product Information: LED Rechargeable Flashlight VLF-A156R Maximum brightness: 1700 lumens with…

15 mins ago