Digital temperature controller
BR6A
INSTRUCTION MANUAL
Thank you for purchasing Hanyoung Nux products. Please read the instruction manual carefully before using this product, and use the product correctly.
Also, please keep this instruction manual where you can view it any time.
Safety information
Please read the safety information carefully before the use, and use the product correctly.
The alerts declared in the manual are classified into Danger and Warning according to their importance.
![]() | DANGER | Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury |
![]() | WARNING | Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury |
![]() | CAUTION | Indicates a potentially hazardous situation which, if not avoided, may result in minor injury or properties damage |
DANGER
- The electric shock may occur in the input/output terminal so please never let your body and/or conductive substance to be contacted by the input/output terminal.
WARNING
- If the user use the product with methods other than specified by the manufacturer, there may be bodily injuries or property damages.
- If there is a possibility of an accident caused by errors or malfunctions of this product, install external protection circuit to prevent the accident.
- To prevent defection or malfunction of this product, apply a proper power voltage in accordance with the rating.
- Since this product is not designed with explosive-protective structure, do not use it any place with flammable or explosive gas.
- Reassemble this product while the power is OFF. otherwise, it may be a cause of malfunction or electric shock.
- There is a possibility of occurring electric shock so please use this product after installing it to a panel while it is operating.
CAUTION
- The contents of the instruction manual are subjective to change without prior notice.
Suffix code
Model | Code | Description | ||||
BR6A- | □ | □ | □ | □ | -□ | Digital temperature controller (selective controller type in parameter (proportional or ON/OFF controller) |
Input | N | Company exclusive sensor(TH-570N) ※Thermistor | ||||
Control of output | M | Relay connect output | ||||
S | Voltage pulse output (voltage pulse output for SSR driving) | |||||
Option | 0 | None | ||||
1 | Communication(RS-485, MODBUS ASCII/RTU) | |||||
Power supply voltage | P4 | 100 -240 V a.c. 50/60 Hz | ||||
LED color | W | White LED display | ||||
R | Red LED display |
Specification
Power consumption | 7 VA Max (220 V a.c. 60 Hz) | |
Input sensor | Company exclusive sensor (TH-570N) ※Thermistor | |
Display accuracy | ± 1 % of FS ± 1 Digit | |
Control output (Main output) | Relay output | Contact composition : 1 c, 250 V a.c., 5 A(Resisitive load) |
SSR | 10 – 15 V d.c. More than(resistive load 500 Ω min) | |
Alarm/Defrost | Relay | Contact composition : 1 c, 250 Va.c., 5 A(Resistive load) |
Control action | Proportional control (P control), ON/OFF control | |
Setting method | Digital setting with operation buttons | |
Other function | Deforsting timer, alarm function, heating/cooling control | |
Communication | RS-485 | |
Protocol | MODBUS ASCII/RTU | |
speed | 4800, 9600, 19200 bps | |
Ambient humidity | 0~50℃ | |
Resistance between wires | Below 10 Ω for each wire | |
Ambient humidity | 35~85 % RH(with no condenssation) | |
Weight | 120 g |
Dimension and panel cutout
■ Sensor(Thermistor/NTC)
Name | Sensory type | Range(℃) | Accuracy | Remark |
TH570N | Thermistor | -50.0~150.0 | ±1.5℃ | Max ± 3.5℃ temperature deviation may be happen (± 1.5℃ sensor deviation & ± 2℃ controller deviation) |
※ Extension of sensor length or modification of sensor will be cause of malfunction.
Control method for temperature
■ Heating/cooling control selection
Connection diagram
■ Cooling control(ON/OFF)
• PV 〉SV → Main output relay “ON” / PV〈 SV → Main output relay “OFF”
■ Heating control(ON/OFF)
• PV 〉SV → Main output relay “OFF” / PV〈 SV → Main output relay “ON”
Proportional control
- Manipulated variable (output size) of set value operates by proportioning to deviation and this is known as proportional control. Also variation range of manipulated variable from 0 ~ 100 % is known as the proportional band. Therefore, when proportional band is less than the current temperature, the manipulated variable becomes 100 % and when PB is more than the current temperature, the manipulated variable becomes 0 % and when set value and current temperature becomes same, the manipulated variable becomes 50 %.
Delay timer set
• Press key continuously for 3 sec, and then, press
key until getting “
“. change a set point by / key, and preservation it by
key.
■ Operating description by delay-timer
※ In case of Delay Time=0, Relay is immediately ON when output signal is generating. In case of delay time=5, Relay is ON after 5 sec.
when output signal is generating. In the interval of 5 sec, the output indicator is flickering during delay timer operation. After the delay time, the output indicator lights as the relay is on.
Auxiliary output(Timer-mode) set and operating description
- It is possible to use timer-mode as defrosting function in case of freezer.
- When using MOC ‘1’, main output will be OFF automatically as timer is ON.
- If using MOC function, you can effectively use timer output as a defrosting function.
※ When auxiliary output is timer mode, time unit is selective between “sec” or “min”.
Set mode for equipment provider
※ Error message : When input is more than +5%, when input is less tham -5%, .
• A : 1 ℃ display mode (trSL = 1), B : 0.1 ℃ display mode (trSL = 0)
Item | Description | Setting range | Default | Unit |
0.typ | Control method setting | Cool/Heat | Cool | — |
1.dlF | Deviation setting | A : 1 ~ 50, B : 0.2 ~ 50.0 | 1.0 | ℃ |
2.dLy | Delay time setting | 0 ~ 240 | 0 | Sec |
3.rST | Input compensation | A : -30 ~ 30, B : -30.0 ~ 30.0 | 0.0 | ℃ |
4.tSH | Higher limit of setting range | A : TSL(min) ~ 150 | 150.0 | |
B : TSL(min) ~ 150.0 | ||||
5.tSL | Lower limit of setting range | A : -50 ~ TSH(max) | -50.0 | |
B : -50.0 ~ TSH(max) | ||||
6.SAo | Selection of auxiliary output function | 0 : Alarm setting | 0 | — |
1 : Timer setting | ||||
Menu of setting alarm | ||||
7.AtS | Setting alarm temperature | A : -50 ~ 150, B : -50.0 ~ 150.0 | -40.0 | ℃ |
8.AdF | Deviation settings for the alarm | A : 1~ 50, B : 0.2 ~ 50.0 | 1.0 | |
9.AdL | Delay time setting for alarm | 0 ~ 240 | 0 | Sec |
Menu for timer setting | ||||
7.ton | On time setting | 0 ~ 3600 | ON time 1 | ※1 |
8.toF | Off time setting | 0 ~ 3600 | OFF time 3 | |
9.Moc | Main output control | 0 : Releasing output control, 1 : Releasing output | 0 | — |
※1 : when time=0 in administrator setting mode, it is Sec. when time=1 in administrator setting mode, it is Min.
Administrator setting mode
※ When changing value, shift. key moves digit.
■ Set Value lock function and decimal point function
Function | SV | Setting range | Description | Default | Unit |
Lock | 0 | 0 ~ 1 | Cancellation of lock function | 0 | — |
1 | Operation of lock function | ||||
trSL | 0 | Decimal point (0.1℃) | 0 | ||
1 | No decimal point (1℃) | ||||
Time | 0 | “sec.” setting in Timer (0 ~ 3,600 sec) | 1 | ||
1 | “min.” setting in Timer (0 ~ 3,600 min) | ||||
ProF | 0 | P.I.D control (P.B value/M.R value setting isavailable) | 1 | ||
1 | ON/OFF control | ||||
G.COM | Communication setting | Click the Shift Key to enter the communication setting |
■ Communication setting
Item | Description | Setting value | Setting range | Default | Unit |
G.COM | Prs | Protocol | ASCII/RTU | RTU | — |
bPS | Baud Rate | 4800/9600/19200 | 9600 | bps | |
Prl | Parity | None/EVEN/ODD | None | bit | |
StP | Stop Bit | 1 or 2 | 1 | ||
dLn | Data Length | 7 or 8 | 8 | ||
Adr | Adress | 1 ~ 31 | 1 | — | |
rP.t | Response Time | 0 ~ 10 | 0 |
Set mode for normal users
Item | Description | Setting range | Default | Unit |
SV | Set value | TSL(min) ~ TSL(max) | 25.0 | ℃ |
Pb | Proportional band setting | 1 ~ 100 | 20 | |
Mr | Remove offset | 0 ~ 100 | 50 | % |
Description per address
Progress (1~) | |||||
Addr | Parameter | Description | Setting range | Remark | R/W |
1 | PV | Present value | -60.0 ~ 160.0 | x10(℃) ※2 | R |
2 | SV | Set value | -50.0 ~ 150.0 | x10(℃) ※2 | |
3 | MV OUT | Manipulated value | 0 ~ 100 | (%) | |
4 | OUT | OUTPUT 1 | 0 or 1 | 0 : Output off | |
1 : Output | |||||
5 | ALM | ALARM 1 | 0 or 1 | 0 : Output off | |
1 : Output | |||||
6 | ON TIME | Remaining ON time | 0 ~ 3600 | (Sec or Min) ※1 | |
7 | OFF TIME | Remaining OFF time | |||
8 | ERR. STS | Error status | Error status information | Refer to BIT INFORMATION | |
Information (100 ~ ) | |||||
Addr | Parameter | Description | Setting range | Remark | R/W |
100 | SYSTEM | System information | 0 x 0001 ~ 0 x FFFF | 0x0001 : BR6A | R |
101 | OPTION | Option information | 0x0000 : NM0P4, 0x0001 : NM1P4 | ||
102 | SPECIAL_1 | Additional information 1 | 0x0000 : N/A | ||
103 | SPECIAL_2 | Additional information 2 | |||
104 | H/W Ver | Hardware version | 0x0001 : Ver 0.1 | ||
105 | F/W Ver | Firmware version | |||
106 | F.INT | Setting initialzation | 0 or 1 | 1 : Flash init | R/W |
Control (200 ~ ) | |||||
Addr | Parameter | Description | Setting range | Remark | R/W |
200 | LOCK | Lock setting | 0 or 1 | 0 : Unlock | R/W |
1 : Lock setting | |||||
201 | TRSL | Decimal point display setting | 0 : Decimal point display | ||
1 : No Decimal point display | |||||
202 | TIME | Time unit setting | 0 : Sec setting in timer | ||
1 : Min setting in timer | |||||
203 | PORF | Control setting | 0 : Proportional control | ||
1 : ON/OFF control | |||||
204 | TYP | Control method setting | 0 : Cool, 1 : Heat | ||
205 | DIF | Deviation setting | 0.2 ~ 50.0 | x10 (℃)※2 | |
206 | DLY | Delay time setting | 0 ~ 240 | (Sec) | |
207 | RST | Input compensation | -30.0 ~ + 30.0 | x10 (℃)※2 | |
208 | TSH | Higher limit of setting range | TSL(min) ~ 150.0 | ||
209 | TSL | Lower limit of setting range | -50.0 ~ TSH(max) | ||
210 | SAO | Selection of auxiliary output function | 0 or 1 | 0 : Alarm setting | |
1 : Timer setting | |||||
211 | ATS | Setting alarm temperature | -50.0 ~ 150.0 | x10 (℃)※2 | |
212 | ADF | Deviation settings for the alarm | 0.2 ~ 50.0 | ||
213 | ADL | Delay time for alarm | 0 ~ 240 | (Sec) | |
214 | TON | On time setting | 0 ~ 3600 | (Sec or Min)※1 | |
215 | TOF | Off time setting | |||
216 | MOC | Main output control | 0 or 1 | 0 : Off output control | |
1 : Output control | |||||
SV (300 ~) | |||||
Addr | Parameter | Description | Setting range | Remark | R/W |
300 | SV | Set value | -50.0 ~ +150.0 | x10 (℃)※2 | R/W |
301 | PB | Proportional band setting | 1 ~ 100 | ||
302 | MR | Remove offset | 0 ~ 100 | (%) | |
Communication (500 ~) | |||||
Addr | Parameter | Description | Setting range | Remark | R/W |
510 | PRS | Protocol | 2 ~ 3 | 2 : Modbus ASCII, 3 : Modbus RTU | R |
511 | BPS | Baud rate | 3 ~ 5 | 3 : 4800 bps, 4 : 9600 bps, 5 : 19200 bps | |
512 | PRI | Parity | 0 ~ 2 | 0 : None, 1 : Even, 2 : Odd | |
513 | STP | Stop bit | 1 ~ 2 | 1 or 2 | |
514 | DLN | Data length | 7 ~ 8 | 7 or 8 | |
515 | ADR | Address | 1 ~ 31 | 1 ~ 31 | |
516 | RPT | Response time | 0 ~ 10 | 0 ~ 10 |
BIT information
BIT | ERR STS |
Addr = 8 | |
0 | -Over |
1 | Over |
2~15 | — |
HANYOUNGNUX CO.,LTD
28, Gilpa-ro 71beon-gil, Michuhol-gu,
Incheon, Korea TEL : +82-32-876-4697
http://www.hanyoungnux.com