hager Vector Surface Mounted Distribution Board

hager Vector Surface Mounted Distribution Board - icon

Vector Surface Mounted Distribution Board

hager Vector Surface Mounted Distribution Board - fig2

hager Vector Surface Mounted Distribution Board - fig3

hager Vector Surface Mounted Distribution Board - fighager Vector Surface Mounted Distribution Board - fig1
Tunnel TerminalSolid ConductorsStranded Conductors4 to 16 mm2Flexible Conductors
0 = 5,7 mm1,5 to 16 mm21,5 to 2,5 mm2 Copper strands must
be twisted (note)
1,5 to 10 mm2 with bootlace
ferrules
0 = 8,1 mm4 to 35 mm24 to 6 mm2 Copper strands must
be twisted (note)
10 to 35 mm24 to 16 mm2 with bootlace
ferrules
Note1: Copper strands must be firmly twisted together using a tool i.e. pliers

hager Vector Surface Mounted Distribution Board - fig4

AHTBCD
VE103111 mm175 mm93 mm120 mm
VE106165 mm190 mm113 mm126 mm108 mm
VE110237 mm210 mm114 mm136 mm180 mm
VE112310 mm302 mm151 mm155 mm230 mm115 mm
VE212310 mm427 mm151 mm280 mm230 mm115 mm
VE312310 mm552 mm151 mm405 mm230 mm115 mm
VE412310 mm677 mm151 mm530 mm230 mm115 mm
VE118418 mm302 mm151 mm155 mm338 mm169 mm
VE218418 mm452 mm151 mm305 mm338 mm169 mm
VE318418 mm602 mm151 mm455 mm388 mm169 mm
hager Vector Surface Mounted Distribution Board - fig5hager Vector Surface Mounted Distribution Board - fig6

hager Vector Surface Mounted Distribution Board - fig7

warning 2 Attention!
It is critical that any enclosure is sized and selected to accommodate and dissipate heat rise generated from all installed devices. The table (right) provides maximum permissible heat dissipation for each golf enclosure size. Please ensure that you calculate the internal heat generated from your installation and select the correct enclosure accordingly.

hager Vector Surface Mounted Distribution Board - fig8

ReferenceAdmissible thermal dissipation loss for surface-mounted distribution boards at temperature rise AT*
10K W15K W20K W25K W30K W
VE103..2,44,05,77,59,4
VE106..3,25,37,610,112,6
VE110..4,57,410,610,017,6
VE112..7,712,818,324,230,3
VE212..9,515,723,529,737,3
VE312..11,318,826,835,444,4
VE412..13,221,831,241,251,7
VE118..9,916,423,531,038,9
VE218..12,320,429,238,648,4
VE318..14,824,635,246,458,2

*) ∆T is the temperature difference between the upper limiting temperature of the installed equipment and the ambient air temperature of the distribution board.
The Assembly (DBO) designated markings must be completed as specifi ed in IEC/EN 61439 – 3 clause 6.1.

Hager Industrial de Envolventes S.A., Alfred Nobel 18, 08430 La Roca Del Valles, Spain 
T +34 93 842 47 30
F +34 93 842 24 64
info@hager.com
hager.com
02.2022

Documents / Resources

hager Vector Surface Mounted Distribution Board [pdf] Instructions
Vector, Surface Mounted Distribution Board, Mounted Distribution Board, Distribution Board, Vector, Board

References

Leave a comment

Your email address will not be published. Required fields are marked *