GROWATT TPM-CT-E Three Phase Smart Meter

GROWATT-TPM-CT-E-Three-Phase-Smart-Meter

Overview

SDM630MCT-MA is a multi-function rail meter, it can accurately measure and display various power parameters in 1P2W/3P3W/3P4W: voltage, current, power, frequency, active power, reactive power, forward power, reverse power, total harmonics, etc. The meter is suitable for real-time power monitoring system, with multi-function, multi-purpose, high stability and long life characteristics. The meter is connected with an external current transformer and is suitable for various high and low voltage power grids. The meter has RS485 communication interface, supports the highest communication rate of 38400bps, can realize remote communication.

Technical Parameters

General Specifications
Rated voltage3×230/400Vac
Rated frequency50/60Hz
L-N voltage range100 ~ 289Vac
L-L voltage range173 ~ 480Vac
Auxiliary power voltage range85 ~ 275Vac or 120 ~ 380Vdc
AC withstand voltage4KV for 1min
Input current range<40mA
Short-term overcurrent20*IMAX for 0.5s
Max. Reading9999999.9kWh/kVArh
Accuracy
Active power0.5% of range maximum
Reactive power1% of range maximum
Environment
Rated temperature-25℃~+55℃
Limit temperature-40℃~+70℃
Relative humidity(average annual)≤90%
Installation categoryCAT III
Degree of pollutionConform to RoHS
Communication
CommunicationRS485 output for Modbus RTU
Baud rate9600bps(default)
Pulse3200imp/kWh
Mechanics
Mounting dimensions94.5x72x65mm(LxWxH  )
Din rail dimensionsDIN rail 35mm
Protection levelIP51 (indoor)

Unpacking

GROWATT-TPM-CT-E-Three-Phase-Smart-Meter-1

ItemQuantityDescription
A1Three-phase meter
B1User Manual
C1RS485 cable (standard length 15m)
D3Current Transformer

Dimension (Unit:mm)

GROWATT-TPM-CT-E-Three-Phase-Smart-Meter-2

Installation

GROWATT-TPM-CT-E-Three-Phase-Smart-Meter-3

Note:
We describe Growatt Grid-tied inverter as “PV inverter”and Growatt Hybrid/AC Coupled Inverter as “Hybrid Inverter”as below.

a. Voltage sampling and power supply wiring
Wiring of the L1 voltage sampling line: corresponding to meter Pin 4
Wiring of the L2 voltage sampling line: corresponding to meter Pin 3
Wiring of the L3 voltage sampling line: corresponding to meter Pin 2
Wiring of the N voltage sampling line: corresponding to meter Pin 1

GROWATT-TPM-CT-E-Three-Phase-Smart-Meter-4

Current transformer wiring

  • The wiring should be executed according to the picture as shown on left. On the right side is the grid, current flows from K to L(grid to load).
  • Wiring of the L1 CT: White Line corresponding to meter Pin 20, Black Line corresponding to meter Pin 19
  • Wiring of the L2 CT: White Line corresponding to meter Pin 18, Black Line corresponding to meter Pin 17
  • Wiring of the L3 CT: White Line corresponding to meter Pin 16, Black Line corresponding to meter Pin 15

RS485 wiring
Connect the Rs485 A to Pin 14 and Rs485 B to Pin 13 (There are corresponding line marks on the network cable in the attachment: 485A, 485B; If you use your own network cable, please choose 568B standard network cable, white orange cable is 485B and white blue cable is 485A)

When you are installing a PV Inverter, first cut off the RJ45 modular plug, then find two cables and crimp the accessory terminals, finally, put them into the correspond interface of the inverter’s 8 Pin signal connector as below.

GROWATT-TPM-CT-E-Three-Phase-Smart-Meter-5

The standard RS485 cable length is 15m. If need longer RS485 cable, please use an ethernet coupler to extend and make sure RS485 cable less than 100m (the recommended length is less than 25m).

GROWATT-TPM-CT-E-Three-Phase-Smart-Meter-6

Button Definition And Display

There are four touch buttons on the panel, from top to bottom are “ESC(←)V/A”, “↑(Alt)MD/PH/HZ”, “↓(Shift)P”, “ENTER (→)E”. There are two types of key operation: long press(Press for more than two seconds) and short press(Pressing time is less than one second).

NO.ButtonFeaturesViewable content (short press)
1GROWATT-TPM-CT-E-Three-Phase-Smart-Meter-7Short press:

display voltage and current, ←

Long press: ESC

Phase voltage, Line voltage, Phase current, Neutral current, Voltage harmonics, Current harmonics
2GROWATT-TPM-CT-E-Three-Phase-Smart-Meter-8Short press: display power factor and frequency, ↑

Long press: Alt

Phase(Total) frequency, Total power factor, Phase(Total) maximum current demand
3GROWATT-TPM-CT-E-Three-Phase-Smart-Meter-9Short press: display power, ↓

Long press: Shift

Phase(Total) active power, Phase(Total) reactive power, Phase(Total) apparent power
4GROWATT-TPM-CT-E-Three-Phase-Smart-Meter-10Short press:

display electric energy, →

Long press: Enter

Total active electric energy, Total reactive electric energy, Forward active electric energy, Reverse active electric energy, Forward reactive electric energy, Reverse reactive electric energy

GROWATT-TPM-CT-E-Three-Phase-Smart-Meter-11

Trouble Shooting

Fault phenomenonReason analysisSolution
Big deviation between electric energy measurement and actual value. 

1.  Wiring error, voltage and current corresponding phase sequence is wrong.

2.  If the output line of the current transformers is reversed.

3.    The transformer ratio is not set, the meter displays the secondary data.

 

1.  Refer to the wiring diagram to check the wiring.

2.  If the transformer ratio setting is wrong, please set the voltage ratio and current ratio correctly.

3.  If the issue still exists,please contact your local supplier.

RS485 communication error (Inverter error 401)1.    RS485 cable is open circuit,short circuit or resersely.

2.   The address, baud rate and data parity of the meter do not match the SPH.

 

1.   If there is a problem with the communication cable, please replace the communication cable.

2.  Set the correct address, baud rate, and data bit check digit of the meter by the button.

3.  If the issue still exists,please contact your local supplier.

The complete system wiring diagram is as follows, if the meter is not operating normally, you can refer to it to check the wiring.EPS port is only available in hybrid inverter.

GROWATT-TPM-CT-E-Three-Phase-Smart-Meter-12

Service and contact

Shenzhen Growatt New Energy Co., Ltd
4-13/F, Building A, Sino-German (Europe) Industrial Park, Hangcheng Ave, Bao’an District, Shenzhen, China
+86 0755 2747 1942
E service@ginverter.com
W www.ginverter.com

Download Manual

GROWATT-TPM-CT-E-Three-Phase-Smart-Meter-13

Documents / Resources

GROWATT TPM-CT-E Three Phase Smart Meter [pdf] User Guide
TPM-CT-E, TPM-CT-E Three Phase Smart Meter, Three Phase Smart Meter, Smart Meter, Meter

References

Leave a comment

Your email address will not be published. Required fields are marked *