GE -logo1Installation Guide
A1019051 | 99008144
Evolve ™ LED Hazardous Location Flood
GE -logo

GE -iconBEFORE YOU BEGIN

Read these instructions completely and carefully. Save these instructions for future use.

GE current A1019051 Evolve LED Hazardous Location Flood-

GE -icon1WARNING

RISK OF ELECTRIC SHOCK OR FIRE
To reduce the risk of electric shock or ignition of hazardous atmospheres, disconnect the luminaire from the supply circuit before opening. Keep tightly closed when in operation.
RISK OF INJURY OR DAMAGE
Unit will fall if not installed properly. Follow installation instructions.
GE -icon1CAUTION
RISK OF INJURY
Wear safety glasses and gloves during installation and servicing.
RISK OF INJURY
The luminaire should be mounted so that prolonged staring into the luminaire at a distance closer than 0.50m is not expected.

Storage & Handling

GE current A1019051 Evolve LED Hazardous Location Flood-fig1

Store packaged units in a covered dry area

GE current A1019051 Evolve LED Hazardous Location Flood-fig2

Check for damage

GE current A1019051 Evolve LED Hazardous Location Flood-fig18

Do not impact

GE current A1019051 Evolve LED Hazardous Location Flood-fig3

Mounting-Wall & Ceiling

GE current A1019051 Evolve LED Hazardous Location Flood-fig4

No vertical trunnion mounting on wall allowed.

GE current A1019051 Evolve LED Hazardous Location Flood-fig5

For Class II optical aimed horizontal or downward only.

GE current A1019051 Evolve LED Hazardous Location Flood-fig6

Mount to a flat surface. Bolts not included.

GE current A1019051 Evolve LED Hazardous Location Flood-fig7

For 3G applications and mounting surfaces less than 16 inches, 3 bolts are required. Bolts not included.

GE current A1019051 Evolve LED Hazardous Location Flood-fig8

Orient luminaire and secure side bolts.

GE current A1019051 Evolve LED Hazardous Location Flood-fig9

Once desired angle, tighten bolts evenly.

GE -icon1WARNING

RISK OF DAMAGE
Do not torque trunnion bolts greater than 30 ft-lbs. Damage may occur.

Wiring

GE current A1019051 Evolve LED Hazardous Location Flood-fig10

Loosen 3 captive screws and open the door.

GE current A1019051 Evolve LED Hazardous Location Flood-fig11

Install ¾ inch NPT conduit.

GE current A1019051 Evolve LED Hazardous Location Flood-fig12

Secure minimum 90°C wire to a terminal block. Do not use violet and gray dimming leads on the drivers.

GE -icon1CAUTION

RISK OF SHOCK OR DAMAGE
Follow applicable national and local electrical codes.
RISK OF DAMAGE
Verify supply voltage and wire insulation temperature rating match nameplate requirements.

Door Closing

GE current A1019051 Evolve LED Hazardous Location Flood-fig13

Hang door on hinge, rotate closed.

GE current A1019051 Evolve LED Hazardous Location Flood-fig14

Close and fasten door.

Cleaning

GE current A1019051 Evolve LED Hazardous Location Flood-fig15

Use mild soap/detergent.

GE current A1019051 Evolve LED Hazardous Location Flood-fig16

Rinse with cool low pressure water.

GE current A1019051 Evolve LED Hazardous Location Flood-fig17

Wipe dry with clean soft cloth.

Installation Guide

GE -icon1CAUTION

RISK OF DAMAGE. Do not use soap/detergent containing aromatic hydrocarbons.

Specification

Luminaire Approx. Net Wt. Dimensions IP Rating Classe IP

 

Effective Projected Area Ambient Temperature
EFMH 25 lbs (11.34 kg) 17.1 x 18.57 x 5.147 in

(434 x 471 x 130 mm)

 

IP66

1.96 ft2 (0.18 m²) -40° < ta < 50°C
EFHH 35 lbs (15.9 kg) 20 x 26.39 x 4.85 in

(508 x 670 x 123 mm)

3.51 ft2 (0.33 m²) -40° < ta < 50°C
Operating Temperature Code
 

Luminaire

Class I Div. 2 / Group A, B, C, & D Zone 2 Group IIA, IIB, IIC, IIB Plus Hydrogen

 

Class II, Div. 2 / Group F & G Zone 22

 

Class I, Div. 2 & Class II Div. 2 Simultaneous

 

EFMH T3A T3A T3A
EFHH T3A T3A T3A

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. This Class [A] RFLD complies with the Canadian standard ICES-005. Ce DEFR de la classe [A] est conforme à la NMB-005 du Canada.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to Current.

GE -logo1Evolve™ EFHH/EFMH-Series
© 2021 Current Lighting Solutions, LLC. All rights reserved. GE and the GE monogram are trademarks of the General Electric Company and are used under license. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions.
www.gecurrent.com
A1019051 (Rev 03/25/21) 99008144

Documents / Resources

GE current A1019051 Evolve LED Hazardous Location Flood [pdf] Installation Guide
A1019051, Evolve LED Hazardous Location Flood, A1019051 Evolve LED Hazardous Location Flood, LED Hazardous Location Flood, Location Flood, Flood

Leave a comment

Your email address will not be published.