INSTALLATION CONTACTOR
Instruction Leaflet DOC:INC2020

Technical information

Rating (A) AC-7a 20,25,40,63
Number of Poles (normally open) 2,4
Rated coil voltage 230V/ 50Hz
Rated insulation voltage (Ui) 500V
Voltage (Ue) 2P/4P 250V AC /400V AC
Rated impulse withstand voltage (Uimp) 2.5kV
Ambient temperature -5°C  to +60°C
Mounting35mm top hat din rail
IP RATING IP20 EN 60529
Complies with  IEC EN 61095

ATTENTION
9mm spacers must be fitted either side, when installing installation contactor beside protection device, to allow free air to circulate

Part number INC202 INC402 INC254 INC634 
Number of poles (N/O)2244
AC-7a (A)20402563
AC-7b (A)6.4158.520
Ith (thermal) (A)20402563
Holding VA16:484.64.66.5
Inrush VA9.2343453
Dissipated W1.21.61.62.1
Torque(control circuit)0.8Nm0.8Nm0.8Nm0.8Nm
Torque(power circuit)0.8Nm3.5Nm0.8Nm3.5Nm
Max. cable capacity4mm²16mm²4mm²16mm²
Module width18mm36mm36mm54mm

Dimensions

INC202 / INC402 / INC254

FuseBox INC2020 Contactor Leaflet - Dimensions 1

INC634

FuseBox INC2020 Contactor Leaflet - Dimensions 2

SPACERS

FuseBox INC2020 Contactor Leaflet - Dimensions 3

1b Installation contactors must be installed by a qualified electrician in accordance with the current IET Wiring Regulations BS 7671.
1c Total load must not exceed the rating of the installation contactor or any additional limitation.

Installation

2a Installation contactor range designed to fit FuseBox consumer units and modular enclosures.
2b Clip securely on to the din rail making sure the din rail clip at the bottom is pushed in, locking the installation contactor onto the din rail. Fit 9mm plastic spacer either side to allow free air to circulate.
2c Cut, dress and connect cables as shown in the wiring diagram on the front of the installation contactor

Connections

3a Before powering up the circuit check all connections are TORQUED. Loose connections cause fires!!!!

Testing

4a On completion of the installation, it must be tested in accordance with the latest edition of the IET Wiring Regulations for Electrical Installations (BS 7671).

FuseBox - LOGO

FuseBox
www.fusebox.co.uk

FuseBox INC2020 Contactor Leaflet - QR

http://www.fusebox.co.uk

After installation and testing of this product it is essential that the INSTRUCTION LEAFLET is available for reference