Fronius TS 100A-1 Smart Meter User Guide
Fronius TS 100A-1 Smart Meter

QR Code FIND MORE INFORMATION
manuals.fronius.com/html/4204260350

Perfect Welding / Solar Energy / Perfect Charging

Note Icon WARNING! Incorrect operation and incorrectly performed work can cause serious personal injury or material damage. The Fronius Smart Meter may only be installed and commissioned by trained personnel and only within the scope of the technical regulations. Before working with the device, read and understand all enclosed, printed and online documents! This document does not describe all of the possible system configurations.

FRONIUS INTERNATIONAL GMBH

www.fronius.com

SOFTWARE REQUIREMENTS
Fronius Data manager 2.0≥ 3.16.1 version
Fronius Symo Hybrid≥ 1.16.1 version
MEASURING INPUT
Nominal voltage (1-phase) range230 V (-30 % to +20 %)
Self-consumption – voltage path (max. voltage)≤ 8 VA
Nominal frequencyTolerance50 – 60 Hz45 – 65 Hz
Nominal current, lb5 A
Maximum current, Imax100 A
Starting current40 mA
Short-time overload(EN IEC 62053-21, EN IEC 62053-23)30 lmax / 0.001 s
Self-consumption – current path (max. current)≤ 1 W
Power factor Operating range(EN IEC 62053-21, EN IEC 62053-23)cosφ 0.5 ind – 0.8 cap
Current distortion factorIn acc. with EN 62053-21
OUTPUTRS485 communication (Electrically isolated from measuring input)
StandardAddressesRS485 – 3 conductors1 – 255
Baud rate9600, 19200 bit/s
Response time≤ 200 ms
INSULATION (EN IEC 62052-11, EN IEC 62053-21)
Installation categoryIII
Degree of pollution2
Insulation voltage4000 VAC RMS (1 min)
ELECTROMAGNETIC COMPATIBILITY
Emission testIn acc. with EN IEC 62052-11, EN 50470-3
Immunity testIn acc. with EN IEC 62052-11, EN 50470-3
OPERATING CONDITIONS
Reference temperature25 °C (± 5 °C)
Operating range-25 to +65 °C
Temperature limit for storage and transport-30 to +80 °C
Mechanical environment Electromechanical environmentM2E2
HOUSING
Housing2 modules according to DIN 43880
Sealable housing/terminal cover
ConnectionScrew connection
MountingCan be snapped onto 35 mm DIN rail
Housing materialNoryl, self-extinguishing
Degree of protection (EN 60529)IP51 housing, IP20 connections
Weight160 grams
TERMINALS – MEASURING INPUT
Wiremax. 25 mm²
Recommended torquemax. 2.8 Nm
TERMINALS – DATA OUTPUT
Wiremin 0.05 mm²
Recommended torquemax. 0.4 Nm

Detailed, country-specific warranty terms are available on: www.fronius.com/solar/warranty

  1. SWITCH OFF THE CIRCUIT BREAKER (Step: 1)
    SWITCH OFF THE CIRCUIT BREAKER
  2. MOUNT THE SMART METER (Step: 2)
    MOUNT THE SMART METER
  3. a 1 PHASE, 2 WIRES (Step: 3a)
    WIRES
    1. b 1 PHASE, 2 WIRES (Step: 3b)
      WIRES
  4. MOUNT THE PROTECTIVE COVER (Step: 4)
    MOUNT THE PROTECTIVE COVER
  5. CONNECT THE DATA CABLES (Step: 5)
    CONNECT THE DATA CABLES
  6. SET UP THE TERMINATING RESISTOR (Steps: 6-7)
    TERMINATING RESISTOR
  7. Connection
  8. MOUNT THE CONNECTOR COVERS (Step: 8)
    MOUNT THE CONNECTOR COVERS
  9. SWITCH ON THE CIRCUIT BREAKER (Step: 9)
    SWITCH ON THE CIRCUIT BREAKER
  10. NAVIGATE IN THE SETTINGS (Step: 10)
    Press Button Value up
    1 x
    page up / value up
    Press Button Value up
    1 x
    page down / value down
    2 sec. adjust / confirm
  11. ENTER THE SETTINGS (Step: 11)
    ENTER THE SETTINGS
  12. SETUP THE PASSWORD (Step: 12)
    Factory default:
    2633
    Factory default
  13. SETUP THE ADDRESS (Step: 13)
    Factory default:
    Modbus Address 001
    Factory Default
  14. EXIT THE SETTINGS (Step: 14)
    EXIT THE SETTINGS
  15. START UP THE SMART METER (Step: 15)
    Fronius Solar.start                 
    SMART METER
    Fronius Solar. start 
    App Store App
    Google Play

Fronius Logo