Fronius TS 100A-1 Smart Meter User Guide
FIND MORE INFORMATION
manuals.fronius.com/html/4204260350
Perfect Welding / Solar Energy / Perfect Charging
WARNING! Incorrect operation and incorrectly performed work can cause serious personal injury or material damage. The Fronius Smart Meter may only be installed and commissioned by trained personnel and only within the scope of the technical regulations. Before working with the device, read and understand all enclosed, printed and online documents! This document does not describe all of the possible system configurations.
FRONIUS INTERNATIONAL GMBH
SOFTWARE REQUIREMENTS | |
Fronius Data manager 2.0 | ≥ 3.16.1 version |
Fronius Symo Hybrid | ≥ 1.16.1 version |
MEASURING INPUT | |
Nominal voltage (1-phase) range | 230 V (-30 % to +20 %) |
Self-consumption – voltage path (max. voltage) | ≤ 8 VA |
Nominal frequencyTolerance | 50 – 60 Hz45 – 65 Hz |
Nominal current, lb | 5 A |
Maximum current, Imax | 100 A |
Starting current | 40 mA |
Short-time overload(EN IEC 62053-21, EN IEC 62053-23) | 30 lmax / 0.001 s |
Self-consumption – current path (max. current) | ≤ 1 W |
Power factor Operating range(EN IEC 62053-21, EN IEC 62053-23) | cosφ 0.5 ind – 0.8 cap |
Current distortion factor | In acc. with EN 62053-21 |
OUTPUTRS485 communication (Electrically isolated from measuring input) | |
StandardAddresses | RS485 – 3 conductors1 – 255 |
Baud rate | 9600, 19200 bit/s |
Response time | ≤ 200 ms |
INSULATION (EN IEC 62052-11, EN IEC 62053-21) | |
Installation category | III |
Degree of pollution | 2 |
Insulation voltage | 4000 VAC RMS (1 min) |
ELECTROMAGNETIC COMPATIBILITY | |
Emission test | In acc. with EN IEC 62052-11, EN 50470-3 |
Immunity test | In acc. with EN IEC 62052-11, EN 50470-3 |
OPERATING CONDITIONS | |
Reference temperature | 25 °C (± 5 °C) |
Operating range | -25 to +65 °C |
Temperature limit for storage and transport | -30 to +80 °C |
Mechanical environment Electromechanical environment | M2E2 |
HOUSING | |
Housing | 2 modules according to DIN 43880 |
Sealable housing/terminal cover | |
Connection | Screw connection |
Mounting | Can be snapped onto 35 mm DIN rail |
Housing material | Noryl, self-extinguishing |
Degree of protection (EN 60529) | IP51 housing, IP20 connections |
Weight | 160 grams |
TERMINALS – MEASURING INPUT | |
Wire | max. 25 mm² |
Recommended torque | max. 2.8 Nm |
TERMINALS – DATA OUTPUT | |
Wire | min 0.05 mm² |
Recommended torque | max. 0.4 Nm |
Detailed, country-specific warranty terms are available on: www.fronius.com/solar/warranty
- SWITCH OFF THE CIRCUIT BREAKER (Step: 1)
- MOUNT THE SMART METER (Step: 2)
- a 1 PHASE, 2 WIRES (Step: 3a)
- b 1 PHASE, 2 WIRES (Step: 3b)
- b 1 PHASE, 2 WIRES (Step: 3b)
- MOUNT THE PROTECTIVE COVER (Step: 4)
- CONNECT THE DATA CABLES (Step: 5)
- SET UP THE TERMINATING RESISTOR (Steps: 6-7)
- MOUNT THE CONNECTOR COVERS (Step: 8)
- SWITCH ON THE CIRCUIT BREAKER (Step: 9)
- NAVIGATE IN THE SETTINGS (Step: 10)
1 x page up / value up
1 x page down / value down
2 sec. adjust / confirm - ENTER THE SETTINGS (Step: 11)
- SETUP THE PASSWORD (Step: 12)
Factory default: 2633 - SETUP THE ADDRESS (Step: 13)
Factory default: Modbus Address 001 - EXIT THE SETTINGS (Step: 14)
- START UP THE SMART METER (Step: 15)
Fronius Solar. start