Fronius logoOperating Instructions
RI FB Inside/i
RI MOD/i CC-M40 Ethernet/IP-2PFronius RI FB Inside Bus Module

General

Safety
warning - 1 WARNING!
Incorrect operation and faulty work can cause serious personal injury and material damage.
All work and functions described in this document must be performed only by trained specialist personnel who have read and understood the following documents in full:
▶ this document
▶ the Operating Instructions of the robot interface “RI FB Inside/i”
▶ all documents relating to system components, especially the safety rules

Connections and Indicators on RJ 45 moduleFronius RI FB Inside Bus Module - Connections

1 TX+
2 TX-
3 RX+
4
5
Not normally used; to ensure signal completeness, these pins must be interconnected
and, after passing through a filter circuit, must terminate at the ground conductor (PE).
6 RX-
7
8
Not normally used; to ensure signal completeness, these pins must be interconnected
and, after passing through a filter circuit, must terminate at the ground conductor (PE).
9 Connection/activity at connection 2 LED
10 MS LED (module status)
11 RJ-45 Ethernet connection 2
12 RJ-45 Ethernet connection 1
13 Connection/activity at connection 1 LED
14 NS LED (network status)
NS LED (Network Status)
Status Meaning
Off No supply voltage or no IP address
Lights up green Online, one or more connections established (CIP category 1 or 3)
Flashes green Online, no connections established
NS LED (Network Status)
Lights up red Double IP address, serious error
Flashes red Overrun of time for one or more connections (CIP category 1 or 3)
NS LED (Network Status)
Lights up red Double IP address, serious error
Flashes red Overrun of time for one or more connections (CIP category 1 or 3)
MS LED (Module Status)
Status Meaning
Off No supply voltage
Lights up green Controlled by a Scanner in Run state and, if CIP Sync is enabled, time is synchronized to a Grandmaster clock
Flashes green Not configured, Scanner in Idle state, or, if CIP Sync is enabled, time is synchronized Grandmaster clock
Lights up red Major error – exception state, serious fault, etc.
Flashes red Correctable error – the module is configured, but there is a difference between the parameters stored and the parameters used (configuration process image, IP ad- dress)
Connection/Activity LED
Status Meaning
Off No connection, no activity
Lights up green Connection established (100 Mbit/s)
Flickers green Activity (100 Mbit/s)
Lights up yellow Connection established (10 Mbit/s)
Flickers yellow Activity (10 Mbit/s)

Connections and Indicators on M12 module

Fronius RI FB Inside Bus Module - Indicators

(1) TXD+
(2) RXD+
(3) TXD-
(4) RXD-
(5) Shield
(6) MS LED (module status)
(7) Connection/activity at M12 connection 2 LED
(8) M12 connection 2
(9) NS LED (network status)
(10) Connection/activity at M12 connection 1 LED
(11) M12 connection 1
NS LED (Network Status)
Status Meaning
Off No supply voltage or no IP address
Lights up green Online, one or more connections established (CIP category 1 or 3)
Flashes green Online, no connections established
Lights up red Double IP address, serious error
Flashes red Overrun of time for one or more connections (CIP category 1 or 3)
MS LED (Module Status)
Status Meaning
Off No supply voltage
Lights up green Controlled by a Scanner in Run state and, if CIP Sync is enabled, time is synchronized to a Grandmaster clock
Flashes green Not configured, Scanner in Idle state, or, if CIP Sync is enabled, time is synchronized Grandmaster clock
Lights up red Major error – exception state, serious fault, etc.
Flashes red Correctable error – the module is configured, but there is a difference between the parameters stored and the parameters used (configuration process image, IP ad- dress)
Connection/Activity LED
Status Meaning
Off No connection, no activity
Lights up green Connection established (100 Mbit/s)
Flickers green Activity (100 Mbit/s)
Lights up yellow Connection established (10 Mbit/s)
Flickers yellow Activity (10 Mbit/s)

Data Transfer Properties

Data Transfer Properties Transfer technology
Ethernet
Medium
When selecting the cables and plugs, the ODVA recommendation for the planning and installation of EtherNet/IP systems must be observed.
The EMC tests were carried out by the manufacturer with the cable  EC5ES8VG0030M40M40-F.
Transmission speed
10 Mbit/s or 100 Mbit/s
Bus connection
RJ-45 Ethernet / M12

Configuration Parameters
In some robot control systems, it may be necessary to state the configuration parameters described here so that the bus module can communicate with the robot.

Parameter Value Description
Vendor ID 0534hex (1332dez) Fronius International GmbH
Device Type 000Chex (12dez) Communication adapter
Product Code 0301hex (769dez) Fronius FB Inside Ethernet/IP-2-Port
Product Name Fronius-FB-Inside-EtherNetIP(TM)
Image Type Instance Type Instance Name Instance Description Instance Number Size [Byte]
Standard Image Produ- cing In- stance Input Da- ta Stan-dard Data from power source to robot 100 40
Con- suming Instance Output Data Standard Data from robot to power source 150 40
Economy Image Produ- cing In- stance Input Da- ta Stan- dard Data from power source to robot 101 16
Con- suming Instance Output Data Standard Data from robot to power source 151 16
Retrofit Image Produ- cing In- stance Input Da- ta Stan- dard Data from power source to robot 102 37
Con- suming Instance Output Data Standard Data from robot to power source 152 37

Configuration of robot interface

Dip-switch functionFronius RI FB Inside Bus Module - robot interface

The dip-switch (1) on the robot interface RI FB Inside/i is used to configure

  • the process data width
  • the node address/IP address

At the factory all positions of the dip switch are set to OFF (3).
This corresponds to the binary value 0.
The position (2) corresponds to the binary value 1.

Configuration of the process data width

Dip switch Configuration
8 7 6 5 4 3 2 1
OFF OFF Standard image 320 Bit
OFF ON Economy image 128 Bit
ON OFF Retro Fit
Scope dependent on bus module
ON ON Not used

The process data width defines the scope of the transferred data volume.
The kind of data volume that can be transferred depends on

  • the robot controls
  • the number of welding machines
  • the type of welding machines
  • “Intelligent Revolution”
  • “Digital Revolution” (Retro Fit)

Set node address with dip switch (example)

Dip switch Node address
8 7 6 5 4 3 2 1
OFF OFF OFF OFF OFF ON 1
OFF OFF OFF OFF ON OFF 2
OFF OFF OFF OFF ON ON 3
ON ON ON ON ON OFF 62
ON ON ON ON ON ON 63

The node address is set with positions 1 to 6 of the dip switch.
The configuration is carried out in binary format. This results in a configuration range of 1 to 63 in decimal format
NOTE!
After every change of the configurations of the dip switch settings, the inter- face needs to be restarted so that the changes will take effect.
(Restart = interrupting and restoring the power supply or executing the relevant function on the website of the power source)
Setting the IP Address
Upon delivery the node address is set to 0 using the dip switch.
This corresponds to the following IP settings:

  • IP address: 0.0.0.0
  • Subnet mask: 0.0.0.0
  • Default gateway: 0.0.0.0

The IP address can be configured in two ways:

  • Using the DIP switch within the range defined by 192.168.0.xx (xx = DIP switch setting = 1 to 63)
  • If the dip switch is set to 0, using the following configuration tools:
  • Using the website of the welding machine

NOTE!
If the IP address is again set to higher than 0 with the dip switch, the relevant IP address will be configured to the range of 1 to 63 after restarting the robot interface.
A node address previously configured by a configuration tool is overwritten.

NOTE!
If configurations have already been made, the network configurations can be restored to factory settings in two ways:
▶ set all dip switches back to 0
▶ with the button Restore factory settings on the website of the welding machine

The Website of the welding machine

The welding machine has its own website, the SmartManager.
As soon as the welding machine has been integrated into a network, the SmartManager can be opened via the IP address of the welding machine.
Depending on the system configuration and software upgrades, the SmartManager may contain the following entries:

  • Overview
  • Update
  • Screenshot
  • Save and restore
  • Function packages
  • Job data
  • Overview of characteristics
  • RI FB INSIDE/i

Call up the welding machine SmartManager and log inFronius RI FB Inside Bus Module - machine

  1. Presettings / System/Information ==> note down IP address of the welding machine
  2. Enter the IP address into the search field of the browser
  3. Enter username and password
    Factory setting:
    Username = admin
    Password = admin
  4. Confirm displayed message

The welding machine SmartManager is displayed.

Input and output signals

Data types 

The following data types are used:

  • UINT16 (Unsigned Integer)
    Whole number in the range from 0 to 65535
  • SINT16 (Signed Integer)
    Whole number in the range from -32768 to 32767

Conversion examples:

  • for a positive value (SINT16) e.g. desired wire speed x factor 12.3 m/min x 100 = 1230dec = 04CEhex
  • for a negative value (SINT16) e.g. arc correction x factor -6.4 x 10 = -64dec = FFCOhex

Availability of Input Signals
The input signals listed below are available from firmware V4.1.x for all Inside/i systems.
Input signals (from robot to power source)

Address Signal Activity / data type Range Factor Process image
Relative Absolu- te Standard Economy
WORD BYTE BIT BIT
0 0 0 0 Welding Start Increa- sing Fronius RI FB Inside Bus Module - Symbol Fronius RI FB Inside Bus Module - Symbol
1 1 Robot ready High
2 2 Working mode Bit 0 High See table Value Range for Working Mode on page 44
3 3 Working mode Bit 1 High
4 4 Working mode Bit 2 High
5 5 Working mode Bit 3 High
6 6 Working mode Bit 4 High
7 7
1 0 8 Gas on Increa- sing
1 9 Wire forward Increa- sing
2 10 Wire backward Increa- sing
3 11 Error quit Increa- sing
4 12 Touch sensing High
5 13 Torch blow out Increa- sing
6 14 Processline selection Bit 0 High See table Value range Process li- ne selection on page 45
7 15 Processline selection Bit 1 High
Address Signal Activity / data type Range Factor Process image
Relative Absolu- te Standard Economy
WORD BYTE BIT BIT
1 2 0 16 Welding simulation High Fronius RI FB Inside Bus Module - Symbol Fronius RI FB Inside Bus Module - Symbol
1 17 Welding process MIG/MAG: 1)
Synchro pulse on
High
Welding process WIG: 2)  TAC on High
2 18 Welding process WIG: 2) Cap shaping High
3 19
4 20
5 21 Booster manual High
6 22 Wire brake on High
7 23 Torchbody Xchange High
3 0 24
1 25 Teach mode High
2 26
3 27
4 28
5 29 Wire sense start Increa- sing
6 30 Wire sense break Increa- sing
7 31
Address Signal Activity / data type Range Factor Process image
Relative Absolu- te Standard Economy
WORD BYTE BIT BIT
2 4 0 32 TWIN mode Bit 0 High See table Value Range for TWIN Mode on page 45 Fronius RI FB Inside Bus Module - Symbol Fronius RI FB Inside Bus Module - Symbol
1 33 TWIN mode Bit 1 High
2 34
3 35
4 36
5 37 Documentation mode High See table Value Range for Docu- mentation Mode on page 45
6 38
7 39
5 0 40
1 41
2 42
3 43
4 44
5 45
6 46
7 47 Disable process controlled correction High
Address Signal Activity / data type Range Factor Process image
Relative Absolu- te Standard Economy
WORD BYTE BIT BIT
3 6 0 48 Fronius RI FB Inside Bus Module - Symbol Fronius RI FB Inside Bus Module - Symbol
1 49
2 50
3 51
4 52
5 53
6 54
7 55
7 0 56 ExtInput1 => OPT_Output 1 High
1 57 ExtInput2 => OPT_Output 2 High
2 58 ExtInput3 => OPT_Output 3 High
3 59 ExtInput4 => OPT_Output 4 High
4 60 ExtInput5 => OPT_Output 5 High
5 61 ExtInput6 => OPT_Output 6 High
6 62 ExtInput7 => OPT_Output 7 High
7 63 ExtInput8 => OPT_Output 8 High
4 8-9 0–7 64–79 Welding characteristic- / Job number UINT16 0 to 1000 1 Fronius RI FB Inside Bus Module - Symbol Fronius RI FB Inside Bus Module - Symbol
5 10 – 11 0-7 80-95 Welding process MIG/MAG: 1)
Constant Wire:
Wire feed speed command va- lue
SINT16 -327,68 to
327,67
[m/min]
100 Fronius RI FB Inside Bus Module - Symbol Fronius RI FB Inside Bus Module - Symbol
Welding process WIG: 2)
Main- / Hotwire current com- mand value
UINT16 0 to
6553,5 [A]
10
For job-mode: Power correction SINT16 -20,00 to
20,00 [%]
100
Address Signal Activity / data type Range Factor Process image
Relative Absolu- te Standard Economy
WORD BYTE BIT BIT
6 12 – 13 0-7 96-111 Welding process MIG/MAG: 1)
Arclength correction
SINT16 -10,0 to
10,0
[Schritte]
10 Fronius RI FB Inside Bus Module - Symbol Fronius RI FB Inside Bus Module - Symbol
Welding process
MIG/MAG Standard-Manuel:
Welding voltage
UINT16 0,0 to
6553,5 [V]
10
Welding process WIG: 2)
Wire feed speed command va- lue
SINT16 -327,68 to
327,67
[m/min]
100
For job-mode:
Arclength correction
SINT16 -10,0 to
10,0
[Schritte]
10
Welding process Constant Wire:
Hotwire current
UINT16 0,0 to
6553,5 [A]
10
7 14 – 15 0-7 112-127 Welding process MIG/MAG: 1)
Pulse-/dynamic correction
SINT16 -10,0 to
10,0
[steps]
10 Fronius RI FB Inside Bus Module - Symbol Fronius RI FB Inside Bus Module - Symbol
Welding process
MIG/MAG Standard-Manuel:
Dynamic
UINT16 0,0 to
10,0
[steps]
10
Welding process WIG: 2) Wire correction SINT16 -10,0 to
10,0
[steps]
10
8 16 – 17 0-7 128-143 Welding process MIG/MAG: 1)
Wire retract correction
UINT16 0,0 to
10,0
[steps]
10 Fronius RI FB Inside Bus Module - Symbol
Welding process WIG: 2)
Wire retract end
UINT16 OFF, 1 to
50
[mm]
1
9 18- 19 0-7 144-159 Welding speed UINT16 0,0 to
1000,0
[cm/min]
10 Fronius RI FB Inside Bus Module - Symbol
Address Signal Activity / data type Range Factor Process image
Relative Absolu- te Standard Economy
WORD BYTE BIT BIT
10 20 – 21 0-7 160-175 Process controlled correction See table Value range for Pro- cess controlled correction on page 45 Fronius RI FB Inside Bus Module - Symbol
11 22 – 23 0-7 176-191 Welding process WIG: 2)
Wire positioning start
Fronius RI FB Inside Bus Module - Symbol
12 24 – 25 0-7 192-207 Fronius RI FB Inside Bus Module - Symbol
13 26 – 27 0-7 208-223 Fronius RI FB Inside Bus Module - Symbol
14 28 – 29 0-7 224-239 Fronius RI FB Inside Bus Module - Symbol
15 30 – 31 0-7 240-255 Wire forward / backward length UINT16 OFF / 1 to 65535 [mm] 1 Fronius RI FB Inside Bus Module - Symbol
16 32 – 33 0-7 256-271 Wire sense edge detection UINT16 OFF / 0,5
to 20,0 [mm]
10 Fronius RI FB Inside Bus Module - Symbol
17 34 – 35 0-7 272-287 Fronius RI FB Inside Bus Module - Symbol
18 36 – 37 0-7 288-303 Fronius RI FB Inside Bus Module - Symbol
19 38 – 39 0-7 304-319 Seam number UINT16 0 to 65535 1 Fronius RI FB Inside Bus Module - Symbol
  1. MIG/MAG Puls-Synergic, MIG/MAG Standard-Synergic, MIG/MAG Standard-Manuel, MIG/MAG PMC, MIG/MAG, LSC
  2. WIG coldwire, WIG hotwire

Value Range for Working Mode

Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Description
0 0 0 0 0 Internal parameter selection
0 0 0 0 1 Special 2-step mode characteristics
0 0 0 1 0 Job mode
0 1 0 0 0 2-step mode characteristics
0 1 0 0 1 2-step MIG/MAG standard manual
1 0 0 0 0 Idle Mode
1 0 0 0 1 Stop coolant pump
1 1 0 0 1 R/L-Measurement

Value range for operating mode
Value range Process line selection

Bit 1 Bit 0 Description
0 0 Process line 1 (default)
0 1 Process line 2
1 0 Process line 3
1 1 Reserved

Value range for process line selection
Value Range for TWIN Mode

Bit 1 Bit 0 Description
0 0 TWIN Single mode
0 1 TWIN Lead mode
1 0 TWIN Trail mode
1 1 Reserved

Value range for TWIN mode
Value Range for Documentation Mode

Bit 0 Description
0 Seam number of welding machine (internal)
1 Seam number of robot (Word 19)

Value range for documentation mode
Value range for Process controlled correction

Process Signal Activity / data type Value range configuration range Unit Factor
PMC Arc length stabilizer SINT16 -327.8 to +327.7
0.0 to +5.0
Volts 10

Value range for process-dependent correction
Availability of Output Signals
The output signals listed below are available from firmware V4.1.x for all Inside/i systems.
Output Signals (from Power Source to Robot)

Address Signal Activity / data type Range Factor Process image
relative absolute Standard Economy
WORD BYTE BIT BIT
0 0 0 0 Heartbeat Powersource High/Low 1 Hz Fronius RI FB Inside Bus Module - Symbol Fronius RI FB Inside Bus Module - Symbol
1 1 Power source ready High
2 2 Warning High
3 3 Process active High
4 4 Current flow High
5 5 Arc stable- / touch signal High
6 6 Main current signal High
7 7 Touch signal High
1 0 8 Collisionbox active High 0 = collisi- on or ca- ble break
1 9 Robot Motion Release High
2 10 Wire stick workpiece High
3 11
4 12 Short circuit contact tip High
5 13 Parameter selection in- ternally High
6 14 Characteristic number valid High
7 15 Torch body gripped High
Address Signal Activity / data type Range Factor Process image
relative absolute Standard Economy
WORD BYTE BIT BIT
1 2 0 16 Command value out of range High Fronius RI FB Inside Bus Module - Symbol Fronius RI FB Inside Bus Module - Symbol
1 17 Correction out of range High
2 18
3 19 Limitsignal High
4 20
5 21
6 22 Main supply status Low
7 23
3 0 24 Sensor status 1 High See table Assign- ment of Sensor Sta- tuses 1–4 on page 49
1 25 Sensor status 2 High
2 26 Sensor status 3 High
3 27 Sensor status 4 High
4 28
5 29
6 30
7 31
2 4 0 32 Fronius RI FB Inside Bus Module - Symbol Fronius RI FB Inside Bus Module - Symbol
1 33
2 34
3 35 Safety status Bit 0 High See table Value ran- ge Safety status on page 50
4 36 Safety status Bit 1 High
5 37
6 38 Notification High
7 39 System not ready High
5 0 40
1 41
2 42
3 43
4 44
5 45
6 46
7 47
Address Signal Activity / data type Range Factor Process image
relative absolute Standard Economy
WORD BYTE BIT BIT
3 6 0 48 Process Bit 0 High See table Value Range for Process Bit on page 50 Fronius RI FB Inside Bus Module - Symbol Fronius RI FB Inside Bus Module - Symbol
1 49 Process Bit 1 High
2 50 Process Bit 2 High
3 51 Process Bit 3 High
4 52 Process Bit 4 High
5 53
6 54 Touch signal gas nozzle High
7 55 TWIN synchronization active High
7 0 56 ExtOutput1 <= OPT_In- put1 High
1 57 ExtOutput2 <= OPT_In- put2 High
2 58 ExtOutput3 <= OPT_In- put3 High
3 59 ExtOutput4 <= OPT_In- put4 High
4 60 ExtOutput5 <= OPT_In- put5 High
5 61 ExtOutput6 <= OPT_In- put6 High
6 62 ExtOutput7 <= OPT_In- put7 High
7 63 ExtOutput8 <= OPT_In- put8 High
4 8- 9 0-7 64-79 Welding voltage UINT16 0.0 to
655.35 [V]
100 Fronius RI FB Inside Bus Module - Symbol Fronius RI FB Inside Bus Module - Symbol
5 10 – 11 0-7 80-95 Welding current UINT16 0.0 to 6553.5 [A] 10 Fronius RI FB Inside Bus Module - Symbol Fronius RI FB Inside Bus Module - Symbol
6 12 – 13 0-7 96-111 Wire feed speed SINT16 -327.68 to
327.67 [m/
min]
100 Fronius RI FB Inside Bus Module - Symbol Fronius RI FB Inside Bus Module - Symbol
7 14 – 15 0-7 112-127 Actual real value for seam tracking UINT16 0 to 6.5535 10000 Fronius RI FB Inside Bus Module - Symbol Fronius RI FB Inside Bus Module - Symbol
8 16 – 17 0-7 128-143 Error number UINT16 0 to 65535 1 Fronius RI FB Inside Bus Module - Symbol
9 18 – 19 0-7 144-159 Warning number UINT16 0 to 65535 1 Fronius RI FB Inside Bus Module - Symbol
Address Signal Activity / data type Range Factor Process image
relative absolute Standard Economy
WORD BYTE BIT BIT
10 20 – 21 0-7 160-175 Motor current M1 SINT16 -327.68 to
327.67 [A]
100 Fronius RI FB Inside Bus Module - Symbol
11 22 – 23 0-7 176-191 Motor current M2 SINT16 -327.68 to
327.67 [A]
100 Fronius RI FB Inside Bus Module - Symbol
12 24 – 25 0-7 192-207 Motor current M3 SINT16 -327.68 to
327.67 [A]
100 Fronius RI FB Inside Bus Module - Symbol
13 26 – 27 0-7 208-223 Fronius RI FB Inside Bus Module - Symbol
14 28 – 29 0-7 224-239 Fronius RI FB Inside Bus Module - Symbol
15 30 – 31 0-7 240-255 Fronius RI FB Inside Bus Module - Symbol
16 32 – 33 0-7 256-271 Wire position SINT16 -327.68 to
327.67
[mm]
100 Fronius RI FB Inside Bus Module - Symbol
17 34 – 35 0-7 272-287 Fronius RI FB Inside Bus Module - Symbol
18 36 – 37 0-7 288-303 Fronius RI FB Inside Bus Module - Symbol
19 38 – 39 0-7 304-319 Fronius RI FB Inside Bus Module - Symbol

Assignment of Sensor Statuses 1–4

Signal Description
Sensor status 1 OPT/i WF R wire end (4,100,869)
Sensor status 2 OPT/i WF R wire drum (4,100,879)
Sensor status 3 OPT/i WF R ring sensor (4,100,878)
Sensor status 4 Wire buffer set CMT TPS/i (4,001,763)

Assignment of sensor statuses
Value range Safety status

Bit 1 Bit 0 Description
0 0 Reserve
0 1 Hold
1 0 Stop
1 1 Not installed / active

Value range Safety status
Value Range for Process Bit

Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Description
0 0 0 0 0 No internal parameter selection or process
0 0 0 0 1 MIG/MAG pulse synergic
0 0 0 1 0 MIG/MAG standard synergic
0 0 0 1 1 MIG/MAG PMC
0 0 1 0 0 MIG/MAG LSC
0 0 1 0 1 MIG/MAG standard manual
0 0 1 1 0 Electrode
0 0 1 1 1 TIG
0 1 0 0 0 CMT
0 1 0 0 1 ConstantWire
0 1 0 1 0 ColdWire
0 1 0 1 1 DynamicWire

Value Range for Process Bit
Value Range for Function status

Bit 1 Bit 0 Description
0 0 Inactive
0 1 Idle
1 0 Finished
1 1 Error

Value range for function status

Retrofit Image Input and Output Signals

Input Signals
The signals listed below are available from firmware V1.6.0 for all Inside/i systems.

Serial no. Signal designation Range Action
E01 Welding on High
E02 Robot ready High
E03 Operating mode bit 0 See table Value range for opera- ting modes on page 52 High
E04 Operating mode bit 1 High
E05 Operating mode bit 2 High
E06
E07
E08
E09 Gas test High
E10 Wire forward High
E11 Wire backward High
E12 Error quit High
E13 Position search High
E14 Purge welding torch High
E15
E16
E17 – E24 Job number 0 to 99
E25 – E31 Program number 1 to 127
E32 Welding simulation High
Only in Job mode (E17 – E32):
E17 – E31 Job number 0 to 999
E32 Welding simulation High
E33 – E40 Output set value – Low byte 0 to 65535

(0 to 100%)

E41 – E48 Output set value – High byte
E49 – E56 Arc length correction, set value Low byte 0 to 65535
(-30 to +30%)
E57–E64 Arc length correction, set value High byte
E65 – E72 Pulse or dynamic correction 0 to 255
(-5 to +5%)
E73–E80
E81 – E88
E89 – E96
Serial no. Signal designation Range Action
E97 – E104 Welding speed – Low byte 0 to 65535
(0 to 6553.5 cm/ min)
E105 – E112 Welding speed – High byte
E113 SynchroPulse on High
E114
E115
E116
E117 Output full range (0 to 30 m) High
E118
E119
E120
E121 – E128
E129 – E296

Value range for operating modes

Bit 2 Bit 1 Bit 0 Description
0 0 0 MIG/MAG Synergic welding
0 0 1 MIG/MAG Synergic welding
0 1 0 Job mode
0 1 1 Internal parameter selection

Output Signals
The signals listed below are available from firmware V1.6.0 for all Inside/i systems.

Seq. no Signal designation Range Action
A01 Arc stable High
A02 Limit signal High
A03 Process active High
A04 Main current signal High
A05 Welding torch collision protection High
A06 Power source ready High
A07 Communication ready High
A08 Life Cycle Toggle Bit (250ms) High
A09 – A16
A17 – A24
A25
Seq. no Signal designation Range Action
A26
A27
A28 Wire present
A29 Short circuit time exceeded High
A30
A31
A32 Power out of range High
A33 – A40 Welding voltage actual value – Low byte 0 to 65535
(0 to 100 V)
A41 – A48 Welding voltage actual value – High byte
A49 – A56 Welding current actual value – Low byte 0 to 65535
(0 to 1000 A)
A57 – A64 Welding current actual value – High byte
A65 – A72 Motor current 0 to 255
(0 to 5 A)
A73 – A80
A81 – A88
A89 – A96
A97 – A104 Wire speed – Low byte 0 to vDmax
A105 – A112 Wire speed – High byte
A113 – A120
A121 – A128
A129 – A296

Fronius logoFronius RI FB Inside Bus Module - Bar Code42,0410,1916
037-17072024Fronius RI FB Inside Bus Module - CR CODEspareparts.fronius.com
Fronius RI FB Inside Bus Module - Symbol 1 SPARE PARTS ONLINE
Fronius International GmbH
Froniusstrafve 1
4643 Pettenbach Austria
contact@fronius.com
www.fronius.com
At www.fronius.com/contact you will find the contact details
of all Fronius subsidiaries and Sales & Service Partners.

Documents / Resources

Fronius RI FB Inside Bus Module [pdf] Instruction Manual
42, 0410, 1916, RI FB Inside Bus Module, RI FB Inside, Bus Module, Module

References

Leave a comment

Your email address will not be published. Required fields are marked *