BELEY 002

Manuel d'utilisation du manomètre numérique BELEY pour systèmes de chauffage, ventilation et climatisation

Modèle: 002

Introduction

The BELEY Digital Manifold HVAC Gauge Set is an intelligent electronic instrument designed to assist in the installation, testing, and maintenance of refrigeration equipment such as air conditioners, refrigerators, and cold storage units. This comprehensive gauge set features dual pressure and temperature testing capabilities, a clear digital readout, multi-unit switching, various functional modes, and a built-in refrigerant database.

BELEY Digital Manifold HVAC Gauge Set with hoses, temperature clips, and user manual

Figure 1: BELEY Digital Manifold HVAC Gauge Set components.

Qu'y a-t-il dans la boîte

À l'ouverture du colis, vérifiez que tous les éléments suivants sont inclus :

  • 1 x Manomètre numérique
  • 2 x Temperature Clips
  • 3 x 59-inch Hoses (Red, Yellow, Blue)
  • 1 x Manuel d'utilisation

Installation

Before operating the device, ensure proper setup to achieve accurate measurements and safe operation.

  1. Raccordez les tuyaux de réfrigérant :

    Attach the 59-inch hoses to the corresponding ports on the digital manifold gauge. The gauge features 1/4-inch standard interface designs for secure connections. Ensure all connections are tight to prevent leaks.

    Close-up of the manifold gauge with hoses connected.Close-up of the manifold gauge with hoses connected.

    Figure 2: Connecting the refrigerant hoses to the manifold gauge.

  2. Raccordement des capteurs de température :

    Plug the two temperature clips into the designated ports on the top of the manifold gauge. These clips are designed to grip pipes for quick and accurate temperature measurements.

    Temperature clips designed to grip pipes for quick temperature measurements.

    Figure 3: Temperature clips for pipe temperature measurement.

  3. Mise sous tension :

    Press the power button to turn on the digital manifold gauge. The LCD backlight will illuminate, displaying the initial readings.

Mode d'emploi

The BELEY Digital Manifold Gauge offers multiple functions for comprehensive HVAC system analysis.

1. Afficher plusview

The large-size liquid crystal display provides clear and easy-to-read data. It shows dual pressure and dual temperature readings simultaneously.

Intelligent digital display showing pressure and temperature readings, compatible with 93 refrigerants.

Figure 4 : Affichage numérique intelligent montrant différents paramètres.

2. Refrigerant Mode

The device has a built-in database of 93 types of refrigerants, including R134A, R290, R404A, R407C, R410A, R507A, R744(Co2), R32, and R-1234yf. You can select the appropriate refrigerant for your system.

  • Use the "R+" and "R-" buttons to navigate through the refrigerant types.
  • The display will show the selected refrigerant and corresponding pressure-evaporation temperature data.
  • The gauge automatically calculates subcooling and superheat values, providing direct operational data.
Evaporation pressure and temperature test display, showing temperature and pressure in kPa.

Figure 5: Evaporation Pressure & Temperature Test.

Condensing pressure and temperature test display, showing temperature and pressure in kPa.

Figure 6: Condensing Pressure & Temperature Test.

3. Pressure Unit Conversion

The instrument supports automatic multi-unit pressure conversion to suit different measurement needs.

  • Press the "UNIT" button to cycle through available pressure units (e.g., psi, bar, kPa, inHg).

4. Conversion des unités de température

The device allows for automatic conversion between Celsius and Fahrenheit for temperature readings.

  • Appuyez sur le bouton « °C/°F » pour basculer entre Celsius et Fahrenheit.

5. Mesure du vide

The gauge can test the percentage of vacuum measurement, crucial for proper system evacuation.

Video 1: Demonstration of the BELEY Digital Manifold HVAC Gauge Set's features, including vacuum testing, refrigerant mode, and pressure unit conversion.

6. Test d'étanchéité sous pression

Perform a pressure leak measurement and record the leak time speed to identify system leaks.

  • Initiate the leak test function (refer to the specific button on the device, often labeled with a percentage or leak icon).
  • The gauge will display the initial pressure, measured pressure, and the difference value over time.
Pressure leak test display showing initial and measured pressure values over time.

Figure 7: Pressure Leak Test interface.

Entretien

Proper maintenance ensures the longevity and accuracy of your BELEY Digital Manifold HVAC Gauge Set.

  • Nettoyage: Essuyez l'appareil avec un chiffon doux et sec. N'utilisez pas de nettoyants abrasifs ni de solvants.
  • Stockage: Store the gauge set in its protective case in a cool, dry place when not in use.
  • Entretien des tuyaux : The hoses are designed to be tough, scratch-resistant, and flexible. Avoid sharp bends or kinks that could damage them. Inspect hoses regularly for wear and tear.
  • Remplacement de la batterie : If the display becomes dim or the device does not power on, replace the batteries as per the instructions in the included user manual.

Dépannage

This section addresses common issues you might encounter with your digital manifold gauge.

ProblèmeCause possibleSolution
La jauge ne s'allume pas.Piles faibles ou mortes.Remplacer les piles.
Relevés de pression inexacts.Loose hose connections; incorrect refrigerant selected; sensor calibration needed.Check all hose connections for tightness. Ensure the correct refrigerant type is selected. Refer to the full user manual for calibration procedures if necessary.
Les relevés de température sont erronés.Temperature clips not properly attached; faulty sensor.Ensure temperature clips are securely attached to the pipes. If issues persist, contact customer support.
Cannot switch units.Button malfunction; temporary software glitch.Press the UNIT/°C/°F button firmly. Try restarting the device.

Caractéristiques

Key technical specifications for the BELEY Digital Manifold HVAC Gauge Set:

  • Marque: BELEY
  • Numéro de modèle : 002
  • Matériel: High-strength engineering plastic and flexible non-slip silicone
  • Poids de l'article : 3 kilogrammes (environ 6.6 livres)
  • Code à barres : 733810031130
  • Base de données sur les fluides frigorigènes : Built-in 93 kinds (e.g., R134A, R290, R404A, R407C, R410A, R507A, R744(Co2), R32, R-1234yf)
  • Test de pression : Dual pressure test capability
  • Test de température : Dual temperature measurement capability
  • Afficher: Large-size liquid crystal display with LCD backlight
  • Interface: 1/4-inch standard interface for hoses
  • Précision: High-precision data acquisition unit
  • Pays d'origine : Chine

Garantie et assistance

BELEY provides the following warranty and support for this product:

  • Garantie de remboursement : Garantie de remboursement de 30 jours.
  • Garantie: Garantie 24 mois.
  • Plans de protection : Des plans de protection supplémentaires sont disponibles à l'achat, notamment des options de 2 et 3 ans.
  • Service client: For any inquiries or support needs, please contact BELEY customer service.

For more detailed information, please refer to the official user manual provided with your product or visit the BELEY Store on Amazon.

© 2024 BELEY. All rights reserved.