finder 58 Series ATEX Relay Interface Module Instruction Manual
finder 58 Series ATEX Relay Interface Module

RELAY INTERFACE MODULE – SAFETY INSTRUCTIONS

finder 58 Atex Relay Interface Modules - icon GENERAL SAFETY INFORMATION
These safety instructions refer to the installation, utilization and maintenance of 58 series relays to be used in potentially explosive areas due to the presence of combustible GAS.

The information of these instructions are only for qualified personnel. The relays and the sockets comply with the Essential Health and Safety Requirements for potentially explosive atmospheres provided by European Standards:
EN 60079-0 (2012+A11:2013), EN 60079-15(2010), EN 60079-7(2015)

Interface CodeSocket CodeRelay CodeModules Retaining clip
58.32.V.XXX.W0JK94.02.755.32.V.XXX.W0Y399.02.Z.XXX.QT94.71
58.32.V.XXX.W0JK94.04.755.32.V.XXX.W0Y399.02.Z.XXX.QT94.71
58.33.V.XXX.W0JK94.03.755.33.V.XXX.W0Y399.02.Z.XXX.QT94.71
58.34.V.XXX.W0JK94.04.755.34.V.XXX.W0Y399.02.Z.XXX.QT94.71
58.32.V.XXX.W00K94.02.755.32.V.XXX.W0Y394.71
58.32.V.XXX.W00K94.04.755.32.V.XXX.W0Y394.71
58.33.V.XXX.W00K94.03.755.33.V.XXX.W0Y394.71
58.34.V.XXX.W00K94.04.755.34.V.XXX.W0Y394.71

J = 4, 5, 6 – K = 8, 9 – V = 8, 9 – Q = 5, 9 – Y = 0, 2 – Z = 0, 9 – T = 8, 9 Marker tags 060.72; xxx**= supply voltage
 TRANSPORT, STORAGE
On receipt verify that the relay has not been damaged during transport. If damaged, do not install and immediately advise the transport service.

INSTALLATION

Installation must comply with the rules of the standard EN60079-14 or with the current national standards. Before the installation in an explosive atmosphere, the installer must ensure that the relay is suitable for the classified area in consideration of the different inflammable substances present in the installation area (please verify the marking on the relay cover before installation). The relay must be installed only by qualified people with knowledge of electrical apparatus for explosive gas atmospheres and electrical installations in hazardous areas and has to be done with the relay and equipment at standstill, electrically dead and locked against restart.
MARKING
finder 58 Atex Relay Interface Modules - icon 1 II 3G Ex ec nC IIC Gc -40°C ≤Ta≤+70°C

41, Specificmarking of explosion protection
finder 58 Atex Relay Interface Modules - icon 1 II – Component for surface plant (different from mines)
3 – Category 3: normal level of protection
GASG – explosive atmosphere due to presence of combustible gas vapour or mist
Ex ec – Increased safety
Ex nC – Sealed device (type of protection for category 3G)
IIC – Gas group
Gc – Equipment Protection Level
-40°C Ta +70°C – Ambient temperature
EPTI 17 ATEX 0195 UEPTI: laboratory which issued the certificate 17: year of issue of certificate0195: number of the certificate
U: Ex component

TECHNICAL CHARACTERISTICS

CONTACT CHARACTERISTICS

  • Contact configurations: 2 CO (58.32) – 3 CO (58.33) – 4 CO (58.34)
  • Rated Current / maximum peak current: 10 / 20 A (58.32) – 9 / 20 A (58.33) – 6 / 15 A (58.34)
  • Rated voltage / max switching voltage: 250 / 400 V AC (58.32) – 250 / 400 V AC (58.33) – 250 / 250 V AC (58.34)
  • Rated load-Category AC1: 2500 VA (58.32) – 2250 VA (58.33) – 1500 VA (58.34)
  • Rated load-Category AC15 (230 V AC): 500 VA (58.32) – 500 VA (58.33) – 350 VA (58.34)
  • Capacity for single phase motor (230 V AC): 0.37 kW (58.32) – 0.37 kW (58.33) – 0.125 kW (58.34)
  • Breaking capacity-Category DC1(30/110/220 V): 10 / 0.25 / 0.12 A (58.32) 9 / 0.25 / 0.12 A (58.33) 6 / 0.25 / 0.12 A (58.34)

CHARACTERISTICS OF COIL

  • Rated Voltage* (UN):
    12…230 V AC
    12…230 V DC
  • Rated power AC/DC : 1.5/1 VA (50 Hz)/W
  • Operating range:
    (0.8…1.1)UN AC
    (0.8…1.1)UN DC
  • Ambient temperature : (−40…+70)°C

* Special rated voltages on request
The supply voltage depends on the characteristics of the timer

finder 58 Atex Relay Interface Modules - iconAEG DVK6980HB 90cm Chimney Cooker Hood - icon 4 SPECIAL CONDITION FOR SAFE USE

Maximum temperature recorded on the surface of the component (obtained suppling the coil at the nominal voltage, Tamb 70°C) not exceed 111°C with the value of rated current as described at the point 5. The wire connected to the terminals of the socket, must be at least 2.5 mm².
On multi-installation, the value of the nominal current is reduced depending on the model of the interface. A pack connection of 5 interface, power supply = rated voltage,
T.amb = 70°C:

INTERFACEMAX PEAK CURRENT [A] (for pack)
58.32….JK7
58.33….JK6
58.34….JK5

The component must be inserted in an enclosure that meets the general requirements for enclosures listed in paragraph 4.10 of EN 60079-7. Connections must be carried out according to the requirements in paragraph 4.2.2 of EN 60079-7.

finder 58 Atex Relay Interface Modules - icon AEG DVK6980HB 90cm Chimney Cooker Hood - icon 4 MAINTENANCE AND REPAIR

The user must not open, modify or repair this relay in any way.

FINDER Spa con unico socio
10040 – Almese (TO) – ITALY
Tel. +39 011 9346211
www.findernet.com/it/ticket/add
www.findernet.com