EPEVER PWM-VS1024AU AU Series Solar Charge Controller
※ Thank you for selecting ViewStar AU series solar charge controller. Please read this manual carefully before using the product. |
Overview
Thank you for selecting the ViewStar AU series common positive solar charge controller. The VS-AU controller is a PWM charge controller with built in LCD display that adopts the most advanced digital technique. The multiple load control modes enable it can be widely used on solar home system, traffic signal, solar street light, solar garden lamp, etc. The features are listed below:
- Adopt high quality components of ST,IR and Infineon, make sure product using lifespan
- Terminals have UL and VDE certification, the product is more safer and more reliable
- Controller can work continuously at full load within the environmen temperature range from -25 to 55 ℃
- 3-Stage intelligent PWM charging:Bulk, Boost/Equalize, Float
- Support 3 charging options: Sealed, Gel, and Flooded
- LCD display design, dynamically displaying device’s operating data and working condition
- Double USB design, the power supply charge for electronic equipment
- With humanized button settings, operation will be more comfortable and convenient
- Multiple load control modes
- Energy statistics function
- Battery temperature compensation function
- Extensive Electronic protection
Product Features
① | LCD | ⑤ | Battery Terminals |
② | MENU Button | ⑥ | Load Terminals |
③ | RTS Port | ⑦ | SET Button |
④ | PV Terminals | ⑧ | USB Output Ports※ |
※ USB output ports provide the power supply of 5VDC/2.4A and have the short circuit protection
![]() | Optional Accessory: Name: Remote Temperature Sensor Model: RTS300R47K3.81A Acquisition of battery temperature for undertaking temperature compensation of control parameters, the standard length of the cable is 3m (length can be customized). The RTS300R47K3.81A connects to the port ③ on the controller. |
NOTE: Unplug the RTS, the temperature of battery will be set to a fixed value 25ºC.
Wiring
- Connect components to the charge controller in the sequence as shown above and pay much attention to the “+” and “-”. Please don’t insert the fuse or turn on the breaker during the installation. When disconnecting the system, the order will be reserved.
- After power on the controller, check the LCD on. Otherwise please refer to chapter 6.Always connect the battery first, in order to allow the controller to recognize the system voltage.
- The battery fuse should be installed as close to battery as possible. The suggested distance is within 150mm.
- The VS AU series is a positive ground controller. Any positive connection of solar, load or battery can be earth grounded as required.
![]() | NOTE: Please connect the inverter or other load that it has the large start current to the battery rather than to the controller, if the inverter or other load is necessary. |
Operation
Button | Function |
MENU button |
|
SET button |
|
LCD Display
- Status Description
Item Icon Status PV array Day Night No charging Charging PV Voltage, Current ,Power Battery Battery capacity, In Charging Battery voltage. current, temperature Battery type Load Load ON Load OFF Load Voltage, Current, Load mode - Browse interface
NOTE:
- When no operation, the interface will be automatic cycle, but the follow two interfaces not be display.
- Accumulative power zero clearing: Under PV power interface, press SET button andhold on 5s then the value blink, press SET button again to clear the value.
- Setting temperature unit: Under battery temperature interface, press SET button and hold on 5s to switch.
- Fault Indication
Status Icon Description Battery over discharged Battery level shows empty, battery frame blink, fault icon blink Battery over voltage Battery level shows full, battery frame blink, fault icon blink Battery Overheating Battery level shows current value, battery frame blink, fault icon blink Load failure Load overload ①,Load short circuit
① When load current reaches1.02-1.05 times 1.05-1.25 times, 1.25-1.35 times and 1.35-1.5 times more than nominal value, controller will automatically turn off loads in 50s, 30s,10s and 2s respectively
Load mode setting
Operating Steps:
Under load mode setting interface, press SET button and hold on 5s till the number begin flashing, then press MENU button to set the parameter, press SET button to confirm.
![]() | Timer 1 | ![]() | Timer 2 |
![]() | Light ON/OFF | ![]() | Disabled |
![]() | Load will be on for 1 hour since sunset | ![]() | Load will be on for 1 hour before sunrise |
![]() | Load will be on for 2 hours since sunset | ![]() | Load will be on for 2 hours before sunrise |
![]() | Load will be on for 3~13 hours since sunset | ![]() | Load will be on for 3~13 hours before sunrise |
![]() | Load will be on for 14 hours since sunset | ![]() | Load will be on for 14 hours before sunrise |
![]() | Load will be on for 15 hours since sunset | ![]() | Load will be on for 15 hours before sunrise |
![]() | Test mode | ![]() | Disabled |
![]() | Manual mode (Default load ON) | ![]() | Disabled |
NOTE: Please set Light ON/OFF, Test mode and Manual mode via Timer1. Timer2 will be disabled and display “2 n”.
Battery Type
- Operating Steps
Under Battery Voltage interface, press SET button and hold on 5s then enter into the interface of Battery type setting. After choosing the battery type by pressing MENU button, waiting for 5s or pressing SET button again to modify successfully.
- Battery Type
NOTE: Please refer to the battery voltage parameters table for the different battery type.
Protections
Protection | Conditions | Status |
PV Reverse Polarity | When the battery is correct connecting, the PV can be reversed. | The controller is not damage |
Battery Reverse Polarity | When the PV is not connecting, the battery can be reversed. | |
Battery Over Voltage | The battery voltage reaches to the OVD | Stop charging |
Battery Over Discharge | The battery voltage reaches to the LVD | Stop discharging |
Battery Overheating | Temperature sensor is higher than 65℃ | Output is OFF |
Temperature sensor is less than 55℃ | Output is ON | |
Controller Overheating | Temperature sensor is higher than 85℃ | Output is OFF |
Temperature sensor is less than 75℃ | Output is ON | |
Load Short Circuit | Load current ≥2.5 times rated current One short circuit, the output is OFF 5s; Two short circuit, the output is OFF 10s; Three short circuit, the output is OFF 15s; Four short circuit, the output is OFF 20s; Five short circuit, the output is OFF 25s; Six short circuit, the output is OFF | Output is OFF Clear the fault: Restart the controller or wait for one night-day cycle (night time>3 hours). |
Load Overload | Load current ≥2.5 times rated current 1.02-1.05 times, 50s, 1.05-1.25 times, 30s 1.25-1.35 times,10s 1.35-1.5 times 2s | Output is OFF Clear the fault: Restart the controller or wait for one night-day cycle (night time>3 hours). |
Damaged RTS | The RTS is short-circuited or damaged | Charging or discharging at 25℃ |
Troubleshooting
Faults | Possible reasons | Troubleshooting |
The LCD is off during daytime when sunshine falls on PV modules properly | P array disconnection | Confirm that PV wire connections are correct and tight |
Wire connection is correct, LCD not display |
|
|
![]() | Battery over voltage | Check if the battery voltage is higher than OVD point (over voltage disconnect voltage), and disconnect the PV. |
![]() | Battery over discharged | When the battery voltage is restored to or above LVR point (low voltage reconnect voltage), the load will recover |
![]() | Battery Overheating | The controller will automatically turn the system off. But while the temperature decline to be below 50 ºC, the controller will resume. |
![]() | Over load or Short circuit | Please reduce the number of electric equipments or check carefully loads connection. |
Disclaimer
This warranty does not apply under the following conditions:
- Damage from improper use or use in an unsuitable environment.
- PV or load current, voltage or power exceeding the rated value of controller.
- The controller is working temperature exceed the limit working environment temperature.
- User disassembly or attempted repair the controller without permission.
- The controller is damaged due to natural elements such as lighting.
- The controller is damaged during transportation and shipment.
Technical Specifications
Item | VS1024AU | VS2024AU | VS3024AU | VS3048AU | VS4524AU | VS4548AU | VS6024AU | VS6048AU |
Nominal system voltage | 12/24VDC Auto | 12/24/36/48VDC Auto | 12/24VDC Auto | 12/24/36/48VDC Auto | 12/24VDC Auto | 12/24/36/48VDC Auto | ||
Battery input voltage range | 9V~32V | 9V~64V | 9V~32V | 9V~64V | 9V~32V | 9V~64V | ||
Rated charge/discharge current | 10A@55℃ | 20A@55℃ | 30A@55℃ | 45A@55℃ | 60A@55℃ | |||
Max. PV open circuit voltage | 50V | 96V | 50V | 96V | 50V | 96V | ||
Battery type | Sealed(Default) / Gel / Flooded | |||||||
Equalize Charging Voltage※ | Sealed:14.6V/ Gel: No/ Flooded:14.8V | |||||||
Boost Charging Voltage※ | Sealed:14.4V/ Gel:14.2V/ Flooded:14.6V | |||||||
Float Charging Voltage※ | Sealed/Gel/Flooded:13.8V | |||||||
Low Voltage Reconnect Voltage※ | Sealed/Gel/Flooded:12.6V | |||||||
Low Voltage Disconnect Voltage※ | Sealed/Gel/Flooded:11.1V | |||||||
Self-consumption | ≤9.2mA/12V;≤11.7mA/24V; ≤14.5mA/36V;≤17mA/48V | |||||||
Temperature compensation coefficient | -3mV/℃/2V(25℃) | |||||||
Charge circuit voltage drop | ≤0.29V | |||||||
Discharge circuit voltage drop | ≤0.16V | |||||||
LCD temperature range | -20℃~+70℃ | |||||||
Working environment temperature | -25℃~+55℃(Product can work continuously at full load) | |||||||
Relative humidity | ≤95%, N.C. | |||||||
Enclosure | IP30 | |||||||
Grounding | Common Positive | |||||||
USB output | 5VDC/2.4A(Total) | |||||||
Overall dimension | 142x85x41.5mm | 160×94.9×49.3mm | 181×100.9×59.8mm | 194×118.4×63.8mm | 214×128.7×72.2mm | |||
Mounting dimension | 130x60mm | 148x70mm | 172x80mm | 185x90mm | 205x100mm | |||
Mounting hole size | Φ4.5mm | Φ5mm | Φ5mm | Φ5mm | ||||
Terminals | 4mm2/12AWG | 10mm2/8AWG | 16mm2/6AWG | 16mm2/6AWG | 25mm2/4AWG | |||
Net weight | 0.22kg | 0.35kg | 0.55kg | 0.58kg | 0.76kg | 0.88kg | 1.02kg | 1.04kg |
※Above the parameters are in 12V system at 25℃, twice in 24Vsystem, triple in 36V system and quadruple in 48V system. |
Any changes without prior notice! Version number:V1.2
BEIJING EPSOLAR TECHNOLOGY CO., LTD. Tel: +86-10-82894112 / 82894962 Website:www.epsolarpv.com / www.epever.com