Enviro-Tech ET3-R Urinal Flush Valve
Product Using Instructions
- Attention: Hold the plug not the wire to connect and disconnect and make sure the pins align to the holes in the right position.
- Note: Ceiling must be level. If ceiling is sloping/pitched, the detection zone will be altered.
- Follow the steps provided in the manual to install the sensor properly.
- Detailed instructions on how to connect the cables for Solenoid Valve, Sensor, and Transformer are provided in the manual.
- The manual includes information on adjusting settings like distance sensitivity, flush time, pre-flush settings, and more.
INSTALLATION INSTRUCTIONS ET-3R URINAL FLUSH VALVE
- We strongly recommend that you use a qualified and registered plumber and electrician.
- You must ensure that all pipe work is flushed adequately, particularly in new builds or where lines have been disrupted.
- Components of sensor products are particularly susceptible to debris and will require more thorough flushing than a standard plumbing fixture.
- IMPORTANT: Flush pipe must be DN20 copper pipe or equivalent. Installation must be in accordance with AS/NZS3500.
- Please note that – incorrect installation is NOT covered by your warranty
TECHNICAL SPECIFICATIONS
Function | ET3-R |
Power Input | AC:220-240V 50/60Hz) |
Power Consumption | 900mA |
Water Pressure | 100kPa-500kPa (recommended 350kPa) |
Inlet/Outlet Diameter | 15mm 1/2G |
Detection Zone | 1600x1000mm (adjustable) |
Inductive Confirmation Time | 6 times within 5 seconds |
Confirmation Time After Use | 5 seconds |
Flush Time | 4 seconds (adjustable) |
Reset Time After Flush | 20 seconds |
Trap Seal Protection | Automatic flush every 6 hours if not used |
Flush Delay Time | After user leaves: 30 seconds |
COMPONENTS
ATTENTION:
- Hold the plug not the wire to connect and disconnect and make sure the pins align to the holes in the right position.
SOLENOID VALVE INSTALLATION
- Flush Pipework thoroughly – failure to do so will result in solenoid sticking soon after install, which is NOT covered by your product warranty.
- Attach bracket, then insert solenoid valve.
- Connect water feed to inlet valve.
- Connect outlet to urinal.
SENSOR INSTALLATION
Note: Ceiling must be level. If ceiling is sloping/pitched the detection zone will be altered.
For Single Urinals
- Drill a 70mm hole in the ceiling centred on the urinal and 100mm from the wall/back of urinal to the centre of the sensor.
- Remove the screws from the sensor plate and install the flush box into the ceiling using the screw clips. (Ensure the screw holes are aligned as shown in 3)
- First make any changes required to flush time or pre-flush settings. Then refix the sensor plate using the 2 screws. Ensure sensor plate screws are parallel to wall for a single urinal.
For Twin or Trough Urinals
- Drill a 70mm hole in the ceiling centred on the trough or the 2 individual urinals and 300mm from the wall/back of urinal to the centre of the sensor.
- Remove the screws from the sensor plate and install the flush box into the ceiling using the screw clips. (Ensure the screw holes are aligned as shown in 3)
- First make any changes required to flush time or pre-flush settings. Then refix the sensor plate using the 2 screws. Ensure sensor plate screws are aligned facing the wall for twin or trough urinals.
CABLE CONNECTIONS
CABLE CONNECTIONS OF ET3-R
- Insert and connect male to male connection cable between sensor and solenoid (Fig 1)
- Connect sensor to transformer with WAGO connectors. Ensure marked taped ends go together in one connector, unmarked ends into the other (Fig 1).
- Lock WAGO connectors and then connect transformer to mains power (Fig 2). System will run test and be ready to use.
SETTINGS
DISTANCE
- Turn the potentiometer clockwise to increase the sensing distance and anti-clockwise to decrease it.
FACTORY SETTINGS
- Pre-flush is “‘ON”.
- Time is “4”.
- “1-10 Jumper Right” at 350kPa, giving flush volume of 0.8ltr for a single urinal.
PRE-FLUSH ON/OFF
- Factory setting is set to ‘ON’ and jumper is set to the ‘Right’.
- To turn ‘OFF’ pre-flush, set the jumper to the ‘Left’.
FULL FLUSH TIME
- Set the jumper to the ‘Left’ to choose 11-20s (20s=0s).
- Set the jumper to the ‘Right’ to choose 1-10s (10s=0s).
- Set the coding wheel to the required flush time – see table on next page for full details of flush volumes, and time setting options for different urinal types.
FLUSH VOLUME SETTINGS
Time settings for flush volumes without ‘pre-flush’ | |||
Urinal Type | Dynamic Pressure | Time Setting | Flush Volume |
Single Urinal | 350 kPa | 6s | 0.8L |
500 kPa | 5s | ||
Twin Urinal | 350 kPa | 12s |
1.6L |
450 kPa | 11s | ||
500 kPa | 10s (10=0) | ||
Slab/Trough Urinal | 350 kPa | 19s |
2.4L |
400 kPa | 17s | ||
450 kPa | 16s | ||
500 kPa | 15s | ||
Time settings for flush volumes with ‘pre-flush’ | |||
Urinal Type | Dynamic Pressure | Time Setting | Flush Volume |
Single Urinal | 350 kPa | 4s | 0.8L |
500 kPa | 3s | ||
Twin Urinal | 350 kPa | 8s |
1.6L |
450 kPa | 7s | ||
550 kPa | 6s | ||
Slab/Trough Urinal | 350 kPa | 12s |
2.4L |
400 kPa | 11s | ||
500 kPa | 10s (10=0) |
DETECTION ZONE
DETECTION ZONE (GUIDE ONLY)
2.4 M Height Installation
Single Urinal
Twin Urinals
Slab Urinal
DETECTION ZONE (GUIDE ONLY)
3 M Height Installation
Single Urinal
Twin Urinals
Slab Urinal
TROUBLESHOOTING
PROBLEM | POSSIBLE CAUSE | SOLUTION |
No water out or will not stop running | Most common: Plugs not connected correctly. No water supply or No Power. | · Check water and power supply. · Unplug all cables, leave unplugged for 5 minutes, then reconnect everything carefully. |
Blocked filter or solenoid | Clean filter. Clean/replace solenoid. | |
Too little water flow | Water pressure is low or turned down. | Adjust/raise the water pressure. |
Flow Valve needs adjusting. | Adjust flow valve on solenoid | |
The filter or solenoid is blocked. | Clean the filter. Clean/replace the solenoid | |
Too much water flow | Water pressure is too high. | Adjust/lower the water pressure. |
Flow valve needs adjusting. | Adjust flow valve on solenoid. | |
Flush time or sensing distance is not adequate | Sensor requires adjustment. | See the ‘Settings’ section of this manual for instructions. |
- For detailed troubleshooting advice, see the Troubleshooting page of our websites enviro-tech.com.au or enviro-tech.co.nz or call us on the numbers below.
WARRANTY
- This Enviro-Tech product is guaranteed for 12 months from the date of purchase.
- This is a parts only warranty and Enviro-Tech is not liable for any associated costs incurred in the replacement or repair of any item.
- For full details of the warranty conditions, see the Warranty page of our websites.
AFTERCARE
- Ensure good water quality is maintained and the filter on the solenoid valve is cleaned out regularly.
- Failure to do so could result in blocked solenoid/impair product functionality and may invalidate your product warranty.
- Surfaces should be maintained using a clean damp cloth, no abrasive agents or materials should be used or come into contact with the surface finish, or this will invalidate your warranty.
- This Enviro-Tech product is manufactured strictly to adhere to the ISO9001 standard, WaterMark certification and WELS standards.
- Enviro-tech reserves the right to update product technology at any time.
CONTACT
- Australia – 1300 530 883 or info@enviro-tech.com.au
- New Zealand – 0800 2 ENVIRO or info@enviro-tech.co.nz
FAQ
Q: How do I adjust the sensing distance of the sensor?
A: Turn the potentiometer clockwise to increase the sensing distance and anti-clockwise to decrease it.
Q: What are the factory settings for flush time?
A: The manual provides detailed information on factory settings, including pre-flush options, flush volumes, and time setting options for different types of urinals.