ENGO-logo

ENGO CONTROLS EONE-BATW, EONE-BATB Internet Controlled Thermostat

ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat-product

Specifications

  • Product: Internet controlled thermostat, ZigBee
  • Model: EONE-BATW
  • Release Date: VII 2024
  • ZigBee Soft Version: v1.0.12
  • MCU Version: v2.0.9
  • Producer: Engo Controls sp z o.o. sp. k.

Product Usage Instructions

Safety Information
Use in accordance with national and EU regulations. Keep the device dry and for indoor use only. Read the manual before installation or use.

Product Advantages

  • Built-in Li-Ion 3.7V Battery
  • Communication in ZigBee 3.0 standard
  • Multiple functions available from ENGO Smart / Tuya Smart application
  • S1-S2 Input for additional sensor
  • ENGO ENGO binding function for device connection

Connection Description
EONE-BATW/B connects via ZigBee 3.0 to Gateway EGATEZB and ECB62-ZB Control box. Additional products like EMOD-ZB Module or EREL-12ZB Relay are sold separately.

Installation Instructions

  1. Ensure your router is within range of your smartphone and connected to the internet.
  2. Step 1 – Download ENGO Smart App: Download the app from Google Play or Apple App Store and install it on your smartphone.

FAQ

  • Q: Do I need a ZigBee gateway for this thermostat?
    A: Yes, this product must be used with a ZigBee gateway which needs to be purchased separately.
  • Q: What is the power supply for this thermostat?
    A: The thermostat has a built-in Li-Ion 3.7V Battery for power.
  • Q: How do I change the temperature settings on the thermostat?
    A: Use the temperature settings icon on the thermostat display and follow the provided button descriptions for navigation.

Internet controlled thermostat, ZigBee

ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (1)

Producer:
Engo Controls sp z o.o. sp. k.
Rolna 4
43-262 Kobielice
Poland www.engocontrols.com

Product Compliance
This product complies with the following EU Directives: 2014/30/EU, 2014/35/EU, 2014/53/EU, 2011/65/EU

SAFETY INFORMATION

Use in accordance with national and EU regulations. Use the device only as intended, keeping it in a dry condition. The product is for indoor use only. Please read the entire manual, before installation or use.

WARNING:
This product must be used with a ZigBee gateway (purchased separately). Thermostat programming is done by ENGO Smart app.

Product advantages

  • ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (2)Built-in Li-Ion 3,7V Battery
  • ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (3)Communication in the ZigBee 3.0 standard
  • ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (4)A multitude of functions available from ENGO Smart / Tuya Smart application
  • ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (5)S1-S2 Input for additional sensor
  • ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (6)ENGO binding function (devices connection in Online and Offline mode)

Wireless communication diagram

ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (7)

Connection description

ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (8)

Legend:

  • ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (9)Battery powered
  • ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (10)Temperature sensor
  • ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (11)Thermostat input for ext. temperature sensor
  • ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (12)Connection with ZigBee 3.0 network
  • ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (13)Connection with WiFi 2.4GHz network

INTRODUCTION

EONE-BAT is a surface-mounted room thermostat which works over ZigBee technology. It has a built-in humidity sensor and a minimum/maximum setpoint temperature limiting function. The EONE-BAT has the ability to work in heating or cooling modes. The unique feature of this thermostat is the possibility of wireless control over ENGO binding function. In order to have the ability to controll wirelessly, EONE-BAT needs to be used with ENGO Smart / TUYA Smart mobile application and EGATE-ZB internet gateway (sold separately). „ENGO binding” function provides wireless and direct connection to the receivers (e.g. ECB62-ZB control box, EMOD-ZB module or EREL-12ZB relay) over the gateway. After adding to the mobile app, thermostat offer more functions, e.g. push notifications or possibility of programming time schedules.

Technical Information

Power supplyBuilt-in Li-Ion 3,7V Battery
Charging connectorUSB type C, 5V DC
Temperature range5,0°C – 45,0°C
Display temperature accuracy0,5°C
Control algorithmTPI or Histeresis (from ±0,1°C to ±2°C)
CommunicationZigBee 3.0 2,4GHz
S1/S2 multifunctional inputFloor temp sensor, external air sensor, occupancy sensor
IP protection classIP30
Dimension [mm]90 x 90 x 14 mm

LCD Icon Description + Button Description

  1. Current humidity reading
  2. Current/Setpoint temperature
  3. Clock
  4. Temperature unit
  5. Heating indicator (icon is animating when there is heating demand)
  6. Cooling indicator (icon is animating when there is cooling demand)
  7. Schedule mode icon
  8. Temporary override mode
  9. External/Floor or Occupancy sensor
  10. Button lock
  11. Holiday mode
  12. Settings icon
  13. Battery indicator
  14. Receiver binding indicator
  15. ZigBee network connection indicator
  16. Settings icon / temperature settings

 

ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (14)

Button description

ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (15)

Installation thermostat in the app
Make sure your router is within range of your smartphone. Make sure you are connected to the Internet. This will reduce the pairing time of the device.

STEP 1 – DOWNLOAD ENGO SMART APP
Download the ENGO Smart app from Google Play or Apple App Store and install it on your smartphone.

ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (16)

STEP 2 – REGISTER THE NEW ACCOUNT
To register a new account, please follow the steps below:

  1. Click „Register” to create new account.
  2. Enter your e-mail address to which the verification code will be sent.
  3. Enter the verification code received in the email. Remember that you only have 60 seconds to enter the code!!
  4. Then set the login password.ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (17)

STEP 3 – CONNECT THE THERMOSTAT TO ZigBee

 

  • Make sure ZigBee Gateway has been added to the Engo Smart app. Press and hold the ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (19) buttons on the thermostat until the display shows „PA”. Then release the keys. The pairing mode will be started up.
  • Thermostat counts the time back (180s).

ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (17)

  1. Enter the gateway interface.
  2. In „Zigbee devices list” go „Add devices”.
  3. Wait for the message “End” to appear on the thermostat screen.
  4. ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (19) Name the device and click „Done”
  5. The thermostat has been installed and displays the main interface.
  6. On the controller screen globe icon appeared stating that he has been he added to the ZigBee network.

ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (21)

Binding thermostat with the module/relay

Make sure that the module/relay and thermostat are in the same ZigBee network (they are added to the same gateway).ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (21)

  1. To properly link thermostat with the module/relay first click quickly the button on the device 5 times. The LED diode will start flashing slowly on red, which means the device is in binding mode.
  2. On the EONE thermostat, holdENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (19)buttons until the “bind” message appears. ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (23)
  3. Release the keys, binding function process of linking thermostat with control box is active.
  4. The “binding” process takes up to 300 seconds. ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (23)
  5. After successfull binding operation „End” message will be displayed. LED on the module will stop flashing.
  6. Both devices have been successfully linked. Thermostat displays the main screen, icon ” ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (25)” appeared on the screenindicating connection with the receiver (module/relay in this case).

ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (27)ATTENTION:
If the binding process fails, it must be repeated taking into account the distances between devices, obstacles and local radio signal interferences.

ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (26)Remember:
Radio range can be increased by Engo ZigBee repeaters.

ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (27)ATTENTION:
When the thermostat is binded with the module, the relay will turn off after 50 minutes, if the communication between the devices is lost.

Binding thermostat with the ECB62-ZB wireless control box
Make sure that the ECB62-ZB control box and thermostat are in the same ZigBee network (they are added to the same gateway) and the POWER LED lights up blue.

  1. In order to correctly link thermostat with the control box, first select the zone in the control box with the SELECT button (1) (zone which you want to link with thermostat). The LED (2) will flash 3 times for the selected zone. Confirm your selection by clicking PAIR button (2). The LED (2) will flash green with the previously selected zone – binding process has started, it is active for 10 minutes and during this time you can link thermostat with the selected zone.ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (28)
  2. On the EONE thermostat, hold ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (19) buttons until the “bind”message appears.
  3. Release the keys, binding functionprocess of linking thermostat with control box is active.
  4. The “binding” process takes up to 300 seconds.ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (29)
  5. After successfull binding operation „End” message will be displayed.
  6. Both devices have been successfully linked. Thermostat displays the main screen, icon “ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (25) ” appeared on the screen indicating connection with the receiver (ECB62ZB in this case). ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (30)

ATTENTION:
If the binding process fails, it must be repeated taking into account the distances between devices, obstacles and local radio signal interferences.

Remember
Radio range can be increased by Engo ZigBee repeaters.

ATTENTION
When the thermostat is binded with the module, the relay will turn off after 50 minutes, if the communication between the devices is lost.

Installer settings

  1. To enter installer parameters press and hold button for 3 seconds.

ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (31)

UseENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (32) button to move between parameters. Enter the parameter by √. Edit the parameter usingENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (32) . Confirm the new parameter value with the √ button.

Installer parameters

PxxFunctionValueDesriptionDefault value
P01Clock format12h12 hour24h
24h24 hour
P02Heating/Cooling SelectionENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (33)HeatingENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (33)
ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (34)Cooling
 

 

 

 

 

P03

 

 

 

 

 

Control algorithm

TPI UFHTPI for Underfloor Heating 

 

 

 

TPI UFH

for heating HIS 1.0 for cooling

TPI RADTPI for Radiators
TPI ELETPI for Electrical Heating
HIS 0.2SPAN +/-0,1°C
HIS 0.4SPAN +/-0,2°C
HIS 0.6SPAN +/-0,3°C
HIS 0.8SPAN +/-0,4°C
HIS 1.0SPAN +/-0,5°C
HIS 2.0SPAN +/-1,0°C
HIS 3.0SPAN +/-1,5°C
HIS 4.0SPAN +/-2,0°C
P04Offset temperature-3.5°C do +3.5°CIf the thermostat indicates wrong temperature, you can correct it by max ± 3.5°C”0°C
P05“Minimum setpoint”5°C – 45°CMinimum heating / cooling temperature that can be set5°C
P06“Maximum setpoint”5°C – 45°CMaximum heating / cooling temperature that can be set35°C
 

P07

 

S1/S2 Input

1Disable 

1

2External sensor as a floor sensor
3External sensor as an air sensor
4Occupnacy sensor (ON/OFF volt free input)
P08Maximum floor temperature for heating (function active when P07=2)5°C – 45°CIn order to protect the floor, the heating will be turned off, when the temperature of the floor sensor rises above the maximum value.35°C
P09Minimum floor temperature for heating (function active when P07=2)5°C – 45°CIn order to protect the floor, the heating will be switched on, when the temperature of the floor sensor drops below the minimum value.10°C
P10Maximum floor temperature for cooling (function active when P07=2)5°C – 45°CIn order to protect the floor, cooling will be switched on, when the temperature of the floor sensor exceeds the maximum value.15°C
P11Minimum floor temperature for cooling (function active when P07=2)5°C – 45°CIn order to protect the floor, cooling will be turned off, when the temperature of the floor sensor drops below the minimum value7°C
P12Comfort warm floorOFFThis function helps to keep the floor warm, even if there is no heating demand from the room thermostat.This feature is available only for Heating Mode. User can select 5 levels of warm floor feature. Note that comfort warm floor function will activate heating for specified amount of time (in relation to Level setting choosen by user). Heating will be activated only if in the past 1 hour heating was OFF.OFF
Level 1 = 7min
Level 2 = 11min
Level 3 = 15min
Level 4 = 19min
Level 5 = 23min
P13Valve protectionONFunction disabledOFF
OFFFunction enabled
P14Backlight brightness10% – 100%Adjustable in the range from 10 to 100%50%
P15PIN Code for settings accessNOFunction disabledNO
PINFunction enabled
P16Require a PIN to unlock the keys every time (function active when P15=PIN)NOFunction disabledNO
YESFunction enabled
CLRClear settings factory resetNONo actionNO
YESFactory Reset

Factory reset
To RESET Thermostat to factory settings, hold down the ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (19)buttons until the FA message appears. Then release the keys. Thermostat will restart, restore default factory settings and displays the home screen. The device will be removed from the ZigBee network you will need to add/pair it again.

ENGO-CONTROLS-EONE-BATW-EONE-BATB-Internet-Controlled-Thermostat- (35)

Documents / Resources

ENGO CONTROLS EONE-BATW, EONE-BATB Internet Controlled Thermostat [pdf] User Guide
EONE-BATW, EONE-BATB, EONE-BATW EONE-BATB Internet Controlled Thermostat, EONE-BATW EONE-BATB, Internet Controlled Thermostat, Controlled Thermostat, Thermostat

References

Leave a comment

Your email address will not be published. Required fields are marked *