Product Specifications

  • Accessories…………………………………………….. IEC 61010-031
  • TP165X Remote Probe with cap ……….. CAT IV 600 V, CAT III 1000 V, 10 A
  • TP165X Remote Probe without cap….. CAT II 1000 V, 10 A
  • TL-L1, TL-L2, TL-L3 Test Leads …………. CAT IV 600 V, CAT III 1000 V, 10 A
  • Test Probes with cap…………………………… CAT IV 600 V, CAT III 1000 V, 10 A
  • Test Probes without cap …………………….. CAT II 1000 V, 10 A
  • AC285 Alligator Clip ……………………………. CAT IV 600 V, CAT III 1000 V, 10 A
  • Country-Specific Mains Cord…………….. CAT II 250 V, 1000 V dc
  • Ingress Protection………………………………….. IEC 60529: IP40

Electromagnetic Compatibility (EMC)

Some mobile devices (for example, handheld transceivers) that transmit RF energy can transmit levels that exceed 3 V/m and can damage sensitive electronic circuits. To ensure the best performance, do not allow a device that transmits RF energy in >3 V/m to be within 30 cm of the Product while in use.
International ……………………………………………. IEC 61326-1: Portable CISPR 11: Group 1, Class A

Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself.
Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purposes. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances.

Caution: This equipment is not intended for use in residential environments and may not provide adequate protection to radio reception in such environments.
Emissions that exceed the levels required by CISPR 11 can occur when the equipment is connected to a test object.

Wireless Radio with Adapter
Frequency Range……………………………………. 2400 MHz to 2483.5 MHz
Output Power ………………………………………….. <100 mW

SIMPLIFIED EU DECLARATION OF CONFORMITY
Hereby, Fluke declares that the radio equipment contained in this Product is in compliance with Directive 2014/53/EU. The full text of the EU declaration is available at the following Internet address: www.fluke.com/red

Electrical Measurement Specifications

The specification for accuracy is defined as ±(% reading +digit counts) at 23 °C ±5 °C, ≤80 % RH. Between 0 °C and 18 °C and between 28 °C and 40 °C, accuracy specifications may degrade by 0.1 x (accuracy specification) per °C. The specifications apply up to one year from the date of calibration.

Note
Accuracy indicates the intrinsic uncertainty according to IEC 61557.

Voltage Measurement (V)

Range Resolution Accuracy 45 Hz to 66 Hz Input Impedance Overload Protection
600 V 0.1 V 0.8 % + 3 320 kW 660 V rms
Note: The display shows if dc voltage is detected.

Insulation Resistance Measurement (RISO)

Test Voltage Accuracy
Model 1672 Model 1673 FC/1674 FC
100-250-500-1000 V 50-100-250-500-1000 V +10 %, -0 %
Test Voltage Insulation Resistance Range Resolution Test Current Accuracy
50 V 10 kW to 50 MW 0.01 MW 1 mA @ 50 kW ±(3 % + 3 digits)
100 V 10 kW to 20 MW 0.01 MW 1 mA @ 100 kW ±(3 % + 3 digits)
20 MW to 100 MW 0.1 MW ±(3 % + 3 digits)
250 V 10 kW to 20 MW 0.01 MW 1 mA @ 250 kW ±(1.5 % + 3 digits)
20 MW to 200 MW 0.1 MW ±(1.5 % + 3 digits)
 

500 V

10 kW to 20 MW 0.01 MW  

1 mA @ 500 kW

±(1.5 % + 3 digits)
20 MW to 200 MW 0.1 MW ±(1.5 % + 3 digits)
200 MW to 500 MW 1 MW ±10 %
1000 V 100 kW to 200 MW 0.1 MW 1 mA @ 1 MW ±(1.5 % + 3 digits)
200 MW to 1000 MW 1 MW ±10 %
Note: The number of insulation tests with full-charge battery is >2000.
Auto Discharge Discharge time constant <0.5 second for C = 1 mF or less.
Live Circuit Detection Inhibits test if terminal voltage >30 V prior to initiation of test.
Maximum Capacitive Load Operable with up to 5 mF load.
Insulation Safety Pretest (1674 FC) Connections from the Tester to L, N, and PE are required.

SPD (Surge Protection Device) Insulation RAMP Test (Varistor Test) IEC 61643-11

Test Voltage Voltage Range Resolution Test Current Accuracy
500 V Step Ramp 0 V to 500 V 1 V 1 mA ±(1.5 % + 3 digits)
1000 V Step Ramp 0 V to 1000 V 1 V 1 mA ±(1.5 % + 3 digits)

Continuity Test (RLO)

Range (Autoranging) Resolution Open Circuit Voltage Accuracy
20 W 0.01 W >4 V ±(1.5 % + 3 digits)[1]
200 W 0.1 W >4 V ±(3 % + 3 digits)
2000 W 1 W >4 V ±(3 % + 3 digits)
Note: The number of 250 mA @ 1 W continuity tests with full-charge battery is >1500. [1] For 10 mA, add 3 digits.
Range Setting Display Range Test Current[1]
 

250 mA

0.2 W to 2.0 W 250 mA
2 W to 160 W 250 mA to 50 mA
160 W to 800 W 10 mA
800 W to 2000 W 2 mA
10 mA 0 W to 800 W 10 mA
800 W to 2000 W 2 mA
[1] All test currents ±10 %.
Test Probe Zeroing Select ZERO to zero the test probe.

Can subtract up to 3 W of lead resistance. Error message for >3 W.

Live Circuit Detection Inhibits test if terminal voltage >10 V ac detected before initiation of test. Does not apply in point-to-point continuous mode.

Mains Wiring Indicator

Icons indicate if L-PE or L-N terminals are reversed.

FLUKE-1673-FC-Multifunction-Tester-1

Loop and RCD tests are inhibited and an error message is generated if the input voltage is not between 100 V and 500 V. The UK Loop and RCD tests are inhibited if the L-PE or the L-N terminals are reversed.

Loop and Line Impedance (ZI No Trip and Hi Current)

Mains Input Voltage Range 50 V ac to 600 V ac (45 Hz to 66 Hz)
Input Connection (softkey selection) Loop Impedance: phase-to-earth
Line Impedance: phase-to-neutral
Limit on Consecutive Tests Auto-shutdown when the temperature of internal components is too high.
Maximum Test Current @ 600 V 30 A sinusoidal for 10 ms
Maximum Test Current @ 400 V 20 A sinusoidal for 10 ms
Maximum Test Current @ 230 V 12 A sinusoidal for 10 ms
Range Setting Resolution Accuracy[1]
10 Ω [2] 0.001 Ω Hi Current mΩ mode: ±(2 % + 35 digits)
20 Ω 0.01 Ω No Trip mode: ±(3 % + 6 digits)
Hi Current mode: ±(2 % + 4 digits)
200 Ω 0.1 Ω No Trip mode: ±(3 %)
Hi Current mode: ±(2 %)
2000 Ω 1 Ω ±6 %[3]
[1]    Valid for resistance of neutral circuit <20 Ω and up to a system phase angle of 30 °. Test leads must be zeroed before testing. [2]    1674 FC model only. [3]    Valid for mains voltage >200 V.

Voltage Drop (ΔV)

Measurement Range Resolution Accuracy
0.0 % to 99.9 % 0.1 % Consider accuracy of line impedance measurements.

Prospective Earth Fault Current (PEFC) Prospective Short Circuit Current (PSC)

 

Computation

Prospective Earth Fault Current (PEFC/IK) or Prospective Short Circuit Current (PSC/IK) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
Range 0 kA to 50 kA
 

Resolution

Range Resolution
IK <1000 A 1 A
IK ³1000 A 0.1 kA
Accuracy Determined by accuracy of loop resistance and mains voltage measurements.

RCD Tests

RCD Types Tested
Limit on consecutive tests: Automatic shutdown for RCD tests when the temperature of internal components is too high.

RCD Type[1] 1672 1673 FC 1674 FC
AC[2] G[3] FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3
AC S[4] FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3
A[5], F[6] G FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3
A, F S FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3
B, B+[7] G   FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3
B, B+ S   FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3
RDC-DD, A/EV, B/Mi[8] G   FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3
GFCI G FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3
[1]    RCD test inhibited for V >265 ac
RCD tests permitted only if the selected current, multiplied by earthing resistance, is <50 V [2]    AC – Responds to ac [3]    G – General, no delay [4]    S – Time delay [5]    A – Responds to ac and pulsed signal [6]    F – responds to ac, pulsed, and high frequency [7]    B, B+ – Responds to ac, pulsed, high frequency, and smooth dc [8]    RDC-DD, A/EV, B/Mi – Responds to dc residual currents >6 mA

Test Signals

Type Test Signal Description
 

RCD type AC (sinusoidal)

The waveform is a sinewave starting at zero crossing, polarity determined by phase selection (0 ° phase starts with low to high zero crossing, 180 ° phase starts with high to low zero crossing). The magnitude of the test current is IΔN x Multiplier for all tests.
A

(half-wave)

The waveform is a half wave rectified sinewave starting at zero, polarity determined by phase selection (0 ° phase starts with low to high zero crossing, 180 ° phase starts with high to low zero crossing). The magnitude of the test current is 0.7 x IΔN (rms) x Multiplier for all tests where the multiplier is x0.5 (x1/2). The magnitude of the test current is 2.0 x IΔN (rms) x Multiplier for all tests where both the multiplier is ≥ x1 and IΔN = 0.01A. The magnitude of the test current is 1.4 x IΔN (rms) x Multiplier for all tests for all other settings.
B (DC) This is a smooth dc current in accordance to EN61557-6 Annex A

RCD Tripping Indicator
The RCD symbol switches on as a good test indicator when testing the RCD trip time or RCD trip current if the trip time meets these conditions:

RCD Type IΔN Trip Time Limits
G x1 <300 ms
S x1 >130 ms and <500 ms
G x5 <40 ms
S x5 >50 ms and <150 ms

RCD Tripping Time (ΔT)

Test Function RCD Current Selection
6 mA 10 mA 30 mA 100 mA[1] 300 mA[1] 500 mA[1] 1000 mA[2] Var[3]
x ½, 1 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3
x 5 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3        
Ramp FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3
Auto FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3 FLUKE-1673-FC-Multifunction-Tester-3        
Mains voltage 100 V – 265 V ac, 45/66 Hz [1]    Type B RCDs require mains voltage range of 195 V to 265 V. [2]    Type AC RCDs only. [3]    Type A RCDs are limited to 700 mA, not available for Type B RCDs.
Current Multiplier RCD Type Measurement Range Accuracy
Europe UK
x ½ G 310 ms 2000 ms ±(1 % Reading + 1 ms)
x ½ S 510 ms 2000 ms ±(1 % Reading + 1 ms)
x 1 G 310 ms 310 ms ±(1 % Reading + 1 ms)
x 1 S 510 ms 510 ms ±(1 % Reading + 1 ms)
x 5 G 50 ms 50 ms ±(1 % Reading + 1 ms)
x 5 S 160 ms 160 ms ±(1 % Reading + 1 ms)
x 1 RDC-DD, A/EV, B/Mi 10 s 10 s ±(1 % Reading + 1 ms)
350 mA A 10 ms 10 ms ±(1 % Reading + 1 ms)
[1] G – General, no delay / S – Time delay

RCD Tripping Current (IΔN) Measurement/Ramp Test

Current Range Step Size Dwell Time Measurement Accuracy
Type G Type S
30 % to 110 % of

RCD-rated current[1]

10 % of IDN[2] 300 ms/step 500 ms/step ±5 %
[1] Specified trip current ranges (IEC 61008-1): 30 % to 150 % for Type A IΔ N >10 mA

30 % to 210 % for Type A IΔ N = 10 mA 20 % to 210 % for Type B

50 % to 100 % for Type AC

35 % to 140 % for Type A (>10 mA) 35 % to 200 % for Type A (≤10 mA) 50 % to 200 % for Type B

[2] 5 % for Type B

Insulation Monitoring Devices (IMD) IEC 61557-8

Range Resolution Note
1 kΩ to 10 kΩ 1 kΩ  

>1 MΩ only available with voltages >100 V

10 kΩ to 100 kΩ 10 kΩ
100 kΩ to 3 MΩ 100 kΩ
Maximum Time[1] Resolution Note
600.0 s 0.1 s Manual timing with TEST button Test
[1] The maximum test time duration may be reduced due to heat development when low resistance values are used in combination with high voltages.

Phase Sequence Test

Icon FLUKE-1673-FC-Multifunction-Tester-2 icon. Phase Sequence indicator is active.
 

Display of Phase Sequence

Displays “1-2-3” in digital display field for correct sequence. Displays “3-2-1” for incorrect phase. Dashes in place of a number indicate a valid determination could not be made.
Mains Input Voltage Range (phase-to-phase) 185 V to 600 V

Earth Resistance Test (RE)
1673 FC and 1674 FC only

Range Resolution Accuracy
200 W 0.1 W ±(2 % + 5 digits)
2000 W 1 W ±(3.5 % + 10 digits)
[1]

Range: RE + RPROBE

Test Current
2200 W 3.5 mA
16 000 W 500 mA
52 000 W 150 mA
[1] Without external voltages.
Freqency Output Voltage
128 Hz 25 V
Live Circuit Detection Inhibits test if terminal voltage >10 V ac is detected before the start of the test.

Auto Test Sequence
Models 1673 FC and 1674 FC only.
Meets the specifications of the individual tests.

Operating Ranges and Uncertainties (IEC 61557)

The maximum permissible error shows as a percent of reading plus a number of digits when all uncertainty influence factors E1-E10 are counted.

 

Function

 

Display Range

IEC 61557

Measurement Range Operating Uncertainty

 

Nominal Values

V 0.0 V ac to 600 V ac 50 V ac to 600 V ac

±(2 % + 2 digits)

UN = 230/400 V ac

f = 50/60 Hz

RLO

IEC 61557-4

0.00 W to 2000 W 0.2 W to 2000 W

±(10 % + 2 digits)

4.0 V dc <UQ <24 V dc RLO ≤2.00 W IN ≥200 mA
 

RISO

IEC 61557-2

 

0.00 MW to 1000 MW

1 MW to 200 MW

±(10 % + 2 digits)

200 MW to 1000 MW

±(15 % + 2 digits)

UN = 50 / 100 / 250 / 500 /

1000 V dc IN = 1.0 mA

 

 

 

ZI

IEC 61557-3

ZI (No Trip)

0.00 W to 2000 W

0.4 W to 2000 W

±(15 % + 6 digits)

 

 

UN = 230/400 V ac

f = 50/60 Hz

IK= 0 A to 10.0 kA

ZI (Hi Current)

0.00 W to 2000 W

0.2 W to 200 W

±(10 % + 4 digits)

ZI (Hi Current, Hi Res) 0 mW to 9999 mW 100 mW to 9999 mW

±(8 % + 20 digits)

RE

0.00 W to 2000 W

10 W to 1000 W

±(10 % + 2 digits)

 

DT, IDN

IEC 61557-6

DT 0.0 ms to 2000 ms 25 ms to 2000 ms

±(10 % + 1 digits)

DT @ 10 / 30 / 100 / 300 /

500 / 1000 / Var mA

IΔN 3 mA to 550 mA

(Var 3 mA to 700 mA)

3 mA to 550 mA

±(10 % + 1 digits)

IΔN = 10 / 30 / 100 / 300 /

500 / 1000 / Var mA

RE

IEC 61557-5

0.0 W to 2000 W 10 W to 2000 W

±(10 % + 2 digits)

f = 128 Hz
Phase

IEC 61557-7

1 : 2 : 3
IMD

IEC 61557-8

0 s to 600 s user-defined manual timer

Operating Uncertainties (IEC 61557)
The Operating Uncertainty shows the maximum permissible uncertainty as a percent of reading when all uncertainty influence factors E1-E10 are counted.

  Volts RLO[1] RISO[2] ZI[3] DT[4] IDN[4] RE[5]
Intrinsic Uncertainty A 0.80 % 1.50 % 10.00 % 6.00 % 1.00 % 5.00 % 3.50 %
[1]    IEC 61557-4              [4] IEC 61557-6 [2]    IEC 61557-2              [5] IEC 61557-5 [3]    IEC 61557-3
Influence Quantity Volts RLO[1] R [2] ISO ZI[3] DT[4] IDN[4] RE[5]
E1

Position

0.00 % 0.00 % 0.00 % 0.00 % 0.00 % 0.00 % 0.00 %
E2

Supply voltage

0.50 % 3.00 % 3.00 % 3.00 % 3.00 % 2.75 % 2.00 %
E3

Temperature

0.50 % 3.00 % 3.00 % 3.00 % 3.00 % 2.25 % 1.50 %
E4

Series interferences voltage

 

 

 

 

 

 

 

2.00 %

E5

Resistance of the probes and auxiliary earth electrodes

 

 

 

 

 

 

 

4.60 %

E6.2

System phase angle

1.00 %
E7

System frequency

0.50 % 2.50 % 0.00 %
E8

System voltage

2.50 % 2.50 % 2.50 % 0.00 %
E9

Harmonics

2.50 %
E10

D.C. quantity

2.50 %
[1]    IEC 61557-4              [4] IEC 61557-6 [2]    IEC 61557-2              [5] IEC 61557-5 [3]    IEC 61557-3

Maximum Display Values

The following tables can be used for the determination of maximum or minimum display values considering maximum instrument operating uncertainty per EN61557-1.
Insulation Resistance (RISO)

50 V 100 V 250 V 500 V 1000 V
Limit Value Maximum Display Value Limit Value Maximum Display Value Limit Value Maximum Display Value Limit Value Maximum Display Value Limit Value Maximum Display Value
1 1.12 1 1.12 1 1.12 1 1.12 1 1.3
2 2.22 2 2.22 2 2.22 2 2.22 2 2.4
3 3.32 3 3.32 3 3.32 3 3.32 3 3.5
4 4.42 4 4.42 4 4.42 4 4.42 4 4.6
5 5.52 5 5.52 5 5.52 5 5.52 5 5.7
6 6.62 6 6.62 6 6.62 6 6.62 6 6.8
7 7.72 7 7.72 7 7.72 7 7.72 7 7.9
8 8.82 8 8.82 8 8.82 8 8.82 8 9.0
9 9.92 9 9.92 9 9.92 9 9.92 9 10.1
10 11.02 10 11.02 10 11.02 10 11.02 10 11.2
20 22.02 20 22.2 20 22.2 20 22.2 20 22.2
30 33.02 30 33.2 30 33.2 30 33.2 30 33.2
40 44.02 40 44.2 40 44.2 40 44.2 40 44.2
45 49.52 50 55.2 50 55.2 50 55.2 50 55.2
  60 66.2 60 66.2 60 66.2 60 66.2
70 77.2 70 77.2 70 77.2 70 77.2
80 88.2 80 88.2 80 88.2 80 88.2
90 99.2 90 99.2 90 99.2 90 99.2
  100 110.2 100 110.2 100 110.2
180 198.2 200 232 200 232
  300 347 300 347
400 462 400 462
430 497 500 577
  600 692
700 807
800 922
850 980

Continuity (RLO)

Limit Value Maximum Display Value
0.2 0.16
0.3 0.25
0.4 0.34
0.5 0.43
0.6 0.52
0.7 0.61
0.8 0.70
0.9 0.79
1 0.88
2 1.78
Limit Value Maximum Display Value
3 2.68
4 3.58
5 4.48
6 5.38
7 6.28
8 7.18
9 8.08
10 8.98
20 17.98
30 26.8

Loop Tests (ZI)

Loop ZI Hi Current Loop ZI No Trip Loop ZI Hi Res
Limit Value Maximum Display Value (Ω) Limit Value Maximum Display Value (Ω) Limit Value Maximum Display Value (mΩ)
0.20 0.14 0.20 180
0.30 0.23 0.30 280
0.40 0.32 0.40 0.28 0.40 370
0.50 0.41 0.50 0.37 0.50 460
0.60 0.50 0.60 0.45 0.60 550
0.70 0.59 0.70 0.54 0.70 640
0.80 0.68 0.80 0.62 0.80 740
0.90 0.77 0.90 0.71 0.90 830
1.00 0.86 1.00 0.79 1.00 920
1.10 0.95 1.10 0.88 1.10 1010
1.20 1.04 1.20 0.96 1.20 1100
1.30 1.13 1.30 1.05 1.30 1200
1.40 1.22 1.40 1.13 1.40 1290
1.50 1.31 1.50 1.22 1.50 1380
1.60 1.40 1.60 1.30 1.60 1470
1.70 1.49 1.70 1.39 1.70 1560
1.80 1.58 1.80 1.47 1.80 1660
1.90 1.67 1.90 1.56 1.90 1750
2.00 1.76 2.00 1.64 2.00 1840
3.00 2.66 3.00 2.49 3.00 2760
4.00 3.56 4.00 3.34 4.00 3680
5.00 4.46 5.00 4.19 5.00 4600
10.00 8.96 10.00 8.44 10.00 9200

RCD/FI (ΔT, IΔN)

RCD/FI Time RCD/FI Current
Limit Value Maximum Display Value Limit Value Maximum Display Value
25 22.4 0.5 0.49
30 26.9 0.6 0.49
40 35.9 0.7 0.59
50 44.9 0.8 0.69
60 53.9 0.9 0.79
70 62.9 1 0.89
80 71.9 2 1.79
90 80.9 3 2.69
100 89.9 4 3.59
200 179.9 5 4.49
300 269 6 5.39
400 359 7 6.29
500 449 8 7.19
600 539 9 8.09
700 629 10 8.99
800 719 20 17.99
900 809 30 26.9
1000 899 40 35.9
2000 1799 50 44.9
  60 53.9
70 62.9
80 71.9
90 80.9
100 89.9
200 179.9
300 269.9
400 359.9
500 449.9

Earth Tests (RE)

Limit Value Maximum Display Value
10 8.8
20 17.8
30 26.8
40 35.8
50 44.8
60 53.8
70 62.8
80 71.8
90 80.8
100 89.8
Limit Value Maximum Display Value
200 179.8
300 268
400 358
500 448
600 538
700 628
800 718
900 808
1000 898
2000 1798