EMS FCX-532-001 Loop Module

EMS FCX-532-001 Loop Module

Pre Installation

Symbol Installation must conform to applicable local installation codes and should only be installed by a fully trained competent person.

  • Ensure the loop module is installed as per the site survey.
  • Refer to step 3 to ensure optimized wireless performance.
  • If using remote aerials with this product, refer to the remote aerial installation guide (MK293) for more information.
  • A maximum of 5 loop modules can be connected per loop.
  • This device contains electronics that may be susceptible to damage from Electrostatic Discharge (ESD). Take appropriate precautions when handling electronic boards.

Components

  1. 4x corner covers,
  2. 4 x lid screws,
  3. Loop module lid,
  4. Loop module PCB,
  5. Loop module back box
    Components

Mounting Location Guidelines

Symbol For optimum wireless performance, the following must be observed:

  • Ensure the loop module is not installed within 2 m of other wireless or electrical equipment (not including the control panel).
  • Ensure the loop module is not installed within 0.6 m of metal work.
    Mounting location guidelines

Optional PCB Removal

  • Remove the three circled retaining screws, before unclipping the PCB.
    Optional PCB removal

Remove Cable Entry Points

  • Drill the cable entry points as necessary.
    Remove cable entry points

Fix to The Wall

  • All five circled fixing positions are available for use as required.
  • The key hole can also be used for locating and fixing where required.
    Fix to the wall

Connection Wiring

  • Loop cables should only be passed via the access points available.
  • Flame retardant cable glands must be used.
  • DO NOT leave excess cable inside the loop module.

Single loop module.

Single loop module.

Multiple loop modules (max. 5)

Multiple loop modules (max. 5)

Configuration

  • Set the loop module address using the on-board 8 way switch.
  • Available selections are shown in the table below.
DIL SWITCH SETTING
Addr.1……8
110000000
201000000
311000000
400100000
510100000
601100000
711100000
800010000
910010000
1001010000
1111010000
1200110000
1310110000
1401110000
1511110000
1600001000
1710001000
1801001000
1911001000
2000101000
2110101000
2201101000
2311101000
2400011000
2510011000
2601011000
2711011000
2800111000
2910111000
3001111000
3111111000
3200000100
3310000100
3401000100
3511000100
3600100100
3710100100
3801100100
3911100100
4000010100
4110010100
4201010100
4311010100
4400110100
4510110100
4601110100
4711110100
4800001100
4910001100
5001001100
5111001100
5200101100
5310101100
5401101100
5511101100
5600011100
5710011100
5801011100
5911011100
6000111100
6110111100
6201111100
6311111100
6400000010
6510000010
6601000010
6711000010
6800100010
6910100010
7001100010
7111100010
7200010010
7310010010
7401010010
7511010010
7600110010
7710110010
7801110010
7911110010
8000001010
8110001010
8201001010
8311001010
8400101010
8510101010
8601101010
8711101010
8800011010
8910011010
9001011010
9111011010
9200111010
9310111010
9401111010
9511111010
9600000110
9710000110
9801000110
9911000110
10000100110
10110100110
10201100110
10311100110
10400010110
10510010110
10601010110
10711010110
10800110110
10910110110
11001110110
11111110110
11200001110
11310001110
11401001110
11511001110
11600101110
11710101110
11801101110
11911101110
12000011110
12110011110
12201011110
12311011110
12400111110
12510111110
12601111110
  • The system can now be programmed.
  • Refer to the Fusion programming manual (TSD062) for details of compatible Fire Cell devices and full programming information.

Apply Power

Apply power to the control panel. The normal LED states for the Loop Module are as below:

  • The green POWER LED will illuminate.
  • The other LEDs should be extinguished.
    Apply power

Close Loop Module

  • Ensure that the loop module PCB is correctly inserted and the PCB retaining screws are refitted.
  • Refit the loop module lid, ensuring LEDs are not damaged by the light pipe when refitting.
    Close loop module

Specification

Operating temperature -10 to +55 °C
Storage temperature 5 to 30 °C
Humidity 0 to 95% non-condensing
Operating voltage 17 to 28 VDC
Operating current 17 mA (typical) 91mA (max.)
IP rating IP54
Operating frequency 868 MHz
Output transmitter power 0 to 14 dBm (0 to 25 mW)
Signalling protocol X
Panel protocol XP
Dimensions (W x H x D) 270 x 205 x 85 mm
Weight 0.95 kg
Location Type A: For indoor use

Specification Regulatory information

Manufacturer

Carrier Manufacturing Poland Sp. z o.o.
Ul. Kolejowa 24. 39-100 Ropczyce, Poland

Year of manufacture

See devices serial number label

Certification

Symbol 13

Certification body

0905

CPR DoP

0359-CPR-0222

Approved to

EN54-17:2005. Fire detection and fire alarm systems.
Part 17:Short-circuit isolators.

EN54-18:2005. Fire detection and fire alarm systems.
Part 18:Input/output devices.

EN54-25:2008. Incorporating corrigenda September 2010 and March 2012. Fire detection and fire alarm systems.

European Union

EMS declares that this device is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address: www.emsgroup.co.uk

Directives

Symbol 2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see www.recyclethis.info
Dispose of your batteries in an environmentally friendly manner according to your local regulations.

Logo

Documents / Resources

EMS FCX-532-001 Loop Module [pdf] Installation Guide
FCX-532-001 Loop Module, FCX-532-001, Loop Module, Module

References

Leave a comment

Your email address will not be published. Required fields are marked *