Pre Installation
Installation must conform to applicable local installation codes and should only be installed by a fully trained competent person.
- Ensure the loop module is installed as per the site survey.
- Refer to step 3 to ensure optimized wireless performance.
- If using remote aerials with this product, refer to the remote aerial installation guide (MK293) for more information.
- A maximum of 5 loop modules can be connected per loop.
- This device contains electronics that may be susceptible to damage from Electrostatic Discharge (ESD). Take appropriate precautions when handling electronic boards.
Components
- 4x corner covers,
- 4 x lid screws,
- Loop module lid,
- Loop module PCB,
- Loop module back box
Mounting Location Guidelines
For optimum wireless performance, the following must be observed:
- Ensure the loop module is not installed within 2 m of other wireless or electrical equipment (not including the control panel).
- Ensure the loop module is not installed within 0.6 m of metal work.
Optional PCB Removal
- Remove the three circled retaining screws, before unclipping the PCB.
Remove Cable Entry Points
- Drill the cable entry points as necessary.
Fix to The Wall
- All five circled fixing positions are available for use as required.
- The key hole can also be used for locating and fixing where required.
Connection Wiring
- Loop cables should only be passed via the access points available.
- Flame retardant cable glands must be used.
- DO NOT leave excess cable inside the loop module.
Single loop module.
Multiple loop modules (max. 5)
Configuration
- Set the loop module address using the on-board 8 way switch.
- Available selections are shown in the table below.
DIL SWITCH SETTING | |
Addr. | 1……8 |
1 | 10000000 |
2 | 01000000 |
3 | 11000000 |
4 | 00100000 |
5 | 10100000 |
6 | 01100000 |
7 | 11100000 |
8 | 00010000 |
9 | 10010000 |
10 | 01010000 |
11 | 11010000 |
12 | 00110000 |
13 | 10110000 |
14 | 01110000 |
15 | 11110000 |
16 | 00001000 |
17 | 10001000 |
18 | 01001000 |
19 | 11001000 |
20 | 00101000 |
21 | 10101000 |
22 | 01101000 |
23 | 11101000 |
24 | 00011000 |
25 | 10011000 |
26 | 01011000 |
27 | 11011000 |
28 | 00111000 |
29 | 10111000 |
30 | 01111000 |
31 | 11111000 |
32 | 00000100 |
33 | 10000100 |
34 | 01000100 |
35 | 11000100 |
36 | 00100100 |
37 | 10100100 |
38 | 01100100 |
39 | 11100100 |
40 | 00010100 |
41 | 10010100 |
42 | 01010100 |
43 | 11010100 |
44 | 00110100 |
45 | 10110100 |
46 | 01110100 |
47 | 11110100 |
48 | 00001100 |
49 | 10001100 |
50 | 01001100 |
51 | 11001100 |
52 | 00101100 |
53 | 10101100 |
54 | 01101100 |
55 | 11101100 |
56 | 00011100 |
57 | 10011100 |
58 | 01011100 |
59 | 11011100 |
60 | 00111100 |
61 | 10111100 |
62 | 01111100 |
63 | 11111100 |
64 | 00000010 |
65 | 10000010 |
66 | 01000010 |
67 | 11000010 |
68 | 00100010 |
69 | 10100010 |
70 | 01100010 |
71 | 11100010 |
72 | 00010010 |
73 | 10010010 |
74 | 01010010 |
75 | 11010010 |
76 | 00110010 |
77 | 10110010 |
78 | 01110010 |
79 | 11110010 |
80 | 00001010 |
81 | 10001010 |
82 | 01001010 |
83 | 11001010 |
84 | 00101010 |
85 | 10101010 |
86 | 01101010 |
87 | 11101010 |
88 | 00011010 |
89 | 10011010 |
90 | 01011010 |
91 | 11011010 |
92 | 00111010 |
93 | 10111010 |
94 | 01111010 |
95 | 11111010 |
96 | 00000110 |
97 | 10000110 |
98 | 01000110 |
99 | 11000110 |
100 | 00100110 |
101 | 10100110 |
102 | 01100110 |
103 | 11100110 |
104 | 00010110 |
105 | 10010110 |
106 | 01010110 |
107 | 11010110 |
108 | 00110110 |
109 | 10110110 |
110 | 01110110 |
111 | 11110110 |
112 | 00001110 |
113 | 10001110 |
114 | 01001110 |
115 | 11001110 |
116 | 00101110 |
117 | 10101110 |
118 | 01101110 |
119 | 11101110 |
120 | 00011110 |
121 | 10011110 |
122 | 01011110 |
123 | 11011110 |
124 | 00111110 |
125 | 10111110 |
126 | 01111110 |
- The system can now be programmed.
- Refer to the Fusion programming manual (TSD062) for details of compatible Fire Cell devices and full programming information.
Apply Power
Apply power to the control panel. The normal LED states for the Loop Module are as below:
- The green POWER LED will illuminate.
- The other LEDs should be extinguished.
Close Loop Module
- Ensure that the loop module PCB is correctly inserted and the PCB retaining screws are refitted.
- Refit the loop module lid, ensuring LEDs are not damaged by the light pipe when refitting.
Specification
Operating temperature -10 to +55 °C
Storage temperature 5 to 30 °C
Humidity 0 to 95% non-condensing
Operating voltage 17 to 28 VDC
Operating current 17 mA (typical) 91mA (max.)
IP rating IP54
Operating frequency 868 MHz
Output transmitter power 0 to 14 dBm (0 to 25 mW)
Signalling protocol X
Panel protocol XP
Dimensions (W x H x D) 270 x 205 x 85 mm
Weight 0.95 kg
Location Type A: For indoor use
Specification Regulatory information
Manufacturer
Carrier Manufacturing Poland Sp. z o.o.
Ul. Kolejowa 24. 39-100 Ropczyce, Poland
Year of manufacture
See devices serial number label
Certification
13
Certification body
0905
CPR DoP
0359-CPR-0222
Approved to
EN54-17:2005. Fire detection and fire alarm systems.
Part 17:Short-circuit isolators.
EN54-18:2005. Fire detection and fire alarm systems.
Part 18:Input/output devices.
EN54-25:2008. Incorporating corrigenda September 2010 and March 2012. Fire detection and fire alarm systems.
European Union
EMS declares that this device is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following internet address: www.emsgroup.co.uk
Directives
2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see www.recyclethis.info
Dispose of your batteries in an environmentally friendly manner according to your local regulations.
Documents / Resources
![]() | EMS FCX-532-001 Loop Module [pdf] Installation Guide FCX-532-001 Loop Module, FCX-532-001, Loop Module, Module |