EMERSON logo

Operating instructions
EXD-SH1/2 Controller with ModBus communication
capability for electrical control valves

General information:

EXD-SH1/2 are stand-alone superheat and or temperature controllers. EXD-SH1 is intended for the operation of one bipolar electrical control valve whereas EXD-SH2 is designed for the operation of two independent bipolar electrical control valves. A table of the available application possibilities is listed below:

Controller  Circuit 1: Main function  Circuit 2: Main function 
EXD-SH1 Superheat or temperature control
EXD-SH2 Superheat or temperature control Superheat Control

Notes:
It is possible to use only circuit 1 from EXD-SH2. In this case, circuit 2 must be disabled (C2 parameter) and the sensors and the valve for the second circuit are not needed.
Modbus communication is described in a Technical Bulletin and it is not covered by this document.

Technical data:

Power supply 24VAC/DC +10%/-10% 50/60HZ,
Power consumption IDX-SH1: 25VA EX-SH2: 50VA
Plug-in connector Removable screw terminals wire size 0.14…1.5 mm2
Protection class WOO
Temperature sensors ECN-N… / TP1… (temperature range down to 45°C) ECN-Z… (temperature range down to -80°C ultra-low temperature)
Allowable operating/surrounding temperature 0…+55°C
Maximum cable distance between EXD-SH and EXD-PM 50 cm
AWG 18 wire size (> 1mm2)
Pressure sensors PT5N, PT5N-FLR or ratiometric probes
Output alarm relay current rating Resistive Load 24 V AC/DC, 1 A Inductive Load 24 V AC/DC, 0.5 A
Contact is closed: During alarm condition
Contact is open: During normal operation and supply power OFF
Stepper motor output Valves: EX4-8 (EX4-7-FLR)
CV4-7
Mounting For standard DIN rail
Marking ERC SYMBOLCE SYMBOL

warning 2 Warning:
EXD-SH1/2 (EXD-PM, ECP-024) has a potential ignition source and does not comply with ATEX requirements. Installation only in a non-explosive environment. For flammable refrigerants only use valves and accessories approved for it!
Dimensions (mm):EMERSON EXD-SH1 2 Controller

warning 2 Safety instructions:

  • Read operating instructions thoroughly. Failure to comply can result in device failure, system damage or personal injury.
  • It is intended for use by persons having the appropriate knowledge and skill.
  • Before installation or service disconnect all voltages from the system and device.
  • Do not operate the system before all cable connections are completed.
  • Do not apply voltage to the controller before completion of wiring.
  • Entire electrical connections have to comply with local regulations.
  • Inputs are not isolated, potential-free contacts needed to be used.
  • Disposal: Electrical and electronic waste must NOT be disposed of with other commercial waste. Instead, it is the user responsibility to pass it to a designated collection point for the safe recycling of Waste Electrical and Electronic Equipment (WEEE directive 2012/19/EU). For further information, contact your local environmental recycling center.

Temperature setting in the normal sense
(Controller function as temperature controller)EMERSON EXD-SH1 2 Controller- normal senseTemperature setting in the reverse sense
(Controller function as temperature controller)EMERSON EXD-SH1 2 Controller- normal sense 2

Electrical connection and wiring:

  • Refer to the electrical wiring diagram for electrical connections.
  • Note: Keep controller and sensor wiring well separated from supply power cables. Minimum recommended distance 30 mm.
  • When connecting the wires of the EXV-M… (an electrical plug of valves) consider the color coding as follows:
    EXV-M…: WH: White; BK: Black; BN: Brown; BL: Blue
  • The digital input DI1 (EXD-SH1/SH2) and DI2 (EXD-SH2) are the interfaces between EXD-SH1/2 and upper-level system controller if the Modbus communication has not been used. The external digital inputs must be free of potential (dry contact) and shall be operated in the function system’s compressor/demand.

EMERSON EXD-SH1 2 Controller- Wiring options

warning 2 Warning:

  • Use a class II category transformer for a 24VAC power supply. Do not ground the 24VAC lines. We recommend using individual transformers for the EXDSH1/2 controller and for third-party controllers to avoid possible interference or grounding problems in the power supply.
  • If EXD-PM is connected, it is mandatory to have an individual transformer for EXD-SH… and EXD-PM.
1 Circuit I (EXD-SH1/SH2) 14-17 Electrical control valve circuit 1 (ECV I) EXV-M… Electrical plug: wire colors WH-white BK-black BL-blue BN-brown
(2) Circuit 2 (EXD-SH2)
(3) Download/upload key 19-22 Electrical control valve circuit 2 (ECV2) EXV-M… Electrical plug: wire colors WH-white BK-black BL-blue BN-brown
I and 7 Supply voltage 24 VAC/DC
2 and 8 Temperature sensor circuit I 23 and 24 RS485 (+/-terminal)
3 and 8 Temperature sensor circuit 2 25 and 26 Alarm relay circuit I (C, NO) — Suitable for re
24 VAC/DC
4 and 5 PT5N… circuit I & circuit 2 (white wire: 4 — 20 mA signal) 27 and 28 Alarm relay circuit 2 (C, NO) — Suitable for 24 VAC/DC
9 + I2VDC Voltage input for PT5N… (brown wire) 29 and 30 contact,i Digital input c rcuit I (DI I) —Dry  potential-free
Alternative ratiometric third Party Pressure Transmitter: Warning: Read the note in the last page for limitation of error condition 31 and 30 Digital input circuit 2 (D12) — Dry contact, potential-free
4 and 5 Pressure transmitter circuit 1 & circuit 2 (0.5 – 4.5 V signal) 35 and36 Battery/Supercapacitor connection terminal
11 + 5 VDC voltage input 4 Fuse: EXD-SH I (IA), EXD-SH2 (2A)
10 GND Ground 6, 1213
18,32-34
Not used (Terminals on EXD-SH12)

*) Parameter 2uP with No. 9 = only pressure sensor circuit 1 is usedEMERSON EXD-SH1 2 Controller- arameter 2uP

Preparation for Startup:

  • Vacuum the entire refrigeration circuit.
  • Note: EX/CV valves are delivered partially open position. Do not charge the system with refrigerant before the closure of the valve.
  • Apply supply voltage 24V to EXD-SH1/2 while the digital input (DI1/DI2) is open. The valve will be driven to a close position.
  • After the closure of the valve, start to charge the system with refrigerant.

Setup of parameters:

(need to be checked/modified before system start-up)

  • Make sure that digital input (DI1/DI2) is open. Turn on the 24V power supply to EXD-SH1/2.
  • Parameters Password (H5), type of function (1Fct), refrigerant type (1u0/2u0), pressure sensor type (1uP/2uP) and valve scaling (1uF/2uF) need to be set according to system requirement and only when digital input DI1/DI2 is open. This feature is for added safety to prevent accidental damage of compressors and other system components.
  • Once the main parameters have been selected and saved, the EXD-SH1/2 is ready for startup. All other parameters can be modified at any time during operation or in system standby if it is necessary.

Display/keypad unit: (LEDs and button functions)

EMERSON EXD-SH1 2 Controller- keypad unit

Display description:

Selected main function
Su erheat control Temperature
control
Compressor
ON
Compressor
OFF
Upper display
shows
Superheat (K/F) Superheat (IUF) Controlled
temperature
(°C/F)
Lower display
shows
Valve opening
(%)
Suction pressure
(bar/ si )
Valve opening
(%)

Instant value display mode:

  • The controller displays the values of one circuit at a time, to change from one circuit to the other, pressFunction the button (Function only for EXD-SH2).
  • By pressing the Menukey, the instant value display mode can be activated/deactivated, which allows the user to check the measured/calculated values in real-time in a sequence shown as below table:
Value on upper display Code on the lower display
Superheat (K/F) SH
Valve opening (%) OPEn
Suction temperature (°C/°F) tASP
Suction pressure (bar/psig) PEuA
Saturation temperature (°C/°F tEuA
Software version: (0A) SH1 or SH2
Repeating display of values

Parameter configuration mode:

The configuration of parameters is protected by a numerical password. The default password is “12”. To enter the parameter configuration:

  • Press both the Downand SETbuttons for more than 5 seconds.
  • A flashing “0” is displayed in the upper and “PAS” at the lower.
  • Press UPuntil “12” is displayed; (password).
  • Press SETto confirm password.
  • Press UPor Downto show the code of the parameter (see table of parameter codes)  that has to be accessed/changed.
  • PressSET to choose and adjust the parameter value.
  • Press or to increase or decrease the value.
  • Press to temporarily confirm the new value. The selected value blinks a few times and the display shows the next available parameter code.
  • Repeat the procedure for other parameters if needed.

To exit and save the new settings:

  • When all parameters were changed pressMenu to save all the new values and exit the parameters modification procedure.

To exit and not save the new settings: 

  • Press SETandUP to cancel the parameter modification and delete any changes made.
  • Another way to exit without saving the changes made at the parameters is to not press any button for at least 120 seconds  (TIME OUT).
  • Note: While in parameter modification mode, the controller will display the parameter code on the lower display and the parameter value on the upper display.

Special manual functions: (Rest, clear)

  • Press both the DownandUP buttons for more than 5 seconds.
  • A flashing “0” is displayed.
  • Press UPuntil “12” is displayed; (if default password has been changed, it must select the new password)
  • PressSET to confirm password
  • Select the special function as explained at the parameter configuration mode

The special functions are:

Displayed Value Code
Factory Reset -Fdt
Clear Alarms (only manual reset) ALrr
  • The default value for each variable is 0, when it set to 1 it will trigger the corresponding function.
  • The factory reset of the controller (-Fdt) is possible when digital input DI1/DI2 is open.

Manual Valve operation (service /maintenance):

  • Press SETfor more than 5 seconds Select, modify and save the variables as explained at the parameter configuration mode
Code Parameter description and choices Min
4
Max Factory setting, Field
setting
1Ho Manual mode operation; circuit 1 0 = disabled 1 = Enabled 0 1 0
1HP Valve opening (%) 0 100 0
2Ho Manual mode operation; circuit 2 0 = disabled 1 = Enabled 0 1 0
2HP Valve opening (%) 0 100 0

Note: During manual operation, functional alarms such as low superheat are disabled. It is recommended to monitor the system operation when the controller is operated manually. Manual operation is intended for service or temporary operation of the valve at a specific condition. After achieving the required operation, set the parameter 1Ho and 2Ho at 0 so the controller automatically operates the valve(s) according to its setpoint(s).
List of parameters in scrolling sequence by pressing the Downbutton:

EMERSON EXD-SH1 2 Controller- List of parametersEMERSON EXD-SH1 2 Controller- List of parameters 2

warning 2 Warning -Flammable refrigerants:
EXD-SH1/2 (EXD-PM, ECP-024) has a potential ignition source and does not comply with ATEX requirements. Installation only in a non-explosive environment. For flammable refrigerants only use valves and accessories approved for it!
MOP default value table (°C):

Refr. Min. Max. (C°) Refr. Min. Max. (C°) Refr. Min. Max. (C°)
R22 -70 +50 +13 R23 -70 -18 -40 R452B -45 +66 +25
R134a -57 +66 +15 R32 -52 +30 +15 R454B -40 +45 +18
R507 -75 +42 +7 R1234ze -57 +66 +24 R454A -57 +66 +10
R404A -76 +42 +7 R448A -57 +66 +12 R452A -45 +66 +15
R407C -66 +48 +15 R449A -57 +66 +12 R444B -45 +66 +15
R410A -52 +30 +15 R450A -57 +66 +19 R455A -57 +66 +14
R124 -45 +91 +50 R513A -57 +66 +13 R1233zde -45 +90 +15
R744 -40 -4 -5 R290 -66 +48 +15 R1234yf -52 +66 +15
R407A -66 +48 +10 R1270 -66 +48 +15
R407F -66 +48 +10 R454C -66 +48 +17

Control (valve) start- up behavior factory settings

(1uu + 1u9) / (2uu +2u9)

EMERSON EXD-SH1 2 Controller- factory settings

EX4/5/6   ≤ 5.3 Seconds
EX7 ≤ 5.6 Seconds
EX8 ≤ 5.9 Seconds
CV4 ≤ 5.3 Seconds
CV5/6 ≤ 5.3 Seconds
CV7 ≤ 6.6 Seconds

Upload/download Key: Function

For serial production of systems/units, upload/download key allows the transmission of configured parameters among range of identical systems.
Uploading procedure (storing configured parameters in key):

  • Insert the key while the first (reference) controller is ON and press the UPbutton; the “uPL” message appears followed by the “End” message for 5 seconds.
  • Note: If the “Err” message is displayed for failed programming, repeat the above procedure.

Downloading procedure (configured parameters from key to other controllers):

  • Turn off power to the new controller.
  • Insert a loaded Key (with stored data from the reference controller) into the new controller and turn on the power supply.
  • The stored parameters of the key will be downloaded automatically into the new controller memory; The “doL” message appears followed by an “End” message for 5 seconds.
  • The new controller with the new loaded parameters setting will start to operate after the “End” message disappears.
  • Remove the key.
  • Note: If the “Err” message is displayed for failed programming, repeat the above procedure.

EMERSON EXD-SH1 2 Controller- programming

Error/Alarm handling:

Alarm code Description Related parameter Alarm relay Valve What to do? Requires clear alarm after
resolving alarm
1E0/2E0 Pressure sensor circuit 1/2 error Triggered Fully close Check wiring connection and measure the signal. No
1E1/2E1 Temperature sensor circuit 1/2 error Triggered Fully close Check wiring connection and measure the resistance of the sensor. No
1 Valve Circuit 1/2 electrical connection error Triggered Check wiring connection and measure the resistance of the winding. No
AFE 1/2 Freeze protection circuit 1/2 I P4/2P4: I Triggered Fully close Check the system for causes of low pressure such as insufficient load on the evaporator. No, if it is ON
AFE 1/2 1P4/2P4:2 Triggered Fully close Yes if it is blinking
LSH 1/2 Low superheat (<0,5K) 1uL/2uL: I Triggered Fully close Check wiring connection and operation of valve. No if it is ON
LSH 1/2 luL/2uL:2 Triggered Fully close Yes if it is blinking
t4L1 Min. temperature alarm 1 tAL Triggered Fully close Check wiring connection, operation of valve, size of valve and load. No
t4H1 Max. temperature alarm I tAH Triggered Fully close No
HSH 1/2 High superheat circuit 1/2 luH/2uH: I Triggered Operating Check the system. No
LOP 1/2 Low-pressure circuit 1/2 1P9/2P9 1 Triggered Operating Check the system for cause of low pressure such as refrigerant loss. No if it is ON
LOP 1/2 1P9/2P9 2 Triggered Operating Yes if it is blinking
EA Failed uploading/downloading Repeat again the procedure for uploading/downloading. No
ACEr Modbus Timed Out Check Modbus communication. Note: Modbus alarm (Acer) detection is active only when the pressure sensor type is configured to be Modbus type and the corresponding circuit is on demand. No
PFA Power failure alarm Triggered Fully close When the controller is connected to the battery supply and the power supply is interrupted, this alarm code will be displayed while the valve is closing. No

ACF1 or ACF2: Alarm code (circuit1/2) for “not permitted configuration/ selection” Alarm will be displayed for the following cases:

  • If two circuits of the EXD-SH2 are connected to two different types of pressure transducers i.e. 4-20 mA and 0-5 V. It is mandatory that two circuits always are connected to the same type of pressure transmitter technology.
  • The temperature control function is possible only with EX4-8 series valves. If other valves are used, then the ACF alarm will be displayed.
  • Ratiometric pressure transmitters cannot be selected in conjunction with R744.

Notes:

  • When several alarms are present, the alarms will be shown one after the other on the lower display.
  • Pressure sensor error for third-party ratiometric pressure transmitters is based on the detection of interruption of two wires (5 V  and signal 0.5 – 4.5 V). If only third wire (ground) is open/ interrupted, no error can be detected and the controller will receive a false signal between 50% and 100% higher. This false signal leads to improper operation of the EXD-SH1/2 controller and can lead to system/compressor damage. EMERSON is not responsible in such cases.

Service / Troubleshooting:

Symptom Cause Action
Operating superheat is several degrees higher or lower than set-point The incorrect signal from pressure or temperature sensors I- Check the sensors (see list of parameters)
2- Make sure the sensor cables are not installed along with other high voltage cables
Operating superheat is too low i.e. compressor wet running I – Incorrect wiring of ECVs 2- Defective sensors I- Check the wiring 2- Check the sensor
Valve is not fully closed I – The digital input is ON
2- Wrong setting of parameter ut.
I – Valve is shut off only when the digital input is turned off. 2- Check the setting of parameter ut.
Instable superheat (hunting) The evaporator is designed to operate at higher superheat Increase the superheat set-point.
Valve opens when EXD commands to close and vice versa Wrong wiring between EXD-SH… and valve Correct the wiring.
EX8 is not able to open at high differential pressure Wrong setting of parameter ut Check the parameter ut. (Larger valve requires higher torque and higher current)
Superheat set-point is shifting after several months of uninterrupted operation or permanent jumper of 24 V digital input Stepper motor driven valves require synchronization Do not jumper digital input permanently. Interrupt digital input once every week for 10 seconds if the compressor never stops.

Emerson Climate Technologies GmbH
Am Borsigturm 31 I 13507 Berlin I Germany
www.climate.emerson.com/en-gb

Documents / Resources

EMERSON EXD-SH1/2 Controller [pdf] Instruction Manual
EMERSON, EXD-SH1, 2 Controller, with, ModBus, communication

References

Leave a comment

Your email address will not be published. Required fields are marked *